Tyco Electronics Integra Ci3 Installation Instruction Download Page 7

 

7

Project 2187 Drawing No. CI-3K51101 Rev 10 
DMR 2720 18/07/11 

Modbus is a Trademark of Schneider Automation Inc.  Other Trademarks or company 
names mentioned herein are the property of their respective owners.

 

5.6.2 bAUd (Baud rate) 

Scroll through the following options: 

 2400 

 4800 

 9600 

 19200 

 38400 

Once the desired baud rate has been found press   to confirm. 

 
5.6.3 PARI (Parity) 

Scroll through the following options: 

 None 

 Odd 

 Even 

Once the required parity has been selected press   to confirm. 

 
5.6.4 STOP (Stop Bits)* 

*Note: This function is only enabled if Parity (5.6.3) is set to “None”. 
Scroll through the following options: 

 None 

 Odd 

 Even 

Once the required stop bits have been selected press   to confirm. 

 
5.6.5 Addr (Device Address) 

The instrument will only allow valid Modbus protocol addresses in the range of 1-247 or Johnson 
Controls addresses in the range 1-255. 
Use the 

 and   buttons to set the digit to the desired number then press   to confirm. 

Repeat this process until the desired 3 digit address has been set.

 

 
5.6.6 Ordr (Floating Point Byte Order)* 

This screen displays the floating point number byte order, either Norm (Normal) or Rev (Reverse). 
*Note: No adjustment of this parameter is allowed via the front of the Integra Ci3 digital meter.  Changes 
to the floating point number byte order must be made on the Modbus system; for information on how to 
adjust this setting please refer to the Integra Communications Guide, available from our web-site. 

 
5.7 RLY (Relay) 

This screen allows the adjustment of all parameters that are required for the optional Pulse Relay Module (if 
fitted).  Selecting this screen opens a sub menu of relay parameters: 

 

5.7.1 OP1 (Relay Output 1) 

This screen allows the user to assign Pulse Relay Output 1 to measure either None, kWh or kVArh. 
Scroll through the following options: 

 None (Relay 

disabled) 

 

KWh 

(kWh pulsed output) 

 

KVAr 

(kVArh pulsed output) 

Once the required pulsed output setting has been selected press   to confirm. 

 
5.7.2 OP2 (Relay Output 2) 

This screen allows the user to assign Pulse Relay Output 2 to measure either None, kWh or kVArh. 
Scroll through the following options: 

 None (Relay 

disabled) 

 

KWh 

(kWh pulsed output) 

 

KVAr 

(kVArh pulsed output) 

Once the required pulsed output setting has been selected press   to confirm. 

 

Summary of Contents for Integra Ci3

Page 1: ...120 350V DC All connections are made to screw clamp terminals that accept 0 05 2 5mm2 stranded or solid core cables Terminal screws are fully tightened for shipment and must be undone before wire inse...

Page 2: ...first screen provides a visual check of the LCD screen by lighting up all the LCD segments The second displays the unit s firmware version whilst the third displays a start up self test result If thi...

Page 3: ...old the and the buttons simultaneously for five seconds This displays the password entry screen Password protection is designed to prevent unauthorised access to Set up screens Password is normally se...

Page 4: ...our Reset kWhr kVAhr counters dMd Reset demand counters COMS Communications PROT Protocol Select from Modb Modbus N2 Johnson Controls bAUd Baud rate Select from 2400 4800 9600 19200 38400 PARI Parity...

Page 5: ...button to scroll down the menu until you see the CT primary setting screen Press the button to enter the CT primary setting screen The first digit should start flashing Use the and buttons to set the...

Page 6: ...and power readings are integrated for maximum demand measurement The values displayed are in minutes Use the and buttons to scroll through the following options 60 60 minutes 30 30 minutes 20 20 minut...

Page 7: ...oating Point Byte Order This screen displays the floating point number byte order either Norm Normal or Rev Reverse Note No adjustment of this parameter is allowed via the front of the Integra Ci3 dig...

Page 8: ...n and off alternate halves of the LCD segments to determine if any are stuck either on or off PHAS SEQ This test determines if the Voltage and Current connections to the Ci3 meter are correct If all t...

Page 9: ...when the sliding window does not yet contain a full set of readings i e the elapsed time since the demands were last reset or the elapsed time since the Integra Ci3 digital meter was switched on is le...

Page 10: ...fe may be present at some of the terminals of this unit Installation and servicing should be performed only by qualified properly trained personnel abiding by local regulations Ensure all supplies are...

Page 11: ...quired a panel gasket must be used The terminals at the rear of the product must be protected from liquids or other contamination This unit is intended for indoor use only at an altitude of less than...

Page 12: ...both lines are fused Choose fuses of a type and with a breaking capacity appropriate to the supply and in accordance with local regulations A suitable switch or circuit breaker conforming to the relev...

Page 13: ...w 5 of Range Maximum voltage current indication may only be approximate Voltage Ci3 VT 5 of Range Maximum to 120 of Potential Transformer secondary voltage below 5 of Range Maximum voltage current ind...

Page 14: ...0 5 of range maximum Current A 0 5 of range maximum 4 for I2 in three wire mode Neutral current calculated A 4 of range maximum Frequency Hz 0 1 Hz Power factor PF 1 of unity Active power W 1 of rang...

Page 15: ...respective owners Environmental Operating temperature 10 C to 55 C Storage temperature 20 C to 70 C Relative humidity 0 to 90 non condensing Shock 30g in 3 planes Vibration 10Hz to 50Hz IEC 60068 2 6...

Page 16: ...r any guarantee that such information is accurate correct reliable or current Tyco Electronics reserves the right to make any adjustments to the information at any time Tyco Electronics expressly disc...

Reviews: