Configurable Fire Output, Fire Protection
and Fault Output Relays
Configuration Links on the motherboard allow each Output Relay
to be individually selected to the EN54 powered/fault-monitored
mode or non-EN54-compliant volt-free changeover contacts.
Factory configuration - Fully Monitored (EN54 Mode).
Reset Relay
A volt-free changeover contact operating for 10 seconds on
panel fire alarm reset.
Auxiliary 24Vdc power supply output
Protected by an electronic fuse. Operation of the fuse is
indicated on the display. Operation of the Reset button on the
panel display resets the electronic fuse.
Open collector outputs
•
Manual Fire Alarm/Muster active.
•
Buzzer Active.
•
Disablement Active.
•
Zonal fire for each zone up to zone 4. [additional zonal
output expansion on T1216-C and T1232-C panel via open
collector output expansion boards].
Remote Inputs
•
Remote Manual Fire Alarm or Muster as configured.
•
Remote Silence Alarms.
•
Remote Reset.
•
Fully monitored Muster activation from repeater panel [via
optional plug in board at panel and repeater].
Earth Fault monitoring
Can be disabled via link on the motherboard.
Zone/Output disablement feature
The following circuits can be independently disabled/enabled:
•
Each Zone
•
Fire Output
•
Fire Protection
•
Fault Output
•
All Sounders
One Man Zone Test
Each zone can be independently set to the One Man test
condition. Sounders can be configured to operate briefly to
confirm the panel has detected the test fire or not to operate
during the test fire.
One Man Sounder Test
Operates the sounders intermittently.