background image

Automatic sprinklers must never be shipped or stored
where its temperature will exceed 100°F/38°C and they
must never be painted, plated, coated, or otherwise al-
tered after leaving the factory. Modified sprinklers must
be replaced. Sprinklers that have been exposed to corro-
sive products of combustion, but have not operated,
should be completely cleaned by wiping the sprinkler with
a cloth or by brushing it with a soft bristle brush.

Care must be exercised to avoid damage - before, dur-
ing, and after installation. Sprinklers damaged by drop-
ping, striking, wrench twist/slippage, or the like, must be
replaced. Also, replace any sprinkler that has a cracked
bulb or that has lost liquid from its bulb (Ref. Installation
Section).

The owner is responsible for the inspection, testing, and
maintenance of their fire protection system and devices in
compliance with this document, as well as with the appli-
cable standards of the National Fire Protection Associa-
tion (e.g., NFPA 25), in addition to the standards of any
other authorities having jurisdiction. The installing contrac-
tor or sprinkler manufacturer should be contacted relative
to any questions.

It is recommended that automatic sprinkler systems be in-
spected, tested, and maintained by a qualified Inspection
Service.

The Stealth Residential must only be replaced with pen-
dent sprinklers which are listed for residential fire protec-

GRAPH A

MAXIMUM PERMITTED VERTICAL DISTANCE BETWEEN THE SPRINKLER MOUNTING SURFACE AND

THE BOTTOM OF CEILING MOUNTED OBSTRUCTIONS SUCH AS BEAMS, OVERHANGS, AND LIGHT FIXTURES

WITHOUT UNDULY OBSTRUCTING THE WATER SPRAY DISTRIBUTION

NOTES:

1.

CEILING OBSTRUCTIONS MUST BE SPACED ON THE BASIS OF USING THE MAXIMUM RESIDUAL PRESSURE WHICH WOULD BE
PRESENT FOR A SINGLE SPRINKLER OPERATION.

2.

BEAMS AND/OR OTHER CONTINUOUS OBSTRUCTIONS ARE NOT TO EXCEED A VERTICAL DEPTH ‘V’ OF MORE THAN 3 INCHES
WITHIN THE SPRINKLER COVERAGE AREA.

STAR SPRINKLER

Page 6

1-3.1.11

TABLE B

MINIMUM VERTICAL CLEARANCE BETWEEN TOP OF

FREE STANDING OBSTRUCTION AND

SPRINKLER DEFLECTOR

Horizontal Distance From

Vertical Clearance

Sprinkler to Obstruction

Below Sprinkler

Below Sprinkler Deflector, ft.

Deflector, in.

More than 6 . .  . .  . .  . .  . .  . .  . .  . .  . .  . .  . .  . .  . .  . 24
From 3 to 6

. .  . .  . .  . .  . .  . .  . .  . .  . .  . .  . .  . .  . .  . 19

Between 2 and 3

.  . .  . .  . .  . .  . .  . .  . .  . .  . .  . .  . .  . 16

From 1 to 2

. .  . .  . .  . .  . .  . .  . .  . .  . .  . .  . .  . .  . .  . 13

Less than 1

. .  . .  . .  . .  . .  . .  . .  . .  . .  . .  . .  . .  . .  . 10

OBSOLETE

Summary of Contents for Star Stealth S240

Page 1: ...tion required by building codes WARNINGS The Stealth Residential Concealed Pendent Sprin klers described herein must be installed and main tained in compliance with this document as well as with the a...

Page 2: ...minimum required discharge from the most hydraulically demand ing single sprinkler and the NFPA 13D 13R multiple sprin kler flow rate is the minimum required discharge from each of the total number o...

Page 3: ...the Protective Cap 3 With pipe thread sealant applied to the pipe threads and using the W Type 13 Wrench positioned as shown in Figure 2 install and tighten the Sprinkler Mounting Cup Assembly into th...

Page 4: ...and larvae by gently brushing with a feather duster or gently vacuuming with a soft bristle i e dusting brush attachment Exercise suitable safety precautions in the use and storage of highly flammabl...

Page 5: ...re to be in a row which runs parallel to the ridge and the sprinklers are to be spaced a minimum of 8 feet apart d the sprinklers are installed with their deflector arms perpendicular to the ceiling r...

Page 6: ...urisdiction The installing contrac tor or sprinkler manufacturer should be contacted relative to any questions It is recommended that automatic sprinkler systems be in spected tested and maintained by...

Page 7: ...s or parts of products Tyco Fire Products shall not be responsible for sprinkler sys tem design errors or inaccurate or incomplete information supplied by Buyer or Buyer s representatives IN NO EVENT...

Page 8: ...REQUIRED SLANT DISTANCE BETWEEN A RIDGE AND A SPRINKLER WITHOUT UNDULY OBSTRUCTING THE WATER DISTRIBUTION NOTES 1 UP TO A MAXIMUM OF ONE HALF THE LENGTH OF THE COVERAGE AREA BEING HYDRAULICALLY CALCUL...

Reviews: