background image

PowerSeries Pro Installation Guide

x= NAS use for ULC Commercial Fire Listed applications and ULC
Commercial Burg Security Level 4 applications.

Corbus wiring

The RED and BLK Corbus terminals are used to provide power while
YEL and GRN are used for data communications. The 4 Corbus terminals
of the alarm controller must be connected to the 4 Corbus terminals or
wires of each module.

The following conditions apply:

l

Corbus should be run with 18 to 22 AWG quad, two pair twisted
preferred.

l

The modules can be home run to the panel, connected in series or
can be T-tapped.

l

Do not use shielded wire for Corbus wiring.

Note:

Any module can be connected anywhere along the Corbus. Separate

wire runs for keypads, zone expanders etc. are not necessary.

Note:

No module can be more than 1000 ft / 305 m (in wire length) from

the panel.

Do not use shielded wire for Corbus wiring.

Figure 1-6 Corbus wiring

Module (A) is wired correctly as it is within 1000 ft / 305 m of the panel,
in wire distance. Module (B) is wired correctly as it is within 1000 ft / 305
m of the panel, in wire distance. Module (C) is NOT wired correctly as it
is farther than 1000 ft / 305 m from the panel. For models that require
more than 1000 ft / 305 m from the main panel, a HSM3204CX power
supply/Corbus extender can be used.

Current ratings

In order for the system to operate properly, the power output of the alarm
controller and power supply modules cannot be exceeded. Use the
following data to ensure that the available current is not exceeded.

Table 1-3 System output ratings

Device

Output Rating (12 V DC)

HS3032

HS3128

HS3248

AUX/
Corbus:

2 A. Subtract the listed rating for each keypad, expansion
module and accessory connected to AUX or Corbus. At least
100 mA must be reserved for the Corbus.

BELL:

700 mA continuous rating. 2 A. short term. Available only
with standby battery connected. DO NOT exceed the 700
mA load for UL/ULC or EN certified applications.

HSM3350

AUX1:

AUX2:

3 A. Subtract the listed rating for each keypad, expansion
module and accessory connected to AUX.

HSM3408

AUX:

500 mA. Continuous rating. Subtract for each device
connected. Subtract the total load on this terminal from the
alarm panel AUX/Corbus output.

HSM3204CX AUX/

Corbus:

2 A. Continuous rating. Subtract for each device connected.

HSM2208

AUX:

250 mA. Continuous rating. Subtract for each device
connected. Subtract the total load on this terminal from the
alarm panel AUX/Corbus output.

HSM2108

AUX:

100 mA. Subtract for each device connected. Subtract the
total load on this terminal from the panel AUX/Corbus
output.

Alarm Control Panel

AUX - 2000 mA available for devices connected to the AUX and PGM
terminals, and modules connected to Corbus terminals. At least 100mA
must be reserved for the Corbus.

Alarm controller current calculation

Panel calculation

Maximum (standby or alarm)

AUX (2 A max. including PGMs 1-4)

Corbus (2 A max.)***

 (200 mA)

USB (500 mA max.)

Cell module (20 mA idle)

Total (must not exceed 2 A)

For UL, ULC and Commercial Listed applications, the total standby and
alarm current cannot exceed 2 A.

Note:

For EN50131, UL, ULC and Commercial Listed applications, the

total standby and alarm current cannot exceed the values in Aux Loading
and Battery Selection for the applicable type of installation.

Capacitance limits

An increase in capacitance on the Corbus affects data transmission and
causes the system to slow down. Capacitance increases for every foot of
wire added to the Corbus. The capacitance rating of the wire used will
determine the maximum length of the Corbus.

Table 1-4 Wire capacitance

Wire Capacitance per 1000 ft
(300 m)

Total Corbus Wire Length

15 nF

5300 ft/1616 m

20 nF

4000 ft/1220 m

25 nF

3200 ft/976 m

30 nF

2666 ft/810 m

35 nF

2280 ft/693 m

40 nF

2000 ft/608 m

- 5 -

Summary of Contents for PowerSeries Pro HS3032

Page 1: ...10xLRSTUL y A B or C A ULC listed models B UL listed models C European and Australian models 4 wire smoke detectors FSA 410xUL FSA 410xTUL FSA 410xSUL FSA 410xSTUL FSA 410xLSTUL FSA 410xRUL FSA 410xRT...

Page 2: ...nnect device If the neutral wire cannot be identified then this equipment must be connected to a mains source that comes from a disconnect device that simultaneously disconnects both poles Line and Ne...

Page 3: ...instructions provided with the module 9 Wire the tamper switch into any available zone Configure the tamper for normally closed NC supervision Zone must be programmed for 24 hour latching or non latch...

Page 4: ...owing terminals are available on the PowerSeries Pro alarm controller Table 1 2 Terminal descriptions Terminal Description BAT BAT Battery terminals Use to provide backup power during a power outage a...

Page 5: ...A continuous rating 2 A short term Available only with standby battery connected DO NOT exceed the 700 mA load for UL ULC or EN certified applications HSM3350 AUX1 AUX2 3 A Subtract the listed rating...

Page 6: ...erride the option in 013 Observe the following guidelines when wiring zones l For UL listed installations use SEOL or DEOL only l Minimum 22 AWG wire maximum 18 AWG l Do not use shielded wire l Do not...

Page 7: ...otion detectors To configure TEOL supervision per zone use programming section 002 bit 15 Figure 1 10 TEOL wiring Note Resistor values are configurable in section 004 Bell wiring These terminals suppl...

Page 8: ...ted on the sticker attached to the device The format is XXX YYYY where l XXX identifies the type or model of the device l YYYY is a short encrypted ID used by the system to identify the specific devic...

Page 9: ...l To assign a keypad to a partition key in 01 08 for partition 1 8 3 Press the key and repeat step 2 for next keypad When finished programming all keypads press the key twice to exit programming Users...

Page 10: ...resent on the system Note When additional information is available for a specific trouble condition a is displayed Press the key to view the additional information 2 Trouble Display This feature is us...

Page 11: ...A temperature sensor falls below the low temperature warning threshold 11 Probe Disconn The probe on the flood detector or the temperature detector is disconnected 12 Fire Trouble A smoke sensor is i...

Page 12: ...915 MHz North America 433 MHz Europe and 912 919 MHz international Access Codes l Up to 1003 access codes 1000 level 2 EN one installer code level 3 EN one maintenance code and one guard code l Progr...

Page 13: ...ies with TS203 021 1 2 3 Telecom equipment require ments and EN50136 1 EN50136 2 ATS SP3 DP2 when used in conjunction with Ethernet and or Cellular paths l The integral Ethernet communication port and...

Page 14: ...0 24 Hour Non Latching Tamper 061 24 Hour Masking 066 Momentary Keyswitch Arm 067 Maintained Keyswitch Arm 068 Momentary Keyswitch Disarm 069 Maintained Keywsitch Disarm 071 Doorbell Zone 072 Push to...

Page 15: ...larm 05 Panic Alarm 06 Burglary Alarm 07 Medical Alarm 08 Supervisory 09 Priority Event 10 Holdup 11 Duress 12 Emergency 13 Fire Supervisory 14 Fire Trouble 15 CO Alarm 157 System Tamper 01 True Outpu...

Page 16: ...tition 1 2 Partition 2 3 Partition 3 4 Partition 4 5 Partition 5 6 Partition 6 7 Partition 7 8 Partition 8 201 208 Partition 1 8 Zone Assignment 001 Zone 1 8 002 Zn 9 16 003 Zn 17 24 004 Zn 25 32 005...

Page 17: ...eiver 3 06 Alt Comm Receiver 3 Restore 07 Alt Comm Receiver 4 08 Alt Comm Receiver 4 Restore 355 Alternate Communicator 5 01 Alt Comm Receiver 1 Supervision Failure 02 Alt Comm Receiver 1 Supervision...

Page 18: ...iday 07 Saturday 404 Interval 4 Holiday Assignment 09 Holiday 1 10 Holiday 2 11 Holiday 3 12 Holiday 4 711 714 Holiday Group 1 4 001 099 Holiday Group 1 4 Date 1 99 000000 MMDDYY Audio Station Program...

Page 19: ...Arming and Disarming Notifications 04 Trouble and Trouble Restore Notifications 05 Test Transmission Notifications 06 Reserved 07 Reserved 08 Reserved 693 Session 3 Notification Control 01 Alarm and A...

Page 20: ...ODUCT installed b Storage Network Use The SOFTWARE PRODUCT may not be installed accessed displayed run shared or used concurrently on or from different computers including a workstation terminal or ot...

Page 21: ...MSTANCES SHALL DSC BE LIABLE FOR ANY SPECIAL INCIDENTAL CONSEQUENTIAL OR INDIRECT DAMAGES BASED UPON BREACH OF WARRANTY BREACH OF CONTRACT NEGLIGENCE STRICT LIABILITY OR ANY OTHER LEGAL THEORY SUCH DA...

Page 22: ...011 012 013 014 015 016 017 018 019 020 021 022 023 024 025 026 027 028 029 030 031 032 033 034 035 036 037 038 039 040 041 042 043 044 045 046 047 048 049 050 051 052 053 054 055 056 057 058 059 060...

Page 23: ...11 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 1...

Page 24: ...06 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 Module Record Module Type Slo...

Page 25: ...PowerSeries Pro Installation Guide Installer Defined Access Codes 001 Installer Code 002 Master Code 003 Maintenance Code System Account Code 25...

Page 26: ...in developing the escape plan 2 Study the possible escape routes from each location within the house Since many fires occur at night special attention should be given to the escape routes from sleepin...

Page 27: ...rrupted service Equipment Maintenance Facility If trouble is experienced with this equipment HS3032 HS3128 HS3248 for repair or warranty information please contact the facility indicated below If the...

Page 28: ...ty applications the integral Ethernet communicator or the plug in cellular modules Models LE9080 3G9080 or 3H9080 shall have the Encryption Key enabled AES128 bit encryption algorithm is validated und...

Page 29: ...by the person operating the security system during the daily arming and disarming cycle Protection of the Control Unit The local control unit and the local power supply must be protected in one of the...

Page 30: ...with HSM2HOST8 Wireless Transceiver mounted in the HSC3020CP plastic enclosure meets the requirements of Grade 2 Class II equipment as per EN50131 1 2006 A1 2009 A2 2017 Standards The model HS3032P H...

Page 31: ...laration of conformity DoC for this product can be found at www dsc com under the Agency Listings section SIA False Alarm Reduction Installations Quick Reference Minimum required system consists of on...

Page 32: ...elected user codes send a duress reporting code to the central station when used to perform any function on the system Section 019 option 6 must be enabled Default N Required Cancel Window 377 002 opt...

Page 33: ...or damage shall be evaluated and a repair estimate shall be provided No repair work will be performed until a valid purchase order is received from the Customer and a Return Merchandise Authorization...

Page 34: ...nt that all system users be trained in the correct operation of the alarm system and that they know how to respond when the system indicates an alarm Smoke Detectors Smoke detectors that are a part of...

Page 35: ...or any kind of construction activity inside or outside the premises The testing should include all sensing devices keypads consoles alarm indicating devices and any other operational devices that are...

Page 36: ...secution wherever necessary All trademarks not owned by Tyco are the property of their respective owners and are used with permission or allowed under applicable laws Product offerings and specificati...

Reviews: