Type 

 

[mm] 

[mm] 

[mm] 

Connectio

DN 25 

209 

40 

45 

T 1 

 

 

 

 

 

DN 32 

209 

45 

50 

T1¼ 

 

 

 

 

 

DN 40 

300 

85 

83 

T1½ 

 

 

 

 

 

DN 50 

285 

71 

69 

T 2 

 

Assembly 

Function 

 

 

 
All above-ground tanks require the installation 
of an anti-syphon protection valve 

with relief

 

for safety reasons. 
Installation is carried out at the highest point 
of the tank, preferably on the dome cover. 
 
The angle check valve is set at the factory to 
the lowest anti-syphon protection value (1.5 
m). 
The value to be set on site results from the 
following difference: 
Height of the max. liquid level in the tank - 
Height of the lowest point of the suction line. 
 
After unscrewing the upper hood [2], the 
adjustment screw [3] for regulating the spring 
force becomes visible. To adjust the anti-
syphon protection, loosen the grub screw [5] 
screwed into the side. 
Turning the adjusting screw on the square 
clockwise increases the spring tension and 
thus the height of the anti-syphon protection. 
The adjustment is made as shown in the 
diagram. For simplification, markings for 1.5 m 
- 2.0 m - 2.5 m - 3.0 m anti-syphon protection 
are attached to the spindle. 
 
After adjustment, the grub screw must be 
tightened again and the protective hood fitted. 
 

 
 
 
 

 

in 

out 

Summary of Contents for tubra DN 25

Page 1: ...D tubra Eckr ckschlagventil DN 25 DN 50 Montage und Bedienungsanleitung...

Page 2: ...ich gemacht werden 2 UrhG 823 BGB Verwendungszweck Das Heberschutzventil tubra Eckr ckschlagventil dient ausschlie lich zur Absicherung gegen Leerhebern von oberirdischen Beh ltern Die Sicherheitseinh...

Page 3: ...e DN 25 DN 32 DN 40 DN 50 Heberschutz 1 5 3 m unter Anlagendruck einstellbar ffnungsdruck Entlastungsventil 2 bar Max Betriebsdruck 10 bar Max Betriebstemperatur 95 C Anschl sse Eingang G1 IG G1 IG G...

Page 4: ...ibt sich aus folgender Differenz H he des max Fl ssigkeitsstands im Tank H he des niedrigsten Punktes der Saugleitung Nach Abschrauben der oberen Haube 2 wird die Einstellschraube 3 zur Regulierung de...

Page 5: ...l DN 25 und DN 32 Heberschutzh he m H henverstellung H mm Einstellung DN 40 DN 50 Werkseinstellung H 74 mm Beispiel notwendige Heberschutzh he 2 10 m H henverstellung H einstellen auf 49 mm Einstellun...

Page 6: ...bra Eckr ckschlagventil best tigt Installierte Armatur tubra Eckr ckschlagventil DN 25 DN 32 DN 40 DN 50 Einstellungen Heberschutzh he ______ m H henverstellung H ______ mm Betreiber Name und Anschrif...

Page 7: ...H ndler Gebr Tuxhorn GmbH Co KG Senner Stra e 171 33659 Bielefeld Tel 49 0 521 44 808 0 Fax 49 0 521 44 808 44 www tuxhorn de...

Page 8: ...GB tubra angle check valve DN 25 DN 50 Assembly and operating instructions...

Page 9: ...t Act section 823 Civil Code Intended purpose The tubra anti syphon protection valve tubra angle check valve is exclusively designed for protecting against syphon effects in above ground storage tanks...

Page 10: ...DN 32 DN 40 DN 50 Anti siphoning valves 1 5 3 m adjustable under system pressure Opening pressure relief valve 2 bar Max operating pressure 10 bar Max operating temperature 95 C Connections Inlet T1 I...

Page 11: ...results from the following difference Height of the max liquid level in the tank Height of the lowest point of the suction line After unscrewing the upper hood 2 the adjustment screw 3 for regulating...

Page 12: ...ht 2 m adjust height adjustment H to 34 5 mm Setting DN 40 DN 50 Factory setting H 74 mm Required anti siphon protection height 2 10 m adjust height adjustment H to 49 mm Maintenance service The angle...

Page 13: ...eck valve is hereby confirmed Installed fitting tubra angle check valve DN 25 DN 32 DN 40 DN 50 Settings Anti syphon protection height ______ m Height adjustment H ______ mm Operator name and address...

Page 14: ...Reseller Gebr Tuxhorn GmbH Co KG Senner Stra e 171 33659 Bielefeld Tel 49 0 521 44 808 0 Fax 49 0 521 44 808 44 www tuxhorn de...

Page 15: ...I Valvola di non ritorno angolare tubra DN 25 DN 50 Istruzioni di assemblaggio e d uso...

Page 16: ...d uso 2 della legge sulla tutela dei diritti d autore federale abbreviata UrhG 823 del codice civile federale abbreviato BGB Scopo d utilizzo La valvola di protezione da sifonamento la valvola di non...

Page 17: ...2 DN 40 DN 50 Protezione da sifonamento impostabile 1 5 3 m sotto la pressione dell impianto Pressione di apertura valvola limitatrice 2 bar Max pressione di esercizio 10 bar Max temperatura di eserci...

Page 18: ...si ha dalla seguente differenza Altezza massima del liquido nel serbatoio Altezza del punto pi in basso del condotto di aspirazione Dopo aver svitato la calotta superiore 2 si vede la vite di regolaz...

Page 19: ...la regolazione l altezza Alt H Impostazione DN 40 DN 50 Impostazione di fabbrica Alt H 74 mm Esempio altezza necessaria protezione sifonamento 2 10 m impostare regolazione altezza Alt H su 49 mm Manu...

Page 20: ...valvola di non ritorno angolare tubra Raccordi installati Valvola di non ritorno angolare tubra DN 25 DN 32 DN 40 DN 50 Impostazioni Altezza protezione da sifonamento ______ m Regolazione altezza Alt...

Page 21: ...Rivenditore Gebr Tuxhorn GmbH Co KG Senner Stra e 171 33659 Bielefeld Tel 49 0 521 44 808 0 Fax 49 0 521 44 808 44 www tuxhorn de...

Page 22: ...FR Clapet anti retour en querre tubra DN 25 DN 50 Instructions de montage et de service...

Page 23: ...tilisation pr vue La vanne de protection de v rin Clapet anti retour en querre tubra est exclusivement destin e la protection contre le levage vide de r servoirs en dehors du sol L unit de s curit de...

Page 24: ...2 DN 40 DN 50 Protection du v rin 1 5 3 m r glables sous la pression de l installation Pression d ouverture soupape de d charge 2 bar Pression de service maxi 10 bar Temp rature de service maxi 95 C R...

Page 25: ...site ressort de la diff rence suivante Hauteur du niveau de liquide max dans le r servoir hauteur du point le plus bas de la conduite d aspiration Apr s avoir d viss le carter sup rieur 2 la vis de r...

Page 26: ...en hauteur H sur 34 5 mm R glage DN 40 DN 50 R glage en usine H 74 mm Exemple hauteur n cessaire de protection du v rin 2 10 m r gler le r glage en hauteur H sur 49 mm Entretien service Le clapet ant...

Page 27: ...ur tubra sont ainsi confirm s Armature install e Clapet anti retour en querre tubra DN 25 DN 32 DN 40 DN 50 R glages Hauteur de protection du v rin ______ m R glage en hauteur H ______ mm Exploitant n...

Page 28: ...Revendeur Gebr Tuxhorn GmbH Co KG Senner Stra e 171 33659 Bielefeld Tel 49 0 521 44 808 0 Fax 49 0 521 44 808 44 www tuxhorn de...

Reviews: