Safety Information
Pad Locking
Your Fill-Rite pump nozzle can be pad locked for added
security. With the pump turned off, and the nozzle in the stored
position, a pad lock can be inserted through the locking link and
the nozzle handle opening. This configuration prevents the
nozzle from being removed and the pump being turned on
.
Installation
FR902 Series Remote dispensers and tank top pumps must be installed in accordance with
local, state, and national electrical code NEC/ANSI/NFPA 70, NFPA 30, NFPA 30A, and
NFPA 395, on a fixed, above ground tank not accessible to the public.
In
FR902RU
and
FR902LRU
installations, a UL listed emergency shut-off valve with fusible
link must be installed at the dispenser inlet. All piping must be Schedule 40. Use UL
classified gasoline and oil resistant pipe compound on all threaded joints. See page 12 for
sample plumbing diagram. For use ONLY with UL Listed Interchangeable (automatic or
manual) Service Station Type Hose Nozzle Valves or Non-Interchangeable Service Station
Type Nozzle Valves Model Catlow MAX 1, Husky 3N1-GS, and Husky 1+V111.
Additionally,
FR902RU
and
FR902LRU
Dispensers require a UL listed pressure relief valve
be incorporated into the installation, either as part of the pump or separately at the dispenser
itself.
WARNING!
This product must not be used to transfer fluids into any type of
aircraft.
WARNING!
This product is not suited for use with fluids intended for human
consumption or fluids containing water.
WARNING!
To ensure safe and proper operation of your equipment, it is critical
to read and adhere to all of the following safety warnings and precautions.
Improper installation or use of this product can cause serious bodily injury or
death!
1)
NEVER
smoke near the dispenser, or use the dispenser near open flames
when dispensing a flammable liquid! Fire can result!
2)
A “Fill-Rite” Filter should be used on the dispenser outlet to insure no foreign
material is transferred to the fuel tank.
3)
Threaded pipe joints and connections should be sealed with the appropriate
sealant or sealant tape to minimize the possibility of leaks.
4)
Storage tanks should be securely anchored to prevent shifting or tipping
when full or empty.
5)
To minimize static electricity build up, use only static wire conductive hose
when dispensing flammable fluids, and keep the fill nozzle in contact with the
container being filled during the filling process.
6)
DO NOT
exceed 50 psi/ 3.5 BARS line pressure.
7)
DO NOT
install a foot valve or check valve without a pressure relief valve;
cracking may result.