background image

TFP1253

Page 8 of 8

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association

1400 Pennbrook Parkway, Lansdale, PA 19446 | Tel1-215-362-0700

© 2021 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

FILTER HOUSING WITH 

LOWER HOUSING REMOVED

FILTER 

CARTRIDGE

BLACK 

DISC

WATER 

SEPARATOR

FILTER 

HOUSING

INLET BALL 

VALVE

OUTLET BALL 

VALVE

BYPASS BALL 

VALVE

DEPRESSURIZATION 

BALL VALVE

POWER ON/OFF 

SWITCH

BYPASS 

MODE 

ALARM 

INDICATOR

FIGURE 4 

MODEL NG-1 1150, NG-1 1500, NG-1 2000, AND NG-1 3000 STAND-ALONE 

NITROGEN GENERATOR FILTER CARTRIDGE REPLACEMENT

Step 8.

 Remove the Water Separator 

housing by pulling down on the blue 

housing lock and turning the housing 

counter-clockwise. Inspect the Water 

Separator and clean as necessary.

Step 9.

 Replace the Water Separator 

housing by pushing up into position 

and turning the housing clockwise until 

blue housing lock locks into place.

Step 10.

 Close the depressurization 

ball valve. The Nitrogen Generator can 

now be placed back into service.

Step 11.

 Turn the power supply to the 

unit ON.

Step 12.

 Close the Bypass Ball Valve.

Step 13.

 Open the Inlet and Outlet Ball 

Valves.

Compressors

Maintenance of the Compressor

For compressor maintenance, please 

refer to the manufacturer’s recom-

mended maintenance plan in the 

owner’s manual for the compressor.

Limited 

Warranty

For warranty terms and conditions, visit 

www.tyco-fire.com.

Ordering 

Procedure

TYCO will supply a list of required part 

numbers to order through regular sales 

channels. Contact your local business 

manager or sales person and specify 

the following:

Sizing of Nitrogen Generator

•  Total cumulative size of all dry/pre-

action sprinkler systems

•  Size of the largest single dry/preac-

tion sprinkler system

•  Total number of dry/preaction sprin-

kler systems

•  Supervisory pressure of all dry/pre-

action sprinkler systems

•  Required voltage needed for dry/pre-

action sprinkler system

Filter Replacement Kit

Filter Replacement Kit . . . . . . . . . . . . . TNGFLTS

Optional Monitoring Equipment

Model THGA Handheld Gas Analyzer. . THGA01

Model TSGA SMART Gas Analyzer. . . . TSGA01

Model TILD In-Line Corrosion Detector

Refer to Technical Data Sheet TFP1261 for 

ordering instructions.

Summary of Contents for NG-1 1150

Page 1: ...to TFP1262 for more information on TYCO Dry Air Vent TAV D and to TFP1263 for more information on TYCO SMART Air Vent TSV D System Assembly The TYCO Nitrogen Generator unit includes the following comp...

Page 2: ...605 1150 4353 2300 8706 NG 1 1500 24 3 688 11000 41640 1440 5451 2880 10902 NG 1 2000 24 688 18500 70030 2025 7666 4050 15331 NG 1 3000 35 992 22500 85172 2900 10978 5800 21955 Notes a Capacity based...

Page 3: ...l Cabinet Dimensions See Table A Weight See Table A Operating Performance See Table B Temperature Range 40 F 5 C to 105 F 40 C Power Supply 120 VAC Single 1 phase 60Hz dedicated circuit 230 VAC Single...

Page 4: ...panel for wall mount ing using standard anchors Step 2 Power Supply The Nitrogen Generator requires a ded icated power supply that connects to the terminal blocks in the nitrogen gen erator cabinet Se...

Page 5: ...ENERATOR RUNNING OUTPUT BYPASS MODE ALARM OUTPUT LEAK MONITORING OUTPUT POWER ON OFF OUTPUT NITROGEN SUPPLY LINE PRESSURE OUTPUT L1 N G PRESSURE SWITCH INCOMING POWER FUSE BOX BUILDING MANAGEMENT SYST...

Page 6: ...compressors in EMEA and APAC the air discharge plumb ing should first be connected to the WSD 25 water separator which then is to be connected to the inlet of the nitro gen generator Step 4 Plumb the...

Page 7: ...gen separation membrane will provide up to 20 years of service life Filter Replacement Procedure With reference to Figure 4 perform the following steps when replacing the cartridge filters located in...

Page 8: ...10 Close the depressurization ball valve The Nitrogen Generator can now be placed back into service Step 11 Turn the power supply to the unit ON Step 12 Close the Bypass Ball Valve Step 13 Open the In...

Reviews: