shielded from the water spay of higher
elevation sprinklers which could oper-
ate earlier during a fire. Intermediate
Level Sprinklers are also used in appli-
cations such as beneath open gridded
catwalks.

Lead coatings are utilized to extend
the life of copper alloy sprinklers be-
yond that which would otherwise be
obtained when exposed to corrosive
atmospheres. Although lead coated
sprinklers have passed the standard
corrosion tests of the applicable ap-
proval agencies, the testing is not rep-
resentative of all possible corrosive at-
mospheres.

Consequently,

it

is

recommended  that the end user be
consulted with respect to the suitability
of these corrosion resistant coatings
for any given corrosive environment.
The effects of ambient temperature,
concentration

of

chemicals,

and

gas/chemical velocity, should be con-
sidered, as a minimum, along with the
corrosive nature of the chemical to
which the sprinklers will be exposed.

APPROVALS AND STANDARDS

Laboratory listings and approvals for
the 5.6 and 8.0 K-Factor Model A In-
termediate Level Sprinklers are given
in Table A.

WARNING

The 5.6 and 8.0 K-Factor Model A

Intermediate Level Sprinklers de-

scribed herein must be installed and

maintained in compliance with this

document, as well as applicable

standards of the National Fire Protec-

tion Association, in addition to the

standards of any other authorities

having jurisdiction. Failure to do so

may impair the integrity of these de-

vices.
The owner is responsible for main-

taining their fire protection system

and devices in proper operating con-

dition. The installing contractor or

manufacturer should be contacted

relative to any questions.

TECHNICAL DATA

The 5.6 and 8.0 K-Factor Model A In-
termediate Level Sprinklers are rated
for use at a maximum service pressure
of 175 psi (12,1 bar) and they are avail-
able  in  the  temperature ratings  and
finishes indicated in Table A.

The nominal flow “Q” in GPM (LPM) is
determined by the following formula:

Q=Kp

1/2

where the nominal discharge coeffi-
cient “K” equals 5.6 (80,7) or 8.0
(115,2) and “p” equals the residual
flowing pressure in psi (bar).

The quick response Model A Interme-
diate Level Sprinklers are obtained by
assembling the Q-67 Pendent Shield
or the Q-66 Upright Shield, as applica-
ble, to the basic pendent or upright
sprinklers. The quick response 5.6 K-
Factor Model A Sprinklers are de-
scribed

in

Technical

Data

Sheet

TD515M and the quick response 8.0
K-Factor Model A Sprinklers are de-
scribed in TD525Q. The quick re-

sponse Model A Sprinklers utilize a 3
mm diameter frangible bulb. Table A
indicates the bulb liquid color as a
function of temperature rating.

The Q-66 and Q-67 Shields are fabri-
cated from a low carbon sheet steel
and are furnished zinc coated with a
clear chromate finish. In the case of
the pendent assembly, the Q-67 Pen-
dent Shield and O-Ring shown in Fig-
ure A are field assembled to the Model
A Pendent Sprinkler. The O-Ring
forms a water seal when it is slightly
compressed between the Shield and
sprinkler fitting. In the case of the up-
right assembly shown in Figure A, the
Q-66 Upright Shield is factory assem-
bled to the Model A Upright Sprinkler
with a Screw that is secured in position
with an adhesive.

NOTES

Inquiries concerning the appropriate-

ness of lead coated sprinklers for a

given corrosive environment should

be submitted to the attention of the

Technical Services Department.
Lead coated sprinklers are not suit-

able for use in open sprinkler applica-

tions.

†

DuPont Registered Trademark

TYPE

TEMPERATURE

RATING

BULB

LIQUID

COLOR

NATURAL

BRASS

Zinc Chromate

Shield

CHROME

PLATED

Zinc Chromate

Shield

135°F/57°C

286°F/141°C

5.6K

UPRIGHT

(G7333)

and

8.0K

UPRIGHT

(G7343)

SPRINKLER FINISH

1, 2, 3, 4

Orange

Red

Yellow

Green

Blue

155°F/68°C

175°F/79°C

200°F/93°C

NOTES:

1. Listed by Underwriters Laboratories, Inc. as Quick Response Sprinklers.
2. Listed by Underwriters’ Laboratories of Canada as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation as Quick Response Rack Storage Sprinklers.
4. Accepted by the City of New York under MEA241-94-E as Quick Response Sprinklers.
N/A: Not Available

TABLE A

LABORATORY LISTINGS AND APPROVALS

LEAD

COATED

1, 2, 3

5.6K

PENDENT

(G7371)

and

8.0K

PENDENT

(G7391)

135°F/57°C

Orange

155°F/68°C

Red

175°F/79°C

Yellow

200°F/93°C

Green

286°F/141°C

Blue

1, 2, 3, 4

N/A

FIGURE B

W-TYPE 6 SPRINKLER WRENCH

WRENCH RECESS

(END "A" USED FOR

1/2" NPT MODELS)

WRENCH RECESS

(END "B" USED FOR

3/4" NPT MODELS)