Option [611]: UPS Battery 1 Trouble
Default (Disabled)
This option is used to enable or disable UPS Battery 1 input supervision. If this option is set to ‘Disabled’, the trouble condition is not reported.
NOTE: Must be enabled for UL installations.
Option [612]: UPS Battery 2 Trouble
Default (Disabled)
This option is used to enable or disable UPS Battery 2 input supervision. If this option is set to ‘Disabled’, the trouble condition is not reported.
NOTE: Must be enabled for UL installations.
Option [613]: SG-Serial Automation Pri - 1 Trouble
Default (Enabled)
This option is used to enable or disable SG-Serial Automation 1 supervision for the primary SG-CPM5. If this option is set to ‘Disabled’, the trouble
condition is not reported.
NOTE: Must be enabled for UL installations.
Option [615]: SG-Serial Automation Sec - 1 Trouble
Default (Disabled)
Secondary SG-CPM5 Default (Enabled)
This option is used to enable or disable SG-Serial Automation 1 supervision for the secondary SG-CPM5. If this option is set to ‘Disabled’, the trouble
condition is not reported.
NOTE: Must be enabled for UL installations.
Option [617]: SG-Serial CPM1 Printer 1 Trouble
Default (Enabled)
This option is used to enable or disable SG-CPM5 1 printer supervision. If this option is set to ‘Disabled’, the trouble condition is not reported.
Option [618]: SG-Serial CPM2 Printer 1 Trouble
Default (Enabled)
This option is used to enable or disable SG-CPM5 2 printer supervision. If this option is set to ‘Disabled’, the trouble condition is not reported.
Option [621]:SG-TCP Automation Pri - 1 Trouble
Default (Enabled)
This option is used to enable or disable SG-TCP automation port (port 1025) supervision for the primary SG-CPM5. If any of these options are set to
‘Disabled’, the corresponding trouble condition will not be reported.
Option [631]:SG-TCP Automation Sec - 1 Trouble
Default (Disabled)
Secondary SG-CPM5 Default (Enabled)
This option is used to enable or disable the SG-TCP automation port (port 1025) supervision for the secondary SG-CPM5. If this option is set to ‘Dis-
abled’, the trouble condition is not reported.
Option [665]:TCP Printer Pri - 1 Trouble
Default (Enabled)
This option is used to enable or disable TCP Printer 1 (port 1027) supervision for the primary SG-CPM5. If this option is set to ‘Disabled’, the trouble
condition is not reported.
Option [675]:TCP Printer Sec - 1 Trouble
Default (Enabled)
This option is used to enable or disable TCP Printer 1 (port 1027) supervision for the secondary SG-CPM5. If this option is set to ‘Disabled’, the
trouble condition is not reported.
S
G
-S
ys
te
m
5
O
pe
ra
ti
ng
M
anua
l
Summary of Contents for SG-System 5
Page 69: ...6 0 Options 69 FIGURE 6 2 Flow Diagram for Fallback Mode 1 SG System 5 Operating Manual ...
Page 70: ...6 0 Options 70 FIGURE 6 3 Flow Diagram for All Mode 2 SG System 5 Operating Manual ...
Page 71: ...6 0 Options 71 FIGURE 6 4 Flow Diagram for IP Fallback Mode 3 SG System 5 Operating Manual ...