![Tynetec Advent XT2 Installation Manual Download Page 27](http://html1.mh-extra.com/html/tynetec/advent-xt2/advent-xt2_installation-manual_1186910027.webp)
Doc No. FM0804 issue 4 Page 27
Options DIL switch
6 in the intercom
must be ON when
strobes are
connected
MASTER
EXTENSION
MASTER
Fit Link
LK1
in position
B
Fit Link
LK2
in position
A
Set Options DIL switch
5 OFF
EXTENSION
Fit Link
LK1
in position
A
Fit Link
LK2
in position
B
Set Options DIL switch
5 ON
NOTE
In master or extension mode you
must also set the intercom type
on Options DIL switch 2:
OFF for standard
ON for door entry
16. INTERCOM UNIT AUXILIARY DEVICES
STROBE LIGHTS
EXTENSION INTERCOM
Intercom
Strobe
24V
24V
0V
0V
18
RS485+
19
RS485-
Strobe lights can be connected to standard or door entry intercoms to
provide visual indication when a call exists.
Advent XT2 Master Strobe Part No
’s:
ZSL060 (blue) and ZSL065 (clear).
When connected to a standard or door entry intercom the blue strobe will
flash for 20 seconds when the intercom is called in warden call mode.
When connected to a door entry XT2 intercom the clear strobe will flash
for 20 seconds when the intercom is called in door entry mode.
DIL switches inside the strobe select if it flashes on a warden call or door
entry call and if it is connected as the main (primary) or extension
(secondary) strobe. Max 4 strobes per door entry intercom.
A second Advent XT2 intercom can be connected as an extension to provide
audio in another room within the same dwelling.
Use a 6 pair CW1308 cable between the master and extension intercoms.
If the master intercom is a standard type then the extension should also be a
standard intercom, if the master is a door entry type then the extension can be
either a door entry type or a standard type (if door entry functions are not
necessary on the extension). Only 1 extension can be connected per intercom.
Other auxiliary devices e.g. pullcords, smoke detectors etc. are normally
connected to the master.
DIL Switch
OFF
ON
1
Warden Call
Door Entry
2
Primary
Secondary
ZSL060 (Blue)
Warden Call Primary
SW1 OFF & SW2 OFF
ZSL060 (Blue)
Warden Call Secondary
SW1 OFF & SW2 ON
ZSL065 (Clear)
Door Entry Primary
SW1 ON & SW2 OFF
ZSL065 (Clear)
Door Entry Secondary
SW1 ON & SW2 ON
ZSL060/65 DIL SWITCH SETTINGS