background image

sprinkler flow rates for systems de-
signed to NFPA 13D or NFPA 13R are
given in Table A as a function of tem-
perature rating and the maximum al-
lowable coverage areas. The single
sprinkler flow rate is the minimum re-
quired discharge from the most hy-
draulically demanding single sprinkler
and, the multiple sprinkler flow rate is
the minimum required discharge from
each of the total number of “design
sprinklers” as specified in NFPA 13D
or NFPA 13R.

TIA 99-1 (Tentative Interim Amend-
ment) with an effective date of May 22,
2000 states

that the minimum re-

quired discharge from each of the “de-
sign sprinklers” for systems designed
to NFPA 13 must be calculated based
on delivering a minimum design den-
sity of 0.1 gpm/sq. ft. for each of the
listed coverage areas shown in Table
A. Consult with the Authority Having
Jurisdiction regarding the application
of  this TIA to  the currently adopted
NFPA 13.

For systems designed  to NFPA 13,
13D, or 13R, consult with the local
authority having jurisdiction with re-
gard to the number of “design sprin-
klers”

for

sloped ceilings having a

slope greater than a 2 inch rise for a
12 inch run.

Spray Coverage Criteria.

Figure 2

and 3 provide spacing rules that must
be followed to assure that the Model
TFP1 Sprinklers will provide their de-
sign distribution of water spray.

Location of sprinklers with respect to
obstructions to water distribution are to
be in accordance with the obstruction
rules for extended coverage pendent
sprinklers per the requirements of
NFPA 13.

Operational Sensitivity Criteria.

For

proper operational sensitivity, the
Model TFP1 must be installed beneath
a solid ceiling having a smooth or tex-
tured surface.

The Model TFP1 must

NOT

be used

above or below open-gridded type sus-
pended ceilings; beneath soffits or
beams exceeding 3 inches in height;
or, with beams, joists, or ducts having
a height of more than 3 inches located
within the  sprinkler coverage areas.
Beams having a height of more than 3
inches may be located with their cen-
terlines along the boundaries separat-
ing adjacent sprinkler coverage areas.

Cold Soldering Criteria.

Figures 2

and 3 provide the minimum spacing
requirements necessary for prevent-
ing the wetting (i.e., cold soldering) of
the heat responsive element of a non-
operated Model TFP1, which is adja-
cent to one which has operated.

Heat Source Criteria.

Refer to NFPA

13D or NFPA 13R for the requirements
relating to preventing the possible re-
lease of a Model TFP1 heat responsive

element, due to exposure to heat
sources other than abnormal fire.

FIGURE 2

SPACING RULES UNDER LEVEL CEILINGS

S =THE LENGTH OF THE COVERAGE AREA BEING HY-
DRAULICALLY CALCULATED (REF. TABLE A).

Figure 2-1 (Plan View)

Figure 2-2 (Plan View)

Figure 2-3 (Plan View)

Figure 2-4 (Plan View)

Figure 2-5 (Plan View)

Figure 2-6 (Plan View)

Figure 2-7 (Plan View)

Figure 2-8 (Plan View)

-3-

OBSOLETE

Close

Summary of Contents for Gem TFP1

Page 1: ...cal ad justment This adjustment reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut to help assure a perfect fit installation The Model TFP1 has been designed with heat se...

Page 2: ...rking understanding of the complete list of criteria prior to initiating the design of the sprin kler system Questions concerning sprinkler installation and usage criteria which are not covered by the...

Page 3: ...lers with respect to obstructions to water distribution are to be in accordance with the obstruction rules for extended coverage pendent sprinklers per the requirements of NFPA 13 Operational Sensitiv...

Page 4: ...orizontal b the compartment openings to adjoining spaces have minimum lintel depths of 8 inches below the lowest sprinkler c any adjacent sprinklers in the direction of the ceiling ridge are to be in...

Page 5: ...6 After the ceiling has been com pleted with the 2 inch 50 mm diame ter clearance hole use the Protective Cap Removal Tool Ref Figure 5 to remove the Protective Cap and then push on the Escutcheon unt...

Page 6: ...Buyer for ten 10 years against defects in material and work manship when paid for and properly installed and maintained under normal use and service This warranty will ex pire ten 10 years from date...

Page 7: ...G THE WATER DISTRIBUTION LOCATED ON AN INTERSECTING PITCHED CEILING COVERAGE AREAS a 20 x 20 c 16 x 16 b 18 x 18 d 14 x 14 d 12 x 12 GRAPH A MINIMUM REQUIRED HORIZONTAL DISTANCE BETWEEN A SPRINKLER LO...

Page 8: ...IS LOCATED AT A PEAK NOTES UP TO A MAXIMUM OF ONE HALF THE LENGTH OF THE COVERAGE AREA BEING HYDRAULICALLY CALCULATED THE MOUNTING SURFACE MUST BE LOCATED WITHIN 4 TO 6 INCHES OF THE PEAK IF IT IS NOT...

Reviews: