7.3
Operating
7.3.1
Indication Elements
During operation, the LEDs have the following functions:
LED
Color
Meaning
ETH1
green
Link established, 100 Mbps
green blinking
Ethernet Traffic, 100 Mbps
yellow
Link established, 10 Mbps
yellow blinking
Ethernet Traffic, 10 Mbps
ETH2
green
Link established, 100 Mbps
green blinking
Ethernet Traffic, 100 Mbps
yellow
Link established, 10 Mbps
yellow blinking
Ethernet Traffic, 10 Mbps
PWR
green
Voltage OK
red
Power supply faulty
MS
off
The device may not be powered
green
No diagnostic message, device is operating in normal condition
green blinking
The Device is in the Idle or Standby State.
red
Critical fault, the device has an unrecoverable fault, may need replacing.
red blinking
Recoverable Fault
green/red blinking During start-up: device is in self test
During operation: device needs commissioning due to configuration or Unique
Node Identifier missing, incomplete or incorrect.
NS
off
Device is not on-line.
The device may not be powered.
green
Active connection to a master
green blinking
Device is on-line but has no connections in the established state.
A connection may be established, but not completed.
red
Failed communication of device.
red blinking
One or more I/O Connections are in the Timed–Out state.
green/red blinking During start-up: device is in self test
During operation: Device detected a Network Access error and is in the
Communication Faulted state.
0…3
green
Channel active
green blinking
Self-testing
red
Discrepancy
red blinking
Cross Connection