EQUIPMENT:
T1200-C
PUBLICATION:
MARINEC-P-A
ISSUE No. & DATE:
3
02/14
© 2014 Thorn Security Ltd
PAGE 39 of 67
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
15. Compatible Field Devices
The T1200 panels are compatible with the devices listed in section 15.1.
15.1 Field Device Part Numbers
Manufacturer
Part no.
Description
Standby
Current
(mA)
Max.
Devices
per zone
Thorn/Tyco
MF601M
Smoke Detector Ionisation [marine]
0.050
24
Thorn/Tyco
MR601M
Smoke Detector Optical [marine]
0.050
24
Thorn/Tyco
M600
Series 600 Universal Base [marine]
N/A
N/A
Thorn/Tyco
MR601T
High Performance Smoke Detector Optical
0.050
24
Thorn/Tyco
MD601
Heat Detector Rate Of Rise
0.050
24
Thorn/Tyco
CP230
Manual call point
0.000
32
Thorn/Tyco
CP200
Manual call point
0.000
32
Tyco
H600
Heat Detector Fixed Temperature
0.000
32
Tyco
H601
Heat Detector Fixed Temperature
0.000
32
Tyco
H602
Heat Detector Fixed Temperature
0.000
32
Tyco
H604
Heat Detector Fixed Temperature
0.000
32
Tyco
H900
Heat Detector Fixed Temperature
0.000
32
Tyco
H902
Heat Detector Fixed Temperature
0.000
32
Tyco
H904
Heat Detector Fixed Temperature
0.000
32
Thorn/Tyco
S231F+
Triple I/R flame detector
0.333
3
Thorn
MS302EX
Flame detector (IS)
0.100
12
Tyco
M300EX
Detector base (IS)
N/A
N/A
Tyco
MU601EX
CO detector (IS)
0.050
24
Tyco
MD611EX
Heat detector (IS)
0.050
24
Tyco
MD601EX
Heat detector (IS)
0.050
24
Tyco
MR601TEX
High performance Smoke detector Optical (IS)
0.060
20
Tyco
MDU601EX
Combined CO and Heat detector (IS)
0.050
24
Tyco
MF601EX
Smoke detector Ionisation (IS)
0.050
24
Thorn/Tyco
MUBEX
Detector base (IS)
N/A
N/A
Thorn/Tyco
S111
I/R flame detector (IS)
0.100
12
Thorn/Tyco
S112
I/R flame detector (IS)
0.100
12
Thorn/Tyco
S121
I/R flame detector (IS)
0.100
12
Thorn/Tyco
S131
I/R flame detector (IS)
0.100
12
Thorn/Tyco
S161
I/R flame detector (IS)
0.100
12
Thorn
S231I+
Triple I/R flame detector (IS)
0.333
3
Thorn
CP220Ex
Manual Call Point (IS)
0.000
32
Non Branded
MC600
Series 600 Relay Base
N/A
N/A
Thorn/Tyco
CP210
Manual Call Point
0.000
32
Thorn
CP250M
Manual Call Point [Marine]
0.000
32
Thorn/Tyco
S232F+
Triple I/R Flame Detector
0.333
3
Thorn/Tyco
MF301
Smoke Detector Ionisation
0.050
24
Thorn/Tyco
MF301EX
Smoke Detector Ionisation (IS)
0.050
24
Thorn/Tyco
MR301
Smoke Detector Optical
0.050
24
Thorn/Tyco
MR301EX
Smoke Detector Optical (IS)
0.050
24
Thorn/Tyco
MD301
ROR Heat Detector Grade 1
0.050
24
Thorn/Tyco
MD301EX
ROR Heat Detector Grade 1 (IS)
0.050
24
Thorn/Tyco
MD303EX
ROR Heat Detector Grade 3 (IS)
0.050
24
Thorn/Tyco
MD305EX
Heat Detector Range 2 (IS)
0.050
24
Thorn/Tyco
M300
Conventional Base
N/A
N/A
Non Branded
601F-M
Conventional Solar Blind Flame Detector [marine]
0.233
5
Non Branded
601FEX-M
Conventional Solar Blind Flame Detector (IS)
[marine]
0.233
5
Thorn/Tyco
MD631EX
Conventional Heat Detector Fixed Temperature
(IS)
0.050
24