Output expansion system for the T1216-C
and T1232-C panels
Three different modules each providing eight switched outputs:
•
Open collector, suitable for LED mimics.
•
Volt-free relays for external signalling or equipment control.
•
Fault-monitored, powered outputs for EN54-2 type Fire
Protection control or additional sounder circuits.
Voyage Data Recorder Output Board
Provides output signals for the Voyage Data Recorder:
•
Common Fire.
•
Common Fault.
•
Mains Failed.
•
Back-up Supply Failed.
•
Machinery space fire. [Zonally configurable]
•
IEC 61162-1 compliant RS422 output.
Other configuration features
•
Prevent the Fire Protection output operating for a fire
condition on a “Non-Latch” zone.
•
Inhibit the silencing and resetting of the panel for 3 minutes
following the occurrence of a fire alarm. [Does not apply to
Muster Alarm].
•
Set the sounders to operate only when the panel is in the
Manual Fire Alarm/Muster condition.
•
Inhibit the resetting of the fire alarm condition until the
alarm sounders have been silenced.
•
Disable the internal panel buzzer.
•
Select latching fault mode where all fault conditions latch
until the panel is manually reset.
•
Restore factory default configuration.
Repeater panels
Support for up to 5 repeater panels via two-wire RS485 serial
communication. [Repeaters are not available for the T1204
panels].