![U.S. Boiler Company ASPEN ASPN-320 Installation, Operating And Service Instructions Download Page 116](http://html1.mh-extra.com/html/u-s-boiler-company/aspen-aspn-320/aspen-aspn-320_installation-operating-and-service-instructions_3134541116.webp)
116
107750-01 - 9/17
XII. Operation
F. Changing Adjustable Parameters (continued)
The Control is shipped with defaults that will provide improved operation. Adjustment is only required to optimize setup.
The expected heat rate adjustment is used to better match boiler output to the home heating needs. After receiving a “call for
heat” the Control first uses the expected heat rate value to set a maximum heat rate. The maximum heat rate is the highest heat
rate that the boiler can fire to at that moment. The maximum heat rate is the summation of the expected heat rates for the active
(turned on) zones. After establishing the maximum heat rate the Control then measures water temperature and fires the boiler only
as hard as required for the heat demand.
Expected Heat Rate Adjustment Screens (HeatMatch Software)
Example “call for heat”
durations for a four zone
house.
Maximum heat rate
limits firing rate and
prevents the Control
from firing to 100% in
response to a smaller
zone demands.
Maximum Heat Rate:
Automatically adjusted
by the Control based on
the size and number of
zones calling for heat.
Actual Heat Rate:
Boiler is free to
modulate based on
temperature from
minimum to maximum
heat rate.
Figure 12.11: Four Zone House (with Zone Control Connected)
Figure 12.12: Expected Heat Rate Adjustment (with Zone Control Connected)
Summary of Contents for ASPEN ASPN-320
Page 88: ...88 107750 01 9 17 Figure 10 4 Proper Installation of Header Sensor X Wiring continued ...
Page 89: ...89 107750 01 9 17 Figure 10 5 Internal Wiring Ladder Diagram X Wiring continued ...
Page 90: ...90 107750 01 9 17 X Wiring continued CONDENSATE FLOAT SWITCH ...
Page 91: ...91 107750 01 9 17 X Wiring continued Figure 10 6 Internal Wiring Connections Diagram ...
Page 100: ...100 107750 01 9 17 Operating Instructions XI Start Up and Checkout continued ...
Page 145: ...145 107750 01 9 17 XV Service Parts continued ...
Page 147: ...147 107750 01 9 17 XV Service Parts continued All Models ...
Page 149: ...149 107750 01 9 17 XV Service Parts continued All Models ...
Page 151: ...151 107750 01 9 17 XV Service Parts continued All models ...
Page 157: ...157 107750 01 9 17 ...
Page 158: ...158 107750 01 9 17 ...
Page 159: ...159 107750 01 9 17 ...