background image

u

 

ZIGBEE POWER SWITCH S2(-R)

 

REFERENCE MANUAL 

 

 

Summary of Contents for ZIGBEE S2(-R)

Page 1: ...u ZIGBEE POWER SWITCH S2 R REFERENCE MANUAL...

Page 2: ...ecific to your region is available as a separate document and is included in printed form in the product package If you have any questions or need additional support please visit the support pages tha...

Page 3: ...Cluster Server 13 7 2 3 Groups Cluster Server 14 7 2 4 Scenes Cluster Server 14 7 2 5 On off Cluster Server 15 7 3 Application Endpoint 2 On off Output 2 17 7 3 1 Basic Cluster Server 17 7 3 2 Identi...

Page 4: ...32 Device Management 27 7 7 1 Basic Cluster Server 27 7 7 2 Identify Cluster Client 28 7 7 3 Commissioning Cluster Server 28 7 7 4 Over the Air Upgrade Cluster Client 28 7 7 5 Device Setup Cluster Ser...

Page 5: ...tralized and distributed security networks as router Supports forming simple centralized security networks as Coordinator and Trust Center Supports forming distributed security networks as router Thre...

Page 6: ...ng maintenance or early stages of system integration In this mode the ZigBee interface is operational and you can run OTA firmware upgrades for example However the inputs and outputs are non operation...

Page 7: ...e times slowly to indicate it is operating as a router on the network ten times slowly to indicate that it is operating as a coordinator and trust center or blink quickly to indicate it is searching f...

Page 8: ...g Binding procedure EZ mode on an initiator or target endpoint Target endpoints will enter identify mode for three minutes Initiator endpoints will query targets and create suitable bindings to these...

Page 9: ...is reached wait for the LED to blink the selected number of times Then press a single time to accept the selection or wait for three seconds to cancel the command The LED will blink one time to confir...

Page 10: ...parent for sleeping end devices S2 provides nine ZigBee application endpoints Endpoint Profile Application 0 0x00 0x0000 ZigBee Device Profile ZigBee Device Object ZDO standard management features 1 0...

Page 11: ...the following example ubisys2 R0 001FEE00000000FF 0F7C1CD805F91649EBA84580AA1CB432F51A 21 Here ubisys2 is the data format identifier R0 is the model string this is just an example it would be S2 or S2...

Page 12: ...in the network parent_annce parent_annce_rsp14 Parent announcement response This is part of the ZigBee 2015 end device child management feature system_server_discovery_req system_server_discovery_rsp...

Page 13: ...ssed using the group address This is also a prerequisite for scenes You may also query group membership and delete group associations 0x0005 Inbound Server Scenes Allows storing one or more scenes per...

Page 14: ...scenes that refer to any of the existing groups 0x05 Add Group if Identifying Adds this endpoint to the group if the endpoint is identifying 7 2 4 Scenes Cluster Server Attributes supported Attribute...

Page 15: ...g reporting targets Currently there is no default reporting configuration in place so you need to configure reporting if you want to receive feedback on state changes Attributes supported Attribute Ty...

Page 16: ...ate switching element 0x40 Off with effect19 Turns the output off after having stored the current setting as the global scene and rejects further global scene storage requests by the On with recall gl...

Page 17: ...ssed using the group address This is also a prerequisite for scenes You may also query group membership and delete group associations 0x0005 Inbound Server Scenes Allows storing one or more scenes per...

Page 18: ...scenes that refer to any of the existing groups 0x05 Add Group if Identifying Adds this endpoint to the group if the endpoint is identifying 7 3 4 Scenes Cluster Server Attributes supported Attribute...

Page 19: ...only GlobalSceneControl21 Determines whether the next Off with Effect command will store the global scene 0x4001 unsigned16 read only OnTime21 Time in tenths of a second the device remains on before i...

Page 20: ...requests by the On with recall global scene command until the device is turned on again or the global scene has been restored 0x41 On with recall global scene21 Restores the global scene Despite the...

Page 21: ...e is currently identifying and returns the remaining time if so 7 4 3 Scenes Cluster Client This cluster is available on devices running firmware version 1 03 and above Notice This cluster does not us...

Page 22: ...of devices on 0x02 Toggle Toggles the target device state Should not be used to control groups 7 4 5 Level Control Cluster Client Notice This cluster uses the binding table for managing command target...

Page 23: ...ce is currently identifying and returns the remaining time if so 7 5 3 Scenes Cluster Client This cluster is available on devices running firmware version 1 03 and above Notice This cluster does not u...

Page 24: ...of devices on 0x02 Toggle Toggles the target device state Should not be used to control groups 7 5 5 Level Control Cluster Client Notice This cluster uses the binding table for managing command target...

Page 25: ...ctive power reactive power apparent power RMS voltage RMS current power factor etc 7 6 1 Basic Cluster Server Please refer to section 7 7 1 for details 7 6 2 Metering Cluster Server Notice This cluste...

Page 26: ...vered positive or generated negative reactive power in VAr 0x0306 unsigned32 read only TotalApparentPower Total of delivered positive or generated negative apparent power in VA 0x0505 unsigned16 read...

Page 27: ...nd when to install the downloaded image 0xFC00 Inbound Server Device Setup This is a manufacturer specific cluster used for basic device setup For example it can be used to assign physical inputs to e...

Page 28: ...this endpoint is used for push button commissioning Cluster commands transmitted Command Description 0x01 Query Identify This command is broadcast during push button commissioning to identify suitable...

Page 29: ...case of S2 this is the white wire Factory default value 0x00 0x0001 Configuration options for high voltage physical input 2 Defines the configuration for the physical input marked with a switch symbol...

Page 30: ...nstruction shall be executed Field Bit s Description HasAlternate 7 0x80 When this bit is set there is another instruction that shall be executed in alternating order with the current one each time th...

Page 31: ...the universal input logic unique to ubisys ZigBee devices This can be a simple toggle command or a more complex move or recall scene command for example Notice that S2 and S2 R will use their binding...

Page 32: ...0006 on off 02 ZCL Command Template Toggle 06 element 2 six bytes 01 InputAndOptions 0x01 0D Transition released pressed 04 Source Endpoint 4 hosts secondary on off client cluster on S2 06 00 Cluster...

Page 33: ...nidirectional and bidirectional23 GPDs Attributes supported Attribute Type Description 0x0000 unsigned8 read only gpsMaxSinkTableEntries The number of sink table entries supported by this device 0x000...

Page 34: ...d Description 0x01 GP Pairing Creates updates or removes proxy table entries 0x02 GP Proxy Commissioning Mode Makes the proxy enter commissioning mode for a particular sink or leave commissioning mode...

Page 35: ...rovides enhanced support for latest generation Green Power generic switches with the ability to distinguish short 1 second and long 1 second presses In fact a generic switch behaves like a physical sw...

Page 36: ...blocks supported by this device 0x0017 bitmap24 read only gppActiveFunctionality Allows to disable certain Green Power features on this device 0x0020 bitmap8 persistent gpSharedSecurityKeyType Determi...

Page 37: ...from a Green Power Device to one or more sinks or groups of sinks 0x04 GP Commissioning Notification Tunnels GP frames from a Green Power Device to a sink in commissioning mode 0x0B GP Proxy Table Res...

Page 38: ...sions Figure 2 Rail mount ZigBee Dual Power Switch S2 R Dimensions Funkvernetzt mit Stromverbrauchsmessung Leistungsschalter S2 230 V 50 Hz 2 x 500 VA 2 1 2 1 43 mm 12 mm 143 mm 47 mm 12 mm Funkvernet...

Page 39: ...ilable Use the specified order code for your orders Please contact ubisys support if you require any customization Order Code Description 1069 ZigBee Dual Power Switch S2 in wall flush mount 1168 ZigB...

Page 40: ...ERMS CONDITIONS OF BUSINESS When placing your order you agree to be bound by our General Terms Conditions of Business Allgemeine Gesch ftsbedingungen which are available for download here http www ubi...

Page 41: ...MC 2014 35 EU Low Voltage Directive LVD 2012 19 EU Waste Electrical and Electronic Equipment Directive WEEE 2011 65 EU Restriction of Hazardous Substances Directive RoHS EN 300 328 V2 2 2 ERM Wideband...

Page 42: ...ry reset it will broadcast a network leave indication 1 5 11 11 2015 Updated the ZDO description to include enhancements and additions made for ZigBee 2015 platform compliance 1 6 11 19 2015 Enhanceme...

Page 43: ...43 www ubisys de u 13 CONTACT UBISYS TECHNOLOGIES GMBH NEUMANNSTRASSE 10 40235 D SSELDORF GERMANY T 49 211 54 21 55 00 F 49 211 54 21 55 99 www ubisys de info ubisys de...

Reviews: