10.2.10 PANEL RESET Sentence Structure
This message is sent when the panel is reset from the fire alarm or fault condition.
Since this is not a fire or fault alarm condition, it uses the EVENT formatter EVE (general event messages are
used to output detailed information about events in a safety related system in a format that can be stored but not
necessarily understood by the VDR).
The message takes the following form:
$ttfff,hhmmss.ss,a—a,c—c*hh<CR><LF>
$
– start of sentence
tt
– Talker Identifier = FR (Fire detection system)
fff
– Sentence Formatter = EVE (EVENT)
,
– Field Separator
hhmmss.ss
– Time of event = VDROB has no clock so set to 000000
a—a
– Tag code used for identification of source of event if applicable.
c—c
– Event description text = PANEL 01 RESET OPERATED
*
– Indicates next two characters are the checksum
hh
– Checksum (XOR of all bytes including commas but excluding
$
and
*
)
<CR>
– Carriage Return character = HEX 0D
<LF>
– Line Feed character = HEX 0A
The RESET sentence is:
$FREVE,000000,Panel01,PANEL 01 RESET OPERATED*07<CR><LF>
The HEX data is:
24 46 52 45 56 45 2C 30 30 30 30 30 30 2C 50 61 6E 65 6C 30 31 2C 50 41 4E 45
4C 20 30 31 20 52 45 53 45 54 20 4F 50 45 52 41 54 45 44 2A 30 37 0D 0A