496349 Issue 1
5 of 10
Figure 3. Wiring 1081 and 1082.
3.
Use terminal 6 (Spare) as a connection point for EOL devices.
4.
Connect terminal 7, (Remote LED Control) to the appropriate switch or
alarm panel walk test output (if required).
5.
Connect terminal 4 to the positive supply.
6.
Connect terminal 5 to the 0V supply.
7.
Connect terminals 1, 2 and 3 (Alarm Relay) and terminals 9 and 10
(Tamper), to the control panel or warning device.
8.
After all connections are complete, seal wire entry openings and apply
power to the detector.
PIR Lens Adjustment
This adjustment can only be carried out with the detector cover removed.
Particular attention should be paid to the lens adjustment procedure for 1082
detectors due to the long range of the detector.
1.
Squeeze the lens carrier handles and remove the lens carrier from the
pcb assembly.
2.
Remove the trbl (Trouble) link and fit it across the Zone pins (see Figure
4). The red Zone Locator LED will remain on to allow adjustment of the
lens to the desired protection pattern.
1081/1082
PIR Lens Adjustment