turck TBIP-L-FDIO1-2IOL Series Safety Manual Download Page 16

16 

Appendix: Switching examples

Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com

Appendix: Switching examples

9.1 

Inputs

Safe equivalent input for potential free contacts (NC/NC) 

2 FDI (T2)

1 T1

3 n.c.
4 FDI (T1)

5 T2

TBPN-L1…

2 FDI (T2)

1 T1

3 n.c.
4 FDI (T1)

5 T2

TBPN-L1…

Safe antivalent input for potential free contacts (NC/NO)

2 FDI (T2)

1 T1

3 n.c.
4 FDI (T1)

5 T2

TBPN-L1…

Safe electronic input (OSSD)

2 FDI (T2)

1 VAUX1

3 GND
4 FDI (T1)

5 n.c.

OSSD

+

TBPN-L1…

9.2 

Outputs

Safe output PP-switching

2 n.c.

1 n.c.

3 GND (V1)
4 FDO +

5 n.c.

TBPN-L1…

For PP-switching outputs, connect the negative 
pole of the load to the GND-connector of the re-
spective output (pin 3). Another connection to the 
GND of the power supply unit is not permitted!
The wiring has to allow an exclusion of faults 
regarding cross connection.

Safe output PM-switching

2 FDO –

1 n.c.

3 n.c.
4 FDO +

5 n.c.

TBPN-L1…

For PM-switching outputs, connect the negative 
pole of the load to the M-connector of the respec-
tive output (pin 2).

Summary of Contents for TBIP-L-FDIO1-2IOL Series

Page 1: ...Your Global Automation Partner TBIP L FDIO1 2IOL Safety Block I O Module Safety manual Translation...

Page 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...

Page 3: ...ites 8 6 2 Reaction Time 8 6 3 Safety Characteristic Data 9 7 Operating Instructions 9 7 1 General 9 7 2 Before Operation 10 7 2 1 Mounting 10 7 2 2 Connecting 11 7 2 3 Address Assignment 12 7 2 4 Con...

Page 4: ...4952 0 F 49 208 4952 264 more turck com www turck com 10 Appendix Designations and Abbreviations 17 11 Appendix Function Tests 17 12 Appendix Document History 17 13 Appendix Technical data 18 14 Appen...

Page 5: ...his is the latest version of the safety manual at www turck com The German version is considered the definitive document Every care was taken in the produc tion of the translations of this document If...

Page 6: ...IO Link slots each provide one digital in output at pin 2 The non safety ports C4 C5 and C7 can be switched off safe via the internal outputs FSO0 and FSO1 see 4 5 Block Diagram on p 7 This allows a s...

Page 7: ...3 safety related input C2 FDX4 5 safety related in output C3 FDX6 7 safety related in output C4 DXP8 9 standard in outputs safe shutdown via FSO0 possible C5 DXP10 11 standard in outputs safe shutdow...

Page 8: ...LOW state 0 to the logic 5 2 Fatal Error The following errors lead to Fatal Error and thus to the safe state Incorrect wiring at the output e g capacitive load energetic recovery Incorrect power suppl...

Page 9: ...gister the devices under www turck de SIL Only trained and qualified personnel must mount install operate and maintain the devices The devices are not specified for a certain application Make sure tha...

Page 10: ...ingle safety component Carry out a validation of the safety category for the complete system depending on the selec tion of the used safety components 7 2 1 Mounting ATTENTION Mounting on uneven surfa...

Page 11: ...y units with PELV according to EN50179 EN50178 PELV Assure that the maximum output voltage not exceeds 60 V even in case of an error Connect the device to the power supply according to the pin assignm...

Page 12: ...P address accept the setting with a device restart 300 BootP 400 DHCP 500 PGM 600 PGM DHCP 900 Factory Reset reset of the device to factory settings 901 Stick Reset Deletes the content of the memory c...

Page 13: ...lt the device has an unrecoverable fault may need replacing red blinking Recoverable Fault green red blinking During start up device is in self test During operation device needs commissioning due to...

Page 14: ...Channel active and overload at supply input only 12 15 green IO Link communication or DI active red Error 0 7 red all blinking alternating Fatal Error WINK white flashing Helps to localize the module...

Page 15: ...tive pole of the load to the M connector of the respective output pin 2 see 9 Appendix Switching examples on p 16 8 5 DXP 8 6 IO Link 1 BK GND V2 2 BU GND V1 3 GNYE FE 4 BN 24 VDC V1 5 WH 24 VDC V2 3...

Page 16: ...Safe electronic input OSSD 2 FDI T2 1 VAUX1 3 GND 4 FDI T1 5 n c OSSD TBPN L1 9 2 Outputs Safe output PP switching 2 n c 1 n c 3 GND V1 4 FDO 5 n c TBPN L1 For PP switching outputs connect the negativ...

Page 17: ...the function test is only carried out by qualified personnel A suggested function test consists of the following steps Step Action 1 Switch every safety related input at least once a year 2 Control th...

Page 18: ...3 Safety Characteristic Data on p 9 Safety inputs for potential free contacts Loop resistance 150 Max cable length max 1 F at 150 limited by line capacity Test pulse typ 0 6 ms Test pulse max 0 8 ms I...

Page 19: ...00 m per segment Sensor actuator 30 m Operating storage temperature 40 C to 70 C 40 to 158 F Protection class IP65 IP67 IP69K Housing material Fibre glass reinforced Polyamide PA6 GF30 Window material...

Page 20: ...20 Appendix Declaration of Conformity Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 14 Appendix Declaration of Conformity...

Page 21: ...28 subsidiaries and over 60 representations worldwide www turck com 100000664 2017 10 100000664...

Reviews: