background image

OPERATION

The sprinkler assembly contains a
small fusible solder element. When ex-
posed to sufficient heat from a fire, the
solder melts and enables the internal
components of the sprinkler to fall
away. At this point the sprinkler acti-
vates with the deflector dropping into
its operated position (Reference Fig-
ure 1C), permitting water to flow.

INSTALLATION

The Model TFP1 must be installed in
accordance with the following instruc-
tions:

NOTES

The Protective Cap is to remain

on the sprinkler during installa-

tion and until the ceiling instal-

lation is complete. The Protective

Cap must be removed to place the

sprinkler in service.

A leak tight 1/2 inch NPT sprin-

kler joint should be obtained with

a torque of 7 to 14 ft.lbs. (9,5 to

19,0 Nm). A maximum of 21 ft.lbs.

(28,5 Nm) of torque is to be used to

install sprinklers. Higher levels

of torque may distort the sprin-

kler inlet with consequent leak-

age or impairment of the sprin-

kler.

Do not attempt to compensate for

insufficient adjustment in an Es-

cutcheon Plate by under- or over-

tightening the Sprinkler. Read-

just the position of the sprinkler

fitting to suit.

Step 1.

The Sprinkler must be installed

only in the pendent position and with
the Sprinkler waterway centerline per-
pendicular to the mounting surface.

Step 2.

Install the sprinkler fitting so

that the distance from the face of the
fitting to the mounting surface will be
nominally 29/32 inches (23,0 mm) as
shown in Figure 1A.

Step 3.

With pipe thread sealant ap-

plied to the pipe threads, hand tighten
the Sprinkler into the sprinkler fitting.

Step 4.

Wrench tighten the Sprinkler

using only the Sprinkler Socket or
Wrench & Socket Combination (Ref.
Figure 4). The wrench recess of the
Socket is to be applied to the sprinkler
wrenching area (Ref. Figure 1A).

Step 5.

Use the “ceiling level tolerance

limit” indicator on the Protective Cap to
check for proper installation height.
Relocate the sprinkler fitting as neces-
sary. If desired the Protective Cap may
also be used to locate the center of the
clearance hole by gently pushing the
ceiling material against the center
point of the Cap.

Step 6.

After the ceiling has been com-

pleted with the 2 inch (50 mm) diame-
ter clearance hole, use the Protective
Cap Removal Tool (Ref. Figure 5) to
remove the Protective Cap and then
push on the Escutcheon until its flange
just comes in contact with the ceiling.
Do not continue to push on the Es-
cutcheon such that it lifts a ceiling
panel out of its normal position. If the
Escutcheon cannot be engaged with
the Sprinkler, or the the Escutcheon
cannot be engaged sufficiently to con-
tact the ceiling, relocate the sprinkler
fitting as necessary.

CARE AND MAINTENANCE

The Model TFP1 must be maintained
and serviced in accordance with the
following instructions:

NOTES

It is the responsibility of the in-

stalling contractor to provide a

copy of this document to the

owner or his representative, and

in turn, it is the obligation of the

owner to provide a copy of this

document to a succeeding owner.

Wet pipe sprinkler systems must

be maintained at a minimum tem-

perature of 40°F/4°C to prevent

freezing and bursting of the pipe

and/or sprinklers.

Automatic sprinklers are not to be

tested with a heat source. Opera-

tion of the heat responsive ele-

ment can result.

Absence of an Escutcheon Plate

may delay the time to sprinkler

operation in a fire situation.

Before closing a fire protection

system main control valve for

maintenance work on the fire pro-

tection system which it controls,

permission to shut down the af-

fected fire protection system must

be obtained from the proper

authorities and all personnel who

may be affected by this action

must be notified.

Do NOT enclose sprinklers within

drapes, curtains, or valances.

Do NOT hang anything from the

sprinklers.

Do NOT cleanse the sprinklers

with soap and water, detergents,

ammonia, cleaning fluids, or

other chemicals. Remove dust,

lint, cobwebs, cocoons, insects,

and larvae by gently brushing

with a feather duster or gently

vacuuming with a soft bristle (i.e.,

dusting) brush attachment.

Exercise suitable safety precau-

tions in the use and storage of

highly flammable materials. The

rapid rate of fire development

and spread of which can be

FIGURE 4

TFP1 SPRINKLER SOCKET

TFP1 WRENCH & SOCKET COMBINATION

DRIVE

3/8" SOCKET

ACCEPTS

WRENCH

RECESS

WRENCH

COMBINATION

WRENCH & SOCKET

#4948

#4947

SOCKET

FIGURE 5

TFP1 PROTECTIVE CAP

REMOVAL TOOL

-5-

OBSOLETE

Close

Summary of Contents for Gem TFP1

Page 1: ...cal ad justment This adjustment reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut to help assure a perfect fit installation The Model TFP1 has been designed with heat se...

Page 2: ...rking understanding of the complete list of criteria prior to initiating the design of the sprin kler system Questions concerning sprinkler installation and usage criteria which are not covered by the...

Page 3: ...lers with respect to obstructions to water distribution are to be in accordance with the obstruction rules for extended coverage pendent sprinklers per the requirements of NFPA 13 Operational Sensitiv...

Page 4: ...orizontal b the compartment openings to adjoining spaces have minimum lintel depths of 8 inches below the lowest sprinkler c any adjacent sprinklers in the direction of the ceiling ridge are to be in...

Page 5: ...6 After the ceiling has been com pleted with the 2 inch 50 mm diame ter clearance hole use the Protective Cap Removal Tool Ref Figure 5 to remove the Protective Cap and then push on the Escutcheon unt...

Page 6: ...Buyer for ten 10 years against defects in material and work manship when paid for and properly installed and maintained under normal use and service This warranty will ex pire ten 10 years from date...

Page 7: ...G THE WATER DISTRIBUTION LOCATED ON AN INTERSECTING PITCHED CEILING COVERAGE AREAS a 20 x 20 c 16 x 16 b 18 x 18 d 14 x 14 d 12 x 12 GRAPH A MINIMUM REQUIRED HORIZONTAL DISTANCE BETWEEN A SPRINKLER LO...

Page 8: ...IS LOCATED AT A PEAK NOTES UP TO A MAXIMUM OF ONE HALF THE LENGTH OF THE COVERAGE AREA BEING HYDRAULICALLY CALCULATED THE MOUNTING SURFACE MUST BE LOCATED WITHIN 4 TO 6 INCHES OF THE PEAK IF IT IS NOT...

Reviews: