Tyco Electronics Integra Ci3 Installation Instruction Download Page 11

 

11

Project 2187 Drawing No. CI-3K51101 Rev 10 
DMR 2720 18/07/11 

Modbus is a Trademark of Schneider Automation Inc.  Other Trademarks or company 
names mentioned herein are the property of their respective owners.

 

 

 
7.1 Checks and Cleaning 

The front of the case should be gently wiped with a dry cloth only.  Do not apply any pressure over the 
central rectangular display viewing window area.  If necessary wipe the rear case with a dry cloth.  If a 
cleaning agent is necessary, isopropyl alcohol is the only recommended agent and should be used 
sparingly.  Water should not be used.  If the rear case exterior or terminals should accidentally be 
contaminated with water, the unit must be thoroughly dried before further service.  Should it be suspected 
that water or other contaminants might have entered the unit, factory inspection and refurbishment is 
recommended.  In normal use, little maintenance is needed.  As appropriate for service conditions, isolate 
electrical power, inspect the unit and remove any dust or other foreign material present.  Periodically check 
all connections for freedom from corrosion and screw tightness, particularly if vibration is present.  The front 
display window also acts as an insulating barrier.  It is not possible to touch, by hand, any live part, even if 
the window is completely missing, but if the window is perforated or significantly damaged in any other way, 
repair is required.  In the unlikely event of a repair being necessary, it is recommended that the unit be 
returned to factory.

 

 
7.2 Location and Mounting 

Units are suitable for panel mounting only and should be installed in a dry position, where the ambient 
temperature is reasonably stable and will not be outside the range -10 to +55°C.  Vibration should be kept to 
a minimum.  Preferably mount the Integra Ci3 digital meter so that the display contrast is not reduced by 
direct sunlight or other high intensity lighting.  The Integra may be mounted in a standard DIN 96 panel up to 
a maximum thickness of 5 mm. Mounting is by four integral retention clips.  Terminals should be 
inaccessible after installation.  Consideration should be given to the space required above and below the 
instrument to allow for associated cables.  If IP54 ingress protection is required, a panel gasket must be 
used.  The terminals at the rear of the product must be protected from liquids or other contamination.  This 
unit is intended for indoor use only at an altitude of less than 2000m. 

 
7.3 Electromagnetic Compatibility 

This unit has been designed to provide protection against EM (electro-magnetic) interference in line with EU 
requirements and other regulations.  Precautions necessary to provide proper operation of this, and 
adjacent, equipment will be installation dependent and so the following can only be general guidance: 
• Avoid routing the wiring to this unit alongside cables and products that are, or could be, a source of 
interference. 
• The auxiliary supply to the unit should not be subject to excessive interference.  In some cases, a supply 
line filter may be required. 
• To protect the product against incorrect operation or permanent damage, surges and transients must be 
controlled.  It is good EMC practice to suppress transients and surges at the source.  The unit has been 
designed to automatically recover from typical transients; however in extreme circumstances it may be 
necessary to temporarily disconnect the auxiliary supply for a period of greater than 10 seconds to restore 
correct operation. 
• Screened communication and small signal leads are recommended and may be required.  These and other 
connecting leads may require the fitting of RF suppression components such as ferrite absorbers, line filters 
etc., if RF fields cause problems. 
• It is good practice to install sensitive electronic instruments that are performing critical functions in EMC 
enclosures that protect against electrical interference causing a disturbance in function. 

 

 
7.4 Metered Supply Wiring 

 

Input connections are made to screw clamp terminals.  Choice of cable should meet local regulations for the 
operating voltage and current.  

The current inputs of this product are designed for connection into 

systems via current transformers only.  

Instrument transformers used for connection to the meter must be of 

approved type and compliant with ANSI/IEEE C57.13 or IEC 60044-1, selected and sized appropriate to the 
supply network being monitored.  All negative current inputs are commoned inside the unit and grounding should 
be at one point only.  To minimise measurement errors, the CTs should be grounded as shown in the wiring 
diagram.  CT secondaries must be grounded in accordance with local regulations.  It is desirable to make 

Summary of Contents for Integra Ci3

Page 1: ...120 350V DC All connections are made to screw clamp terminals that accept 0 05 2 5mm2 stranded or solid core cables Terminal screws are fully tightened for shipment and must be undone before wire inse...

Page 2: ...first screen provides a visual check of the LCD screen by lighting up all the LCD segments The second displays the unit s firmware version whilst the third displays a start up self test result If thi...

Page 3: ...old the and the buttons simultaneously for five seconds This displays the password entry screen Password protection is designed to prevent unauthorised access to Set up screens Password is normally se...

Page 4: ...our Reset kWhr kVAhr counters dMd Reset demand counters COMS Communications PROT Protocol Select from Modb Modbus N2 Johnson Controls bAUd Baud rate Select from 2400 4800 9600 19200 38400 PARI Parity...

Page 5: ...button to scroll down the menu until you see the CT primary setting screen Press the button to enter the CT primary setting screen The first digit should start flashing Use the and buttons to set the...

Page 6: ...and power readings are integrated for maximum demand measurement The values displayed are in minutes Use the and buttons to scroll through the following options 60 60 minutes 30 30 minutes 20 20 minut...

Page 7: ...oating Point Byte Order This screen displays the floating point number byte order either Norm Normal or Rev Reverse Note No adjustment of this parameter is allowed via the front of the Integra Ci3 dig...

Page 8: ...n and off alternate halves of the LCD segments to determine if any are stuck either on or off PHAS SEQ This test determines if the Voltage and Current connections to the Ci3 meter are correct If all t...

Page 9: ...when the sliding window does not yet contain a full set of readings i e the elapsed time since the demands were last reset or the elapsed time since the Integra Ci3 digital meter was switched on is le...

Page 10: ...fe may be present at some of the terminals of this unit Installation and servicing should be performed only by qualified properly trained personnel abiding by local regulations Ensure all supplies are...

Page 11: ...quired a panel gasket must be used The terminals at the rear of the product must be protected from liquids or other contamination This unit is intended for indoor use only at an altitude of less than...

Page 12: ...both lines are fused Choose fuses of a type and with a breaking capacity appropriate to the supply and in accordance with local regulations A suitable switch or circuit breaker conforming to the relev...

Page 13: ...w 5 of Range Maximum voltage current indication may only be approximate Voltage Ci3 VT 5 of Range Maximum to 120 of Potential Transformer secondary voltage below 5 of Range Maximum voltage current ind...

Page 14: ...0 5 of range maximum Current A 0 5 of range maximum 4 for I2 in three wire mode Neutral current calculated A 4 of range maximum Frequency Hz 0 1 Hz Power factor PF 1 of unity Active power W 1 of rang...

Page 15: ...respective owners Environmental Operating temperature 10 C to 55 C Storage temperature 20 C to 70 C Relative humidity 0 to 90 non condensing Shock 30g in 3 planes Vibration 10Hz to 50Hz IEC 60068 2 6...

Page 16: ...r any guarantee that such information is accurate correct reliable or current Tyco Electronics reserves the right to make any adjustments to the information at any time Tyco Electronics expressly disc...

Reviews: