V 01.01 | 2018/11
33
13.3
TBIL-S…-8DXP
Technical Data
Power supply
Operating/load voltage
18…30 VDC
Operating current
< 90 mA
Sensor/actuator supply V
AUX
Supply connectors C0…C7 or C…C3
0.5 A per channel group, short-circuit protec-
ted with diagnostics
channel groups:
n
TBIL-S3-8DIP: C0…C3, C4…C7
n
TBIL-S4-8DIP: C0…C1, C2…C3
Total current
max. 4 A per module
Inputs
Number of channels
8 digital pnp inputs (EN 61131-2)
Input voltage
18…30 VDC e.g. from supply voltage
Signal voltage, low level
-3…5 VDC (EN 61131-2, type 1 and 3)
Signal voltage, high level
11…30 VDC (EN 61131-2, type 1 and 3)
Input delay
0.010 ms
Max. input current
15 mA
Potential isolation
Inputs to FE, 500 VDC
Outputs
Number of channels
8 digital pnp outputs
Type of output diagnostics
Channel diagnostics
Output voltage
24 VDC from supply voltage
Output current per channel
0.5 A, short-circuit-proof
Output delay
0.15 ms
Load type
Ohmic, inductive lamp load
Potential isolation
Outputs to FE, 500 VDC
IO-Link
Minimum cycle time
2.8 ms