Integra Ci3 digital metering system 

 
1. Features and options 
 

The Integra Ci3 digital meter is designed for accurate measurement and display of all major electrical and power 
quality parameters.  It is has been designed, developed and manufactured in the UK, by Crompton Instruments.  
It is user programmable to suit single-phase two wire, three-phase three-wire, and three-phase four-wire system 
configurations. 
 
The product features a DIN 96 panel mounted snap-fit enclosure, backlit Liquid Crystal Display (LCD) and user 
programmable CT ratios, accessible via an intuitive user interface.  The Integra Ci3 digital meter measures 17 
electrical parameters including total harmonic distortion (THD) up to the 31st harmonic. 
 
The Integra Ci3 digital meter offers two output ports at the rear of the product.  This allows to fit either two 
isolated pulsed output relays or a RS-485 communication module to allow Modbus protocol or Johnson Controls 
communication output.  These are configurable via internal settings. 
 

1.1 Power Supply 

The Integra Ci3 digital meter must be powered from an auxiliary AC or DC supply that is separate (but it may 
also be commoned) from the metered supply.  The input range of the auxiliary is 110-400V AC or 120-350V 
DC.  All connections are made to screw clamp terminals that accept 0.05 - 2.5mm

2

 stranded or solid core 

cables.  Terminal screws are fully tightened for shipment and must be undone before wire insertion.  
Terminal screws should be tightened to 0.5 Nm (4.4 lbf in) only. 

 
1.2 RS485 Module Option 

An optional RS485 module is available for purchase.  Where a RS485 module is available, it can be 
connected to a PC for control and monitoring purposes using either Modbus protocol or Johnson Controls 
protocol.  A maximum of one RS485 module can be fitted to an Integra Ci3 digital meter. 

 
1.3 Pulse Relay Module Option 

An optional Pulsed Relay module is available for purchase.  Pulse relays are user programmable for 
corresponding energy type, pulse divisor (one pulse for every 0.1, 1, 10, 100 or 1000kWh/kVArh for 
example) and pulse width (duration).  A maximum of two Pulsed Relay modules can be fitted to an Integra 
Ci3 digital meter, when no RS485 module is fitted.  When two Pulsed Relay modules are fitted, they share a 
common divisor value and pulse width. 

 
1.4 Display Screen 

The display screen is used in two main modes: display of measured values and parameter setup. 

 
1.5 Front Panel Buttons 

The front of the product has four buttons that select different electrical parameters and are also used for 
system configuration. 
 

is used to select the Voltage and Frequency parameter screens. 
In set-up mode this is the “Back” button. 
 
 
is used to select the Current parameter screens. 
In set-up mode this is the “Up” button. 
 
 
is used to select the Power and Power Factor parameter screens. 
In set-up mode this is the “Down” button. 

Installation instruction

Summary of Contents for Integra Ci3

Page 1: ...120 350V DC All connections are made to screw clamp terminals that accept 0 05 2 5mm2 stranded or solid core cables Terminal screws are fully tightened for shipment and must be undone before wire inse...

Page 2: ...first screen provides a visual check of the LCD screen by lighting up all the LCD segments The second displays the unit s firmware version whilst the third displays a start up self test result If thi...

Page 3: ...old the and the buttons simultaneously for five seconds This displays the password entry screen Password protection is designed to prevent unauthorised access to Set up screens Password is normally se...

Page 4: ...our Reset kWhr kVAhr counters dMd Reset demand counters COMS Communications PROT Protocol Select from Modb Modbus N2 Johnson Controls bAUd Baud rate Select from 2400 4800 9600 19200 38400 PARI Parity...

Page 5: ...button to scroll down the menu until you see the CT primary setting screen Press the button to enter the CT primary setting screen The first digit should start flashing Use the and buttons to set the...

Page 6: ...and power readings are integrated for maximum demand measurement The values displayed are in minutes Use the and buttons to scroll through the following options 60 60 minutes 30 30 minutes 20 20 minut...

Page 7: ...oating Point Byte Order This screen displays the floating point number byte order either Norm Normal or Rev Reverse Note No adjustment of this parameter is allowed via the front of the Integra Ci3 dig...

Page 8: ...n and off alternate halves of the LCD segments to determine if any are stuck either on or off PHAS SEQ This test determines if the Voltage and Current connections to the Ci3 meter are correct If all t...

Page 9: ...when the sliding window does not yet contain a full set of readings i e the elapsed time since the demands were last reset or the elapsed time since the Integra Ci3 digital meter was switched on is le...

Page 10: ...fe may be present at some of the terminals of this unit Installation and servicing should be performed only by qualified properly trained personnel abiding by local regulations Ensure all supplies are...

Page 11: ...quired a panel gasket must be used The terminals at the rear of the product must be protected from liquids or other contamination This unit is intended for indoor use only at an altitude of less than...

Page 12: ...both lines are fused Choose fuses of a type and with a breaking capacity appropriate to the supply and in accordance with local regulations A suitable switch or circuit breaker conforming to the relev...

Page 13: ...w 5 of Range Maximum voltage current indication may only be approximate Voltage Ci3 VT 5 of Range Maximum to 120 of Potential Transformer secondary voltage below 5 of Range Maximum voltage current ind...

Page 14: ...0 5 of range maximum Current A 0 5 of range maximum 4 for I2 in three wire mode Neutral current calculated A 4 of range maximum Frequency Hz 0 1 Hz Power factor PF 1 of unity Active power W 1 of rang...

Page 15: ...respective owners Environmental Operating temperature 10 C to 55 C Storage temperature 20 C to 70 C Relative humidity 0 to 90 non condensing Shock 30g in 3 planes Vibration 10Hz to 50Hz IEC 60068 2 6...

Page 16: ...r any guarantee that such information is accurate correct reliable or current Tyco Electronics reserves the right to make any adjustments to the information at any time Tyco Electronics expressly disc...

Reviews: