Tyco PowerSeries Pro HS3032 Installation Manual Download Page 10

PowerSeries Pro Installation Guide

[001] – Installer code

[002] – Master code

[003] – Maintenance code

Access codes are either 4, 6 or 8 digits in length, depending on the setting
of programming section [041]. Duplicate codes are not valid.

Communication paths

The path of communication between the alarm panel and the central station
must be established through either the alarm panel’s on-board Public
Switched Telephone Network (PSTN) connection (Ethernet) or through
the alternate communicator if equipped.

Alternate communicator setup

The alternate communicator is an ethernet or optional cellular
communications device that can be used as a backup to the PSTN
connection or as a primary means of communication between the alarm
panel and the central monitoring station. The alternate communicator
communicates via 2G, 3G, LTE or Ethernet.

The following configuration steps are required to set up the alternate
communicator:

l

Install the optional cellular alternate communicator to the alarm
panel

l

Enroll the alternate cellular communicator with Connect 24 (North
America only)

l

Set the communication path: [300]

l

Enable the alternate communicator: [383] option 3 for Ethernet,
and [383] option 4 for cellular.

l

The Ethernet or Cellular receivers IP and Port: [851]

l

Enable event reporting: [307]/[308]

l

Program communication delay timer: [377]

l

Program DLS access: [401] option 07

Refer to Section 5: Programming for details.

[300] Panel/Receiver Communication Paths

This section is used to select the path of communications between the
alarm system and the central station.

Testing the system

Installer Walk Test

Walk test enables the installer to test the operation of each detector by
tripping zones, causing an actual alarm. Enter section [901] to initiate a
walk test. When a zone is tripped, all system sirens emit a tone to indicate
that the zone is working correctly.

After 15 minutes without zone activity, the walk test terminates
automatically. To manually exit walk test mode, enter [901] again.

Viewing the event buffer

The event buffer contains logs of events that have occurred on the alarm
system beginning with the most recent. The capacity of the event buffer is
scalable and can hold 500/1000 events (depending on panel model) before
rolling over. The buffer displays events according to their time stamp,
beginning with the most recent. The event buffer can be uploaded using
DLS.

Each event displays the time and date, a description of the event, the zone
label, access code number or any other pertinent information. To view the
event buffer, press [*][6][Master Code][*].

Troubleshooting

LCD programmable-message keypad:

l

Press [*][2] followed by access code if required to view a trouble
condition

l

The trouble light flashes and the LCD displays the first trouble
condition

l

Use the arrow keys to scroll through all trouble conditions present
on the system

Note:

When additional information is available for a specific trouble

condition, a [*] is displayed. Press the [*] key to view the additional
information.

[*][2] Trouble Display

This feature is used to view system troubles. If a trouble is present, the
keypad Trouble indicator illuminates and an audible indication is emitted
(two short beeps every 10 seconds, except while in AC failure). Silence
the audible indicator by pressing [#].

Troubles may be viewed while the system is armed or disarmed. The
system may be programmed to show all troubles while armed or only fire
troubles.

The system can be configured to require a user code to view [*][2] system
troubles. See section [023] option 5.

To view trouble conditions:

l

Press [*][2] to enter the Trouble menu.

l

On an LCD keypad, scroll to a trouble type then press [*] to view
the specific trouble. The zone name and trouble condition for each
trouble are displayed on the screen.

Note:

The trouble beeps generated by fire trouble are only silenced after

[*][2]trouble menu is exited. A keypress in the keypad will not silence the
fire trouble beeps. For UL installations, set the value in section [023] bit 5
access code required for [*][2] to enabled.

Table 1-8 : Trouble Indications

Trouble 01

Service Required:

[01]

Bell Circuit Trouble: The bell circuit is open

[02]

RF Jam: The HSM2HOSTx has detected an RF Jam condition

[03]

Loss of Clock: System time and date require programming.

[04]

Output 1 Fault: An HSM2204 module has detected an open condition on output

#1.

[05]

Warm Start: Warm restart has occured.

[06]

USB Wi-Fi Connected: USB Wi-Fi adapter is detected

[07]

Power Unit Failure (System): Failure detected with internal power unit.

[08]

Failure detected with internal power unit (HSM3204CX Corbus Repeater)

[09]

Failure detected with internal power unit (HSM3350 3 A Power Supply)

[10]

Overcurrent Trouble: If the total current of the panel internal components and all

outputs exceeds a threshold of 2.1 A for a period longer than 5 minutes, an
overcurrent trouble is generated. When the current goes below a 2.0 A threshold, the
trouble restores. Do not exceed 2A combined between AUX and Corbus.

Note:

Total current does not include bell current or battery charging.

Trouble 02 – Battery Trouble:

[01]

Panel Low Battery Trouble: The battery voltage is low.

[02]

Panel No Battery: No battery connected to alarm controller.

[04]

HSM2204 01 - 04 Low Battery: An HSM2204 has a low battery voltage.

[05]

HSM2204 01 - 04 No Battery: No battery connected to HSM2204.

[07]

HSM2300 01 - 04 Low Battery: An HSM2300 has a low low battery voltage.

[08]

HSM2300 01 - 04 No Battery: No battery connected to HSM2300.

[10]

HSM3204CX Low Battery: A Corbus repeater has a low battery voltage.

[11]

HSM3204CX No Battery: No battery connected to corbus repeater.

[13]

HSM3350 Low Battery 1: A 3 A power supply module has a low battery voltage.

[14]

HSM3350 Low Battery 2: A 3 A power supply module has a low battery voltage.

[15]

HSM3350 No Battery 1: No battery connected to 3A power supply module.

[16]

HSM3350 No Battery 2: No battery connected to 3A power supply module.

- 10 -

Summary of Contents for PowerSeries Pro HS3032

Page 1: ...10xLRSTUL y A B or C A ULC listed models B UL listed models C European and Australian models 4 wire smoke detectors FSA 410xUL FSA 410xTUL FSA 410xSUL FSA 410xSTUL FSA 410xLSTUL FSA 410xRUL FSA 410xRT...

Page 2: ...nnect device If the neutral wire cannot be identified then this equipment must be connected to a mains source that comes from a disconnect device that simultaneously disconnects both poles Line and Ne...

Page 3: ...instructions provided with the module 9 Wire the tamper switch into any available zone Configure the tamper for normally closed NC supervision Zone must be programmed for 24 hour latching or non latch...

Page 4: ...owing terminals are available on the PowerSeries Pro alarm controller Table 1 2 Terminal descriptions Terminal Description BAT BAT Battery terminals Use to provide backup power during a power outage a...

Page 5: ...A continuous rating 2 A short term Available only with standby battery connected DO NOT exceed the 700 mA load for UL ULC or EN certified applications HSM3350 AUX1 AUX2 3 A Subtract the listed rating...

Page 6: ...erride the option in 013 Observe the following guidelines when wiring zones l For UL listed installations use SEOL or DEOL only l Minimum 22 AWG wire maximum 18 AWG l Do not use shielded wire l Do not...

Page 7: ...otion detectors To configure TEOL supervision per zone use programming section 002 bit 15 Figure 1 10 TEOL wiring Note Resistor values are configurable in section 004 Bell wiring These terminals suppl...

Page 8: ...ted on the sticker attached to the device The format is XXX YYYY where l XXX identifies the type or model of the device l YYYY is a short encrypted ID used by the system to identify the specific devic...

Page 9: ...l To assign a keypad to a partition key in 01 08 for partition 1 8 3 Press the key and repeat step 2 for next keypad When finished programming all keypads press the key twice to exit programming Users...

Page 10: ...resent on the system Note When additional information is available for a specific trouble condition a is displayed Press the key to view the additional information 2 Trouble Display This feature is us...

Page 11: ...A temperature sensor falls below the low temperature warning threshold 11 Probe Disconn The probe on the flood detector or the temperature detector is disconnected 12 Fire Trouble A smoke sensor is i...

Page 12: ...915 MHz North America 433 MHz Europe and 912 919 MHz international Access Codes l Up to 1003 access codes 1000 level 2 EN one installer code level 3 EN one maintenance code and one guard code l Progr...

Page 13: ...ies with TS203 021 1 2 3 Telecom equipment require ments and EN50136 1 EN50136 2 ATS SP3 DP2 when used in conjunction with Ethernet and or Cellular paths l The integral Ethernet communication port and...

Page 14: ...0 24 Hour Non Latching Tamper 061 24 Hour Masking 066 Momentary Keyswitch Arm 067 Maintained Keyswitch Arm 068 Momentary Keyswitch Disarm 069 Maintained Keywsitch Disarm 071 Doorbell Zone 072 Push to...

Page 15: ...larm 05 Panic Alarm 06 Burglary Alarm 07 Medical Alarm 08 Supervisory 09 Priority Event 10 Holdup 11 Duress 12 Emergency 13 Fire Supervisory 14 Fire Trouble 15 CO Alarm 157 System Tamper 01 True Outpu...

Page 16: ...tition 1 2 Partition 2 3 Partition 3 4 Partition 4 5 Partition 5 6 Partition 6 7 Partition 7 8 Partition 8 201 208 Partition 1 8 Zone Assignment 001 Zone 1 8 002 Zn 9 16 003 Zn 17 24 004 Zn 25 32 005...

Page 17: ...eiver 3 06 Alt Comm Receiver 3 Restore 07 Alt Comm Receiver 4 08 Alt Comm Receiver 4 Restore 355 Alternate Communicator 5 01 Alt Comm Receiver 1 Supervision Failure 02 Alt Comm Receiver 1 Supervision...

Page 18: ...iday 07 Saturday 404 Interval 4 Holiday Assignment 09 Holiday 1 10 Holiday 2 11 Holiday 3 12 Holiday 4 711 714 Holiday Group 1 4 001 099 Holiday Group 1 4 Date 1 99 000000 MMDDYY Audio Station Program...

Page 19: ...Arming and Disarming Notifications 04 Trouble and Trouble Restore Notifications 05 Test Transmission Notifications 06 Reserved 07 Reserved 08 Reserved 693 Session 3 Notification Control 01 Alarm and A...

Page 20: ...ODUCT installed b Storage Network Use The SOFTWARE PRODUCT may not be installed accessed displayed run shared or used concurrently on or from different computers including a workstation terminal or ot...

Page 21: ...MSTANCES SHALL DSC BE LIABLE FOR ANY SPECIAL INCIDENTAL CONSEQUENTIAL OR INDIRECT DAMAGES BASED UPON BREACH OF WARRANTY BREACH OF CONTRACT NEGLIGENCE STRICT LIABILITY OR ANY OTHER LEGAL THEORY SUCH DA...

Page 22: ...011 012 013 014 015 016 017 018 019 020 021 022 023 024 025 026 027 028 029 030 031 032 033 034 035 036 037 038 039 040 041 042 043 044 045 046 047 048 049 050 051 052 053 054 055 056 057 058 059 060...

Page 23: ...11 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 1...

Page 24: ...06 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 Module Record Module Type Slo...

Page 25: ...PowerSeries Pro Installation Guide Installer Defined Access Codes 001 Installer Code 002 Master Code 003 Maintenance Code System Account Code 25...

Page 26: ...in developing the escape plan 2 Study the possible escape routes from each location within the house Since many fires occur at night special attention should be given to the escape routes from sleepin...

Page 27: ...rrupted service Equipment Maintenance Facility If trouble is experienced with this equipment HS3032 HS3128 HS3248 for repair or warranty information please contact the facility indicated below If the...

Page 28: ...ty applications the integral Ethernet communicator or the plug in cellular modules Models LE9080 3G9080 or 3H9080 shall have the Encryption Key enabled AES128 bit encryption algorithm is validated und...

Page 29: ...by the person operating the security system during the daily arming and disarming cycle Protection of the Control Unit The local control unit and the local power supply must be protected in one of the...

Page 30: ...with HSM2HOST8 Wireless Transceiver mounted in the HSC3020CP plastic enclosure meets the requirements of Grade 2 Class II equipment as per EN50131 1 2006 A1 2009 A2 2017 Standards The model HS3032P H...

Page 31: ...laration of conformity DoC for this product can be found at www dsc com under the Agency Listings section SIA False Alarm Reduction Installations Quick Reference Minimum required system consists of on...

Page 32: ...elected user codes send a duress reporting code to the central station when used to perform any function on the system Section 019 option 6 must be enabled Default N Required Cancel Window 377 002 opt...

Page 33: ...or damage shall be evaluated and a repair estimate shall be provided No repair work will be performed until a valid purchase order is received from the Customer and a Return Merchandise Authorization...

Page 34: ...nt that all system users be trained in the correct operation of the alarm system and that they know how to respond when the system indicates an alarm Smoke Detectors Smoke detectors that are a part of...

Page 35: ...or any kind of construction activity inside or outside the premises The testing should include all sensing devices keypads consoles alarm indicating devices and any other operational devices that are...

Page 36: ...secution wherever necessary All trademarks not owned by Tyco are the property of their respective owners and are used with permission or allowed under applicable laws Product offerings and specificati...

Reviews: