Automatic sprinklers must never be shipped or stored
where its temperature will exceed 100°F/38°C and they
must never be painted, plated, coated, or otherwise al-
tered after leaving the factory. Modified sprinklers must
be replaced. Sprinklers that have been exposed to corro-
sive products of combustion, but have not operated,
should be completely cleaned by wiping the sprinkler with
a cloth or by brushing it with a soft bristle brush.
Care must be exercised to avoid damage - before, dur-
ing, and after installation. Sprinklers damaged by drop-
ping, striking, wrench twist/slippage, or the like, must be
replaced. Also, replace any sprinkler that has a cracked
bulb or that has lost liquid from its bulb (Ref. Installation
Section).
The owner is responsible for the inspection, testing, and
maintenance of their fire protection system and devices in
compliance with this document, as well as with the appli-
cable standards of the National Fire Protection Associa-
tion (e.g., NFPA 25), in addition to the standards of any
other authorities having jurisdiction. The installing contrac-
tor or sprinkler manufacturer should be contacted relative
to any questions.
It is recommended that automatic sprinkler systems be in-
spected, tested, and maintained by a qualified Inspection
Service.
The Stealth Residential must only be replaced with pen-
dent sprinklers which are listed for residential fire protec-
GRAPH A
MAXIMUM PERMITTED VERTICAL DISTANCE BETWEEN THE SPRINKLER MOUNTING SURFACE AND
THE BOTTOM OF CEILING MOUNTED OBSTRUCTIONS SUCH AS BEAMS, OVERHANGS, AND LIGHT FIXTURES
WITHOUT UNDULY OBSTRUCTING THE WATER SPRAY DISTRIBUTION
NOTES:
1.
CEILING OBSTRUCTIONS MUST BE SPACED ON THE BASIS OF USING THE MAXIMUM RESIDUAL PRESSURE WHICH WOULD BE
PRESENT FOR A SINGLE SPRINKLER OPERATION.
2.
BEAMS AND/OR OTHER CONTINUOUS OBSTRUCTIONS ARE NOT TO EXCEED A VERTICAL DEPTH ‘V’ OF MORE THAN 3 INCHES
WITHIN THE SPRINKLER COVERAGE AREA.
STAR SPRINKLER
Page 6
1-3.1.11
TABLE B
MINIMUM VERTICAL CLEARANCE BETWEEN TOP OF
FREE STANDING OBSTRUCTION AND
SPRINKLER DEFLECTOR
Horizontal Distance From
Vertical Clearance
Sprinkler to Obstruction
Below Sprinkler
Below Sprinkler Deflector, ft.
Deflector, in.
More than 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
From 3 to 6
. . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Between 2 and 3
. . . . . . . . . . . . . . . . . . . . . . . . 16
From 1 to 2
. . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Less than 1
. . . . . . . . . . . . . . . . . . . . . . . . . . . 10
OBSOLETE