93
106375-01 - 4/16
XI. Start-Up and Checkout
(continued)
DANGER
Asphyxiation Hazard. Failure to properly convert this boiler for use on LP Gas (propane) can cause
unreliable operation at elevated carbon monoxide (CO) levels, resulting in personal injury or death.
NOTICE
To minimize the risk of premature heat exchanger failure, observe the following water chemistry requirements:
1) Minimize the introduction of make-up water, dissolved oxygen, and contaminants into the boiler by following
the installation guidelines shown in the “Water Quality and Boiler Water Additives Note” on Page 67.
2) Make sure the system is filled with water meeting the following criteria:
• pH between 6.6 and 8.5
• Chloride level less than 125PPM. If fill water is drawn from a system containing a water softener, test a
sample of the fill water to confirm that this criteria is met.
• Hardness less than 7 grains/gallon.
• Iron level less than 0.5PPM.
• Copper level less than 0.1PPM.
3) Avoid the use of petroleum based boiler additives. These can attack seals in both the boiler and system.
4) If freeze protection is required, use the following or its equivalent:
• Fernox Alphi -11 (inhibited Propylene Glycol). U.S. Boiler Part # 101146-01 is for a 5 gallon bucket.
• Sentinel
®
X500 Inhibited Antifreeze (combined antifreeze and inhibitor)
Refer to the antifreeze manufacturer’s instructions for required dosage. In general these products are a blend
of glycol (for freeze protection) and inhibitors (to protect the glycol from attacking metallic system components).
Do not add any more antifreeze than is necessary to protect the system from freeze damage. Many of these
products require annual testing of the system water to ensure that the inhibitors are still active; consult the
manufacturer’s instructions for maintenance requirements. Allowance must be made for the additional expansion
of the glycol solution.
5) For system cleaning, use the following or its equivalent:
• Fernox Cleaner F3
• Sentinel
®
X400 System Restorer (For Older Closed Loop Hydronic Heating Systems)
• Sentinel
®
X300 System Cleaner (For New Heating Systems)
• Sentinel
®
X100 Inhibitor (For Protecting Closed Loop Hydronic Heating Systems Against Lime scale And
Corrosion)
Refer To the instructions supplied with the cleaner for proper dosage and use.
Fernox products are available from Alent plc Consumer Products Division, 4100 6th Avenue, Altoona PA.
(972) 547 6002 ([email protected]).
Sentinel
®
products are available from Douglas Products and Packaging, 1550 E. Old 210 Highway, Liberty, MO
64068, Tel:(877) 567-2560 (Toll Free) and/or selected HVAC distributors.
WARNING
Poison Hazard. Use only inhibited propylene glycol solutions specifically formulated for hydronic systems.
Do not use ethylene glycol, which is toxic and can attack gaskets and seals used in hydronic systems. Use
of ethylene glycol could result in property damage, personal injury or death.