tion service and which have the same nominal K-factor,
the same coverage area, and the same or lower flow rat-
ings (as indicated under “Hydraulic Design Criteria”).

When remodeling, such as by adding false beams or light
fixtures or changing the location of compartment walls,
first verify that the new construction will not violate the in-
stallation requirements stated under WARNINGS. Alter
the new construction and/or the sprinkler system to suit
the requirements of this document.

LIMITED WARRANTY

Products manufactured by Tyco Fire Products are war-
ranted solely to the original Buyer for ten (10) years
against defects in material and workmanship when paid
for and properly installed and maintained under normal
use and service. This warranty will expire ten (10) years
from date of shipment by Tyco Fire Products. No warranty
is given for products or components manufactured by
companies not affiliated by ownership with Tyco Fire Prod-
ucts or for products and components which have been
subject to misuse, improper installation, corrosion, or
which have not been installed, maintained, modified or re-
paired in accordance with applicable Standards of the Na-
tional Fire Protection Association, and/or the standards of
any other Authorities Having Jurisdiction. Materials found
by Tyco Fire Products to be defective shall be either re-
paired or replaced, at Tyco Fire Products’ sole option.
Tyco Fire Products neither assumes, nor authorizes any
person to assume for it, any other obligation in connec-
tion with the sale of products or parts of products. Tyco
Fire Products shall not be responsible for sprinkler sys-
tem design errors or inaccurate or incomplete information
supplied by Buyer or Buyer’s representatives.

IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LI-
ABLE, IN CONTRACT, TORT, STRICT LIABILITY OR UN-
DER ANY OTHER LEGAL THEORY, FOR INCIDENTAL,
INDIRECT, SPECIAL OR CONSEQUENTIAL DAMAGES,
INCLUDING BUT NOT LIMITED TO LABOR CHARGES,
REGARDLESS OF WHETHER TYCO FIRE PRODUCTS
WAS INFORMED ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT SHALL TYCO FIRE
PRODUCTS’ LIABILITY EXCEED AN AMOUNT EQUAL
TO THE SALES PRICE.

THE FOREGOING WARRANTY IS MADE IN LIEU OF
ANY AND ALL OTHER WARRANTIES EXPRESS OR IM-
PLIED, INCLUDING WARRANTIES OF MERCHANT-
ABILITY AND FITNESS FOR A PARTICULAR PUR-
POSE.

ORDERING PROCEDURE

Please Specify:

1 Stealth Residential S240, 4.2 K-Factor, Concealed

Pendent Sprinkler (#2450)

2. W-Type 13 Sprinkler Wrench (#2111-01)

Refer to Price List for a complete listing of Part Numbers
with respect to temperature ratings, replacement covers,
finishes, etc.

GRAPH B

MINIMUM REQUIRED HORIZONTAL DISTANCE

BETWEEN A SPRINKLER LOCATED ON A LEVEL

CEILING AND AN INTERSECTING PITCHED CEILING

WITHOUT UNDULY OBSTRUCTING

THE WATER DISTRIBUTION

NOTE:

SPRINKLERS MUST BE INSTALLED WITH THEIR

DEFLECTOR ARMS PERPENDICULAR TO THE CEILING
RIDGE.

GRAPH C

MINIMUM REQUIRED SLANT DISTANCE BETWEEN

A LEVEL CEILING AND A SPRINKLER LOCATED ON A

PITCHED CEILING WITHOUT UNDULY OBSTRUCTING

THE WATER DISTRIBUTION LOCATED ON AN

INTERSECTING PITCHED CEILING

NOTE:

SPRINKLERS MUST BE INSTALLED WITH THEIR

DEFLECTOR ARMS PERPENDICULAR TO THE CEILING
RIDGE.

STAR SPRINKLER

1-3.1.11

Page 7

COVERAGE AREAS:

(a)

20’ x 20’

(c)

16’ x 16’

(b)

18’ x 18’

(d)

14’ x 14’ & 12’ x 12’

OBSOLETE

Summary of Contents for Star Stealth S240

Page 1: ...tion required by building codes WARNINGS The Stealth Residential Concealed Pendent Sprin klers described herein must be installed and main tained in compliance with this document as well as with the a...

Page 2: ...minimum required discharge from the most hydraulically demand ing single sprinkler and the NFPA 13D 13R multiple sprin kler flow rate is the minimum required discharge from each of the total number o...

Page 3: ...the Protective Cap 3 With pipe thread sealant applied to the pipe threads and using the W Type 13 Wrench positioned as shown in Figure 2 install and tighten the Sprinkler Mounting Cup Assembly into th...

Page 4: ...and larvae by gently brushing with a feather duster or gently vacuuming with a soft bristle i e dusting brush attachment Exercise suitable safety precautions in the use and storage of highly flammabl...

Page 5: ...re to be in a row which runs parallel to the ridge and the sprinklers are to be spaced a minimum of 8 feet apart d the sprinklers are installed with their deflector arms perpendicular to the ceiling r...

Page 6: ...urisdiction The installing contrac tor or sprinkler manufacturer should be contacted relative to any questions It is recommended that automatic sprinkler systems be in spected tested and maintained by...

Page 7: ...s or parts of products Tyco Fire Products shall not be responsible for sprinkler sys tem design errors or inaccurate or incomplete information supplied by Buyer or Buyer s representatives IN NO EVENT...

Page 8: ...REQUIRED SLANT DISTANCE BETWEEN A RIDGE AND A SPRINKLER WITHOUT UNDULY OBSTRUCTING THE WATER DISTRIBUTION NOTES 1 UP TO A MAXIMUM OF ONE HALF THE LENGTH OF THE COVERAGE AREA BEING HYDRAULICALLY CALCUL...

Reviews: