Tyco Electronics Integra Ci3 Installation Instruction Download Page 12

 

12

Project 2187 Drawing No. CI-3K51101 Rev 10 
DMR 2720 18/07/11 

Modbus is a Trademark of Schneider Automation Inc.  Other Trademarks or company 
names mentioned herein are the property of their respective owners.

 

provision for shorting links to be made across CTs to permit easy replacement of a unit should this ever be 
necessary. 

All connections are made to screw clamp terminals.  Terminals are suitable for copper wires only and will accept 
one stranded 0.05 - 2.5mm

2

 (30 - 12AWG) stranded or solid core cables. Instruments are intended for panel 

mounting. Terminals must be enclosed within the panel. Use wire rated at 600V for main terminals, 60°C 
minimum temperature.  Terminal screws are fully tightened for shipment and must be undone before wire 
insertion.  Terminal screws should be tightened to 0.5 Nm (4.4 lbf in) only. 

Additional considerations for three wire systems 

The neutral terminal (terminal N) is indirectly connected to the voltage input terminals (terminals L1, L2, L3).  
When connected to a three wire system the neutral terminal will adopt a potential somewhere between the 
remaining lines.  If external wiring is connected to the neutral terminal it must be connected to either the neutral 
line or earth (ground) to avoid the possibility of electric shock from the neutral terminal. 

Fusing 

This unit must be fitted with external fuses in voltage and auxiliary supply lines.  Voltage input lines must be 
fused with a fast blow fuse 1A maximum.  Auxiliary supply lines must be fused with a slow blow fuse rated 1A 
maximum (if product is powered line-to-line, ensure both lines are fused).  Choose fuses of a type and with a 
breaking capacity appropriate to the supply and in accordance with local regulations. 
A suitable switch or circuit breaker conforming to the relevant parts of IEC 60947-1 and IEC 60947-3 should be 
included in the installation.  It should be positioned so as to be easy to operate, in close proximity to the 
equipment, and clearly identified as the disconnecting device. 

Earth/Ground Connections 

For safety reasons, current transformer secondary connections should be grounded in accordance with local 
regulations.  Under no circumstances should the product be operated without this Earth connection. 

 

8. Auxiliary and Output Connections 
 

8.1 Auxiliary Supply 

The auxiliary supply is rated at 100-400V AC ± 10%, 120-350 DC ±20%.  The Integra Ci3 digital meter 
should ideally be powered from a dedicated supply, however it may be powered from the signal source 
providing the source remains within tolerance of the auxiliary supply voltage range. 

 

8.2 Output Connections 

 
8.2.1 RS485 module Option 

The recommended cable between the RS485 master and the Integra Ci3 digital meter is two core 
screened cable.  Preferably select a cable specifically recommended for RS485 use (for example Belden 
9860, 8761) although for shorter distances of a few metres most two core screened cables will usually 
be satisfactory.  Cable length (transmission distance) can be up to 1200 metres in good conditions.  
Electrical interference or other adverse conditions may reduce the maximum cable length possible. 

8.2.2 Pulse Relay Module Option 

Up to 2 solid state relays can be fitted, if there is no RS485 module fitted.  Relay rating is 250V, 50mA, 
maximum.  Lines connected to these terminals must be either short in length or filtered where 
appropriate. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for Integra Ci3

Page 1: ...120 350V DC All connections are made to screw clamp terminals that accept 0 05 2 5mm2 stranded or solid core cables Terminal screws are fully tightened for shipment and must be undone before wire inse...

Page 2: ...first screen provides a visual check of the LCD screen by lighting up all the LCD segments The second displays the unit s firmware version whilst the third displays a start up self test result If thi...

Page 3: ...old the and the buttons simultaneously for five seconds This displays the password entry screen Password protection is designed to prevent unauthorised access to Set up screens Password is normally se...

Page 4: ...our Reset kWhr kVAhr counters dMd Reset demand counters COMS Communications PROT Protocol Select from Modb Modbus N2 Johnson Controls bAUd Baud rate Select from 2400 4800 9600 19200 38400 PARI Parity...

Page 5: ...button to scroll down the menu until you see the CT primary setting screen Press the button to enter the CT primary setting screen The first digit should start flashing Use the and buttons to set the...

Page 6: ...and power readings are integrated for maximum demand measurement The values displayed are in minutes Use the and buttons to scroll through the following options 60 60 minutes 30 30 minutes 20 20 minut...

Page 7: ...oating Point Byte Order This screen displays the floating point number byte order either Norm Normal or Rev Reverse Note No adjustment of this parameter is allowed via the front of the Integra Ci3 dig...

Page 8: ...n and off alternate halves of the LCD segments to determine if any are stuck either on or off PHAS SEQ This test determines if the Voltage and Current connections to the Ci3 meter are correct If all t...

Page 9: ...when the sliding window does not yet contain a full set of readings i e the elapsed time since the demands were last reset or the elapsed time since the Integra Ci3 digital meter was switched on is le...

Page 10: ...fe may be present at some of the terminals of this unit Installation and servicing should be performed only by qualified properly trained personnel abiding by local regulations Ensure all supplies are...

Page 11: ...quired a panel gasket must be used The terminals at the rear of the product must be protected from liquids or other contamination This unit is intended for indoor use only at an altitude of less than...

Page 12: ...both lines are fused Choose fuses of a type and with a breaking capacity appropriate to the supply and in accordance with local regulations A suitable switch or circuit breaker conforming to the relev...

Page 13: ...w 5 of Range Maximum voltage current indication may only be approximate Voltage Ci3 VT 5 of Range Maximum to 120 of Potential Transformer secondary voltage below 5 of Range Maximum voltage current ind...

Page 14: ...0 5 of range maximum Current A 0 5 of range maximum 4 for I2 in three wire mode Neutral current calculated A 4 of range maximum Frequency Hz 0 1 Hz Power factor PF 1 of unity Active power W 1 of rang...

Page 15: ...respective owners Environmental Operating temperature 10 C to 55 C Storage temperature 20 C to 70 C Relative humidity 0 to 90 non condensing Shock 30g in 3 planes Vibration 10Hz to 50Hz IEC 60068 2 6...

Page 16: ...r any guarantee that such information is accurate correct reliable or current Tyco Electronics reserves the right to make any adjustments to the information at any time Tyco Electronics expressly disc...

Reviews: