41
APPENDIX A – COMBUSTION AIR
PROVIDE ENOUGH AIR to ventilate the
boiler room, dilute the flue gases, and
sustain combustion. Ignition failure, overheating,
fire, carbon monoxide, and spillage of flue gases
may result from poor air supply.
If the boiler is a Direct Vent boiler and exchanges
all combustion air and combustion products
directly with the outdoors, there are no special
requirements for providing combustion, ventilation,
and dilution air.
If the boiler is chimney vented, power vented or
induced draft and draws combustion air from within
the building, follow the steps below to determine
how to provide air to the boiler.
Is the boiler located in a confined space?:
1.
Calculate the floorspace (in square feet) of
the boiler room and all rooms connected
to the boiler room by passageways not
furnished with doors.
___________ floorspace (sq. ft.)
2.
Add up the input rates of all the combustion
appliances installed in the same floorspace.
combined appliance
___________ input (BTU/hr)
3.
In the table below, find the Minimum
Allowable Floorspace based on the
Combined Input Rate from Step 2 and the
ceiling height. If the Combined Input Rate
is between two rates, use the next highest
rate.
minimum allowable
___________ floorspace (sq. ft.)
4.
If the Floorspace from Step 1 is
less than
the
Minimum Floorspace from Step 3, then you
must provide outdoor air to the boiler room.
Proceed to Step 6.
Is the boiler located in a building of unusually tight
construction?
5.
If the answer to
all
of the three questions
below is “yes”, then you must provide
outdoor air to the boiler room.
Do the walls and ceilings exposed to the
outside atmosphere have a continuous
water vapor retarder with a rating of 1 perm
or less, with openings gasket or sealed?
Yes
No
Are operable windows and doors
weatherstripped?
Yes
No
Are exterior wall joints caulked or sealed?
Yes
No
6.
If you must provide outdoor air to the boiler
room, the top of the permanent opening
into the boiler room must be within 12” of
the ceiling, and the free area of the opening
(sq. in.) must be no less than the Combined
Appliance Input (from Step 2) divided by
3000 BTU/hr/sq. in.
combined appliance
__________ input (Step 2)
÷
3000
BTU/hr/sq. in.
Minimum
Opening
Size
__
___
(sq. in.)
7.
Duct this opening vertically or horizontally
directly to the outdoors, or directly to a
space that communicates directly with the
outdoors, such as an attic or crawlspace.
Minimum Allowable Floorspace in the Boiler Room
and Freely Connected Rooms (sq. ft.)
Ceiling Height
7’
8’
9’
10’
Combined
Appliance
Input Rate
(see Step 2)
(BTU/hr)
50,000
357
313
278
250
100,000
714
625
556
500
150,000
1071
938
833
750
200,000
1429
1250
1111
1000
250,000
1786
1563
1389 1250
300,000
2143
1875
1667 1500
350,000
2500
2188
1944 1750
400,000
2857
2500
2222 2000
For more details and options, refer to the
National
Fuel Gas Code
(
ANSI Z223.1/NFPA 54
)
, or
applicable provisions of local building codes.
Summary of Contents for ESC
Page 7: ...7 Figure S 1 Minimum Clearances to Combustibles SPECIFICATIONS continued...
Page 20: ...20 Figure 10 d Operating Instructions 10 Perform Startup Checks and Adjustments continued...
Page 37: ...37 Internal Wiring Figure IW 1 Wiring Diagram...
Page 38: ...38 Internal Wiring continued Figure IW 2 Wiring Diagram...