background image

NOTE

Use of overhangs or soffits with

dimensions exceeding the above

specified criteria is permitted if

additional sprinkler protection is

provided for the area below the

overhang/soffit.

The F685 Sprinklers must NOT be lo-
cated

1. along a wall/partition having a re-

cessed range oven, countertop, or
alcove,

2. along a wall/partition having an ad-

joining wood or coal burning stove,
or

3. along a wall/partition containing a

fireplace or wall oven.

NOTE

The spray from the F685 is dis-

tributed radially outward and

downward from the sprinkler

deflector. Consequently, the

sprinklers must be located

such that there will not be any

blind spaces shielded from

spray by partitions, room di-

viders, overhangs or other

parts of the dwelling structure.

Operational Sensitivity Criteria.

The

F685 Sprinklers must only be installed

1. beneath level ceilings,

2. beneath solid ceilings having a

smooth or textured surface,

3. with a deflector-to-wall surface dis-

tance of 1-1/2 to 6 inches or a deflec-
tor-to soffit surface distance of 1-1/2
to 3 inches when using a flush mount
mount escutcheon as shown in Fig-
ure B-1, unless the Model F705 Re-
cessed Escutcheon is being utilized
as shown in Figure B-2.

4. with a deflector-to-ceiling distance

per Table A, and

5. at least 4 inches away from an inside

or outside corner.

The F685 Sprinklers must

NOT

be

used

1. beneath soffits or overhangs, unless

they are only providing protection for
the area underneath the soffit/over-
hang and additional sprinkler protec-
tion is provided for the area in front
of the soffit/overhang,

2. above or below open-gridded type

suspended ceilings, or

3. with beams, joists, or ducts located

within the sprinkler coverage areas.

NOTE

Where utilized, beams, joists, or

ducts must be located with their

centerlines along the boundaries

separating adjacent sprinkler

coverage areas.

It is recommended that as part of the
sprinkler system design, the designer
review the dwelling plans and, where
appropriate, advise the owner or his
representative as to the following.

I. Lintels of at least 3 inches in height

and preferably 8 inches should be
used over all passageways from one
space to another, in order to reduce
the possibility of sprinkler operations
outside of the fire area.

II. Beams of at least 3 inches of height

should be used to border each of 3
or  more adjoining areas of F685
Sprinkler coverage (within the same
compartment), in order to decrease
the time to first sprinkler operation as
well as to reduce the possibility of
multiple sprinkler operations.

Cold Soldering Criteria.

With refer-

ence to Table A, the F685 Sprinklers
must be located such that

1. the minimum lateral distance “C” be-

tween adjacent sprinklers is 8 feet,
and

2. the minimum distance “D” between

sprinklers located opposite or with
their waterway centerlines at 90° to
each other is 14 feet, except where
a portion of the dwelling structure or
a partition will shield the spray of one
sprinkler from the other.

Heat Source Criteria.

Refer to NFPA

13D and NFPA 13R for the require-
ments relating to preventing the possi-
ble release of an F685 heat responsive
element (Bulb), due to exposure  to
heat sources other than abnormal fire.

—5—

NOTES:

1. For a given position within the coverage area, ceiling mounted obstructions must not

hang below the elevation dimension given in the graph.

2. Elevation dimensions are with respect to the top of the Deflector Hat (Ref. Figure A),

where positive (+) dimensions are above the Deflector Hat and negative (-) dimen-
sions are below. (Reference: the Deflector Hat is 5/16" above the sprinkler centerline
of waterway.)

FIGURE C

ALLOWABLE ELEVATION FOR CEILING MOUNTED OBSTRUCTIONS

SUCH AS HEATING OR AIR CONDITIONING DIFFUSERS, OVERHANGS

AND LIGHT FIXTURES

OBSOLETE

Summary of Contents for Gem F685

Page 1: ...or up to 1 2 inch 12 7 mm of total adjustment from the flush sidewall position The F705 has a separable two piece design which allows installation of the sprinklers and pressure testing of the fire pr...

Page 2: ...his condition consult the authorities having jurisdiction for guidance and approval It is the responsibility of an in stalling contractor to provide a copy of this document to the owner or his represe...

Page 3: ...SED DIMENSIONS Up to 1 4 inch adjustment from minimum 1 4 inch to maximum 1 2 inch recessed position HIGH ADJUSTMENT DIMENSIONS Up to 1 2 inch adjustment from the flush sidewall position to 1 2 inch r...

Page 4: ...ided by the manu facturer NOTES 1 Residential Fire Sprinkler Sys tems should only be designed and installed by those compe tent and completely familiar with automatic sprinkler sys tem design installa...

Page 5: ...nterlines along the boundaries separating adjacent sprinkler coverage areas It is recommended that as part of the sprinkler system design the designer review the dwelling plans and where appropriate a...

Page 6: ...can be used to com pensate for the possible manufac turing variations in the take out of the fitting as well as in the make in of the sprinklers as permitted by ANSI B1 20 1 3 After installing the F7...

Page 7: ...the heat responsive element Bulb can result Do NOT cleanse the sprinklers with soap and water detergents ammonia cleaning fluids or other chemicals Remove dust lint cobwebs cocoons insects and larvae...

Page 8: ...sh 155 F 68 C PSN 51 685 9 155 Natural Brass Finish 155 F 68 C PSN 51 685 1 155 White Polyester Finish 155 F 68 C PSN 51 685 4 155 Chrome Plated Finish 175 F 79 C PSN 51 685 9 175 Natural Brass Finish...

Reviews: