607.32.09.00
Last updated 2022/03/22
- 4 -
GB
Type
A
B
C
D
[mm]
[mm]
[mm]
Connectio
n
DN 25
209
40
45
T 1
DN 32
209
45
50
T1¼
DN 40
300
85
83
T1½
DN 50
285
71
69
T 2
Assembly
Function
All above-ground tanks require the installation
of an anti-syphon protection valve
with relief
for safety reasons.
Installation is carried out at the highest point
of the tank, preferably on the dome cover.
The angle check valve is set at the factory to
the lowest anti-syphon protection value (1.5
m).
The value to be set on site results from the
following difference:
Height of the max. liquid level in the tank -
Height of the lowest point of the suction line.
After unscrewing the upper hood [2], the
adjustment screw [3] for regulating the spring
force becomes visible. To adjust the anti-
syphon protection, loosen the grub screw [5]
screwed into the side.
Turning the adjusting screw on the square
clockwise increases the spring tension and
thus the height of the anti-syphon protection.
The adjustment is made as shown in the
diagram. For simplification, markings for 1.5 m
- 2.0 m - 2.5 m - 3.0 m anti-syphon protection
are attached to the spindle.
After adjustment, the grub screw must be
tightened again and the protective hood fitted.
in
out
Summary of Contents for tubra DN 25
Page 1: ...D tubra Eckr ckschlagventil DN 25 DN 50 Montage und Bedienungsanleitung...
Page 8: ...GB tubra angle check valve DN 25 DN 50 Assembly and operating instructions...
Page 15: ...I Valvola di non ritorno angolare tubra DN 25 DN 50 Istruzioni di assemblaggio e d uso...
Page 22: ...FR Clapet anti retour en querre tubra DN 25 DN 50 Instructions de montage et de service...