background image

PCN 504819-000

Effective Date:  June 29, 2010

PII 54863
Revision AD

9

34.  Position black/red dual layer tubes; shrink in place

Center tubes over the red insulating tubes.  Shrink in place using the 
same method as in Step 31.

Black Red Dual Layer Tube

313

Note:

 

 If External Grounding or Shield Interrupting

Refer to the Raychem HVS-EG, “Guide for External Grounding and 
Shield Interrupting of Power Cable Splices” for modifications to these 
instructions.

33.  Apply red sealant

Remove backing from red sealant.  Using light tension, wrap sealant 
over the cable, butted against the red insulating tube as shown.  
Build the sealant to the level of the red insulating tube.

Red Sealant

Red Sealant

312

35.  Position black reinforcing tubes; shrink in place

Center tubes over the black/red dual layer tubes.  Shrink in place 
using the same method as in Step 31.

Black Reinforcing Tube

314

32.  Position red insulating tubes; shrink in place

Center tubes over the black stress control tubes.  Shrink in place 
using the same method as in Step 31.

Red Insulating Tube

311

Summary of Contents for HVSA-3-1580S Series

Page 1: ...tive contaminants on the product Clean burning torches include the Tyco Electronics FH 2629 FH 2649 uses refillable propane cylinders and FH 2618A uses disposable cylinder Adjusting the Torch Adjust r...

Page 2: ...wire have equivalent cross section to cable metallic shield Additional braid may be needed for LC shield lead sheath cables or if external grounding or shield interrupting is required Raychem HVS EG...

Page 3: ...res Grounding Conductor s P OL Y 4 102mm 178 4 Prepare lead sheath Abrade the lead sheath and clean with oil free solvent as shown PILC Abrade lead oxide and clean 16 406mm Lead Sheath 653 5 Remove le...

Page 4: ...nal Width H PILC 105 9 Position OBT shrink in place Place an Oil Barrier Tube OBT over each phase butted to the lead sheath or belt paper cutback Shrink the three OBTs in place starting at the lead sh...

Page 5: ...203mm HVSA 3 1584S 8 1 2 216mm OBT Insulation I C L PILC 220 14 Clean OBTs Using an approved solvent clean the OBT Insulation as shown OBT Insulation Clean PILC 222 15 Install SRM insert Assemble SRM...

Page 6: ...he finished SRM diameter should not exceed that of the breakout installed in the next step PILC Stretch SRM to 1 2 Original Width 358 20 Position conductive breakout shrink in place Position the condu...

Page 7: ...remaining backing strip tightly wrap the SRM around the connector and exposed conductor Be sure to fill the gaps and low spots around the connector Continue to wrap the SRM onto the insulation as sho...

Page 8: ...tive tube Repeat Steps 25 30 for the remaining two phases Black Stress Control Tube 309 29 Apply Discharge Control Compound DCC Snip open the end of the DCC ampule and apply a thin film of compound ov...

Page 9: ...ons to these instructions 33 Apply red sealant Remove backing from red sealant Using light tension wrap sealant over the cable butted against the red insulating tube as shown Build the sealant to the...

Page 10: ...spring clamp over the braid 3 Fold the braid back over the spring clamp wraps Continue to wrap the remaining clamp over the braid Tighten clamp by twisting it in the direction it is wrapped and secur...

Page 11: ...area and center on the exposed cable armor and lead sheath Bind the ends of the armorwrap to the cable armor and lead sheath with the tape provided Abrade and solvent clean cable jackets as shown to p...

Page 12: ...eating Note Green heat sensitive paint will turn black as sleeve shrinks in place This completes the splice Note Allow to cool before moving or placing in service Adhesive Flow both ends White indicat...

Reviews: