NOTE:

 To return to factory calibration settings, enter all zeros for both SPAN and OFST.

Setting the Latch Mode (Manual Reset) 

The Safety Relay Output can be configured to latch open when the set point is reached.  Refer to the Programming Flowchart on page 

19.
•  LCH1: In the Programming Mode, press the right 

g

 button.  

•  If OFF is displayed, press the left 

2

 button to set LCH1 to ON.

•  Press the right 

g

 button to set the latch.  When latch mode is on (set), the Safety Relay Output changes state from closed to open 

when the set point is crossed and remains latched until the Safety Relay Output is manually reset by the user or the One Series 

Field Safety System™

 is power cycled.

When latched, the display will read MAN RSET.
To Reset the Latch
•  Enter the Programming Mode (see page 10).  If the Latch is set, the display will read MAN RSET.  To return to the Process Display 

without resetting the latch, press the right 

g

 button.

•  To continue programming without resetting the latch, press the left 

2

 button.

•  Press both 

2g

 buttons to reset the latch.  The display now reads RSET DONE.

•  Press the right 

g

 button to return to the Process Display.

•  Press the left 

2

 button to continue Programming.

Setting the Plugged Port Feature

The One Series 

Field Safety System™

 IAW™

 

self-diagnostics have the ability to detect that the process port may be plugged.  It does 

this by monitoring the sensor for changes over time.  The amount of change and the time period are programmable.  If the process 

variable does not change by the amount and selected time period, the display will indicate PLUG and the IAW™

 

Output will open, indicat-

ing a fault.  Refer to the Programming Flowchart on page 19.

•  Enter the Programming Mode and press the left 

2

 button until PLUG PORT is scrolling on display.  Press the right 

g

 button.

•  There are four possible selections -

•  OFF - This disables the plugged port function and is the default setting.  This should be done where sensor plugging is 

not a concern or where the system pressures may not change over time (example: a storage tank).

•  1 minute
•  1 Hour           Maximum time with no process variation before fault indication
•  24 Hours

•  Using the left 

2

 button, select a time.

•  If OFF is selected, press the right 

g

 button to return to the PLUG PORT command and leave Plug Port deactivated.

•  Press the right 

g

 button to enter a process value < 10% of the sensor’s maximum range.  This number represents the minimum 

variation expected in the process value over the time period entered above under normal operating conditions.  Each time the 
process value reaches this value, the Plug Port timer is reset.

NOTE:

 This value can be accurately determined by subtracting the minimum from the maximum process value as recorded by the MAX/

MIN feature.  See RESETTING MAXIMUM AND MINIMUM VALUES on page 12 for additional information.

}

Summary of Contents for Field Safety System One Series

Page 1: ...HAZARDOUS AND THE FOLLOWING HAZARDOUS LOCATIONS AND IS ATEX AND IECEX CERTIFIED SUITABLE FOR APPROPRIATE USE IN GAS AND DUST ZONE 1 APPLICATIONS Model 2SLP N America Europe International Flameproof Ce...

Page 2: ...eries transmitter switch product line is based on an all solid state electronic module that incorporates a microprocessor The One Series Field Safety System is a loop powered all in one device connect...

Page 3: ...y pushing the right g button once the display will scroll as follows SP1 XX XX DB1 XX XX SP2 XX XX DB2 XX XX By pushing the left 2 button once the display will scroll the min max process values record...

Page 4: ...re that the sensor housing will not be damaged and where the measured temperature is representative of the surrounding environment For Local Spring Loaded model T A suitable thermowell made from corro...

Page 5: ...ved Tools Required Small flat head screwdriver wire strippers TO PREVENT IGNITION DISCONNECT POWER BEFORE REMOVING ENCLOSURE COVER KEEP COVER TIGHT WHILE IN OPERATION DO NOT DISCONNECT EQUIPMENT UNLES...

Page 6: ...diagnostics to determine the integrity of the SRO wiring and if the SRO is functioning properly NOTE As an alternative to loop power model 2SLP may be wired directly to a 24 VDC power supply and minus...

Page 7: ...t function as normal NOTE The 4 20 mA analog signal is not possible in this wiring configuration In this configuration the 4 20 mA output and IAW Output are monitored by the safety system logic solver...

Page 8: ...Field Safety System fully configured where the health status IAW and SRO switch status signals are being monitored by a logic solver PLC or DCS These connections are not required however UE recommend...

Page 9: ...00 0 39 714 3 1045 5 40 761 9 1090 9 No Fault Displayed 4 20 mA Normal Operating range Unused Fault 3 6 3 8 mA Normal Under range 4 20 20 5 mA Normal Over range 21 0 mA 21 0 mA only when the temperatu...

Page 10: ...t 2 button increments the blinking digit The right g button sets the digit and moves to the next Once a valid password is entered OK will appear on the display Press and release the right g button CLR...

Page 11: ...opens on falling process values that reach the set point OPEN WINDOW The Safety Relay Output opens when process values are within a specified range set by two points set point high and set point low P...

Page 12: ...6 Resetting the Maximum Minimum Values The One Series Field Safety System continuously records the readings from the sensor and stores the minimum and maximum MAX MIN peak hold values in non volatile...

Page 13: ...and change the offset Zero is the factory setting Press the left 2 button to increment the blink ing digit Press the right g button to enter and move to the next digit Press the right g button to ente...

Page 14: ...ity to detect that the process port may be plugged It does this by monitoring the sensor for changes over time The amount of change and the time period are programmable If the process variable does no...

Page 15: ...ations it is desirable to dampen the Safety Relay Output response and prevent intermittent false trips due to pressure spikes or other transient isolated events The Filter feature provides a software...

Page 16: ...left 2 button to change to NEG Press the right g button to view and change the scale Press the left 2 button to increment the blinking digit Press the right g button to enter and move to the next digi...

Page 17: ...en check all sensor connections E 16 Diagnostic Fault Sensor SHORT A short circuit has been detected on the sensor drive pins 2 3 Diagnostic Fault Sensor Short check all sensor connections E 18 Diagno...

Page 18: ...ORIGINAL DATE DRWN CHKD APPD DO NOT SCALE THIS DRAWING DOC DE733010102 Rev B EM ONE SERIES 1X NAMEPLATE A 6211 847 SR 5 14 15 6211 847 DESCRIPTION DATE DRWN APPD UNLESS OTHERWISE SPECIFIED DIMENSIONS...

Page 19: ...end on sensor range Invalid PWORD BOTH Abort NO RESET OK Flash Err Abort BDOOR PWORD Valid SAVING SAVING One Series Field Safety System LCH1 ON OFF OFST POS NEG 8888 Set Blinking Digit Increments Blin...

Page 20: ...R PORT 1 2 14 NPT SENSOR PORT 1 20 NPT SENSOR PORT 1 20 NPT SENSOR PORT 111 92 mm 76 2 mm 133 35 mm 12 7 mm SURFACE MOUNTING KIT 6361 704 144 78 mm 134 62 mm 137 16 mm 154 94 mm 134 62 mm 137 16 mm 26...

Page 21: ...LATED CABLE 0 125 3 18 mm FOR DC UNITS 0 250 6 35 mm 1 2 NPT COMPRESSION FITTING 300 SERIES st st 26 AWG STRANDED TEFLON INSULATION 4 50 114 3 mm FIXED DIM EPOXY SEAL 2 00 50 8 mm FIXED DIM 1 2 14 NPT...

Page 22: ...e de fil lectrique Ne pas monter l unit des temp ratures ambiantes d passant les limites publi es Cela est particuli rement important pour les unit s de tem p rature montage locale L utilisation enve...

Page 23: ...avant de retirer le couvercle du bo tier Maintenir le couvercle ferm pendant le fonctionnement Ne pas d con necter l quipement que lorsque l alimentation est coup e ou que la zone est connue pour tre...

Page 24: ...r personnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit accord ing to local and national elect...

Reviews: