Input 
 

Nominal Input voltage 

                               

  CI3-01                                  100 to 289V AC L-N (173 to 500V AC L-L) 

                                 CI3-VT                                  60 to 120V AC L-N (104 to 208V AC L-L) 
Max. continuous input overload voltage   

120% of nominal (Maximum 600V AC L-L) 

Max. short duration input voltage 

2 x range maximum (1 second application repeated 5 times at 5 
minute intervals) 

Nominal input voltage burden    

 

< 0.2VA per phase 

Nominal input current    

 

 

5A AC rms 

Max. continuous input overload current   

120% of nominal 

Max. short duration input current 

10 x nominal (1 second application repeated 5 times at 5 
minute intervals) 

Frequency 

 

    45 

to 

66Hz 

Burden                                                                 5VA nominal 
 

Auxiliary 

Operating range  

110 to 400V AC nominal ±10% (99-440V AC absolute limits) 
120 to 350V DC nominal ±20% (96-420V DC absolute limits) 

 
Accuracy 

Voltage 

(V) 

 

    0.5% 

of 

range 

maximum 

Current 

(A) 

 

    0.5% 

of 

range 

maximum

 (4% for I2 in three wire mode)

 

Neutral current calculated (A) 

 

 

4% of range maximum 

Frequency 

(Hz) 

    0.1 

Hz 

Power 

factor 

(PF) 

 

   1% 

of 

unity 

Active power (W)  

 

 

 

± 1% of range maximum 

Reactive power (VAr)    

 

 

± 1% of range maximum 

Apparent power (VA)    

 

 

± 1% of range maximum 

Active energy (kWh)  

 

 

 

Class 1 (IEC 62053-21) 

Reactive energy (kVArh)  

 

 

± 1% of range maximum 

THD 

     1% 

up 

to 

31

st

 harmonic 

Response time to step input 

 

 

1s typical to >99% of final value 

 

Output modules (optional) 

Pulsed output relays 

 

 

 

1 per module 
(maximum of 2 modules fitted per 

Integra Ci3 digital meter

Contact rating   

 

 

50mA max at 250V AC 

Type 

    Solid 

state 

relay 

RS485 output module   

 

 

1 channel per module 
(maximum of 1 module fitted per 

Integra Ci3 digital meter

Type 

 

    2-wire 

half 

duplex 

Baud rate  

 

 

 

2400, 4800, 9600, 19200, 38400 

 
Enclosure 

Style 

     DIN 

96 

panel 

mount 

Dimensions 

96x96x64.1mm (depth behind panel front without module 
58mm, with module 82.5mm) 

Panel 

cut-out 

    92x92mm 

Panel 

thickness 

    1 

to 

5mm 

Front 

protection 

rating 

   IP52 

Case 

protection 

rating 

   IP30 

Material 

     Polycarbonate 

to 

UL94V0 

Weight 

     300g 

Terminals 

 

 

 

 

Shrouded screw-clamp 0.05 to 2.5mm

2

 wire 

      Tighten 

to 

0.5 

Nm 

(4.4 

lbf 

in) 

 

Summary of Contents for Integra Ci3

Page 1: ...120 350V DC All connections are made to screw clamp terminals that accept 0 05 2 5mm2 stranded or solid core cables Terminal screws are fully tightened for shipment and must be undone before wire inse...

Page 2: ...first screen provides a visual check of the LCD screen by lighting up all the LCD segments The second displays the unit s firmware version whilst the third displays a start up self test result If thi...

Page 3: ...old the and the buttons simultaneously for five seconds This displays the password entry screen Password protection is designed to prevent unauthorised access to Set up screens Password is normally se...

Page 4: ...our Reset kWhr kVAhr counters dMd Reset demand counters COMS Communications PROT Protocol Select from Modb Modbus N2 Johnson Controls bAUd Baud rate Select from 2400 4800 9600 19200 38400 PARI Parity...

Page 5: ...button to scroll down the menu until you see the CT primary setting screen Press the button to enter the CT primary setting screen The first digit should start flashing Use the and buttons to set the...

Page 6: ...and power readings are integrated for maximum demand measurement The values displayed are in minutes Use the and buttons to scroll through the following options 60 60 minutes 30 30 minutes 20 20 minut...

Page 7: ...oating Point Byte Order This screen displays the floating point number byte order either Norm Normal or Rev Reverse Note No adjustment of this parameter is allowed via the front of the Integra Ci3 dig...

Page 8: ...n and off alternate halves of the LCD segments to determine if any are stuck either on or off PHAS SEQ This test determines if the Voltage and Current connections to the Ci3 meter are correct If all t...

Page 9: ...when the sliding window does not yet contain a full set of readings i e the elapsed time since the demands were last reset or the elapsed time since the Integra Ci3 digital meter was switched on is le...

Page 10: ...fe may be present at some of the terminals of this unit Installation and servicing should be performed only by qualified properly trained personnel abiding by local regulations Ensure all supplies are...

Page 11: ...quired a panel gasket must be used The terminals at the rear of the product must be protected from liquids or other contamination This unit is intended for indoor use only at an altitude of less than...

Page 12: ...both lines are fused Choose fuses of a type and with a breaking capacity appropriate to the supply and in accordance with local regulations A suitable switch or circuit breaker conforming to the relev...

Page 13: ...w 5 of Range Maximum voltage current indication may only be approximate Voltage Ci3 VT 5 of Range Maximum to 120 of Potential Transformer secondary voltage below 5 of Range Maximum voltage current ind...

Page 14: ...0 5 of range maximum Current A 0 5 of range maximum 4 for I2 in three wire mode Neutral current calculated A 4 of range maximum Frequency Hz 0 1 Hz Power factor PF 1 of unity Active power W 1 of rang...

Page 15: ...respective owners Environmental Operating temperature 10 C to 55 C Storage temperature 20 C to 70 C Relative humidity 0 to 90 non condensing Shock 30g in 3 planes Vibration 10Hz to 50Hz IEC 60068 2 6...

Page 16: ...r any guarantee that such information is accurate correct reliable or current Tyco Electronics reserves the right to make any adjustments to the information at any time Tyco Electronics expressly disc...

Reviews: