V 01.01 | 2018/11
15
ISDU
Index
Hex.
(Dec.)
Object name
Access
Length
[Byte]
Meaning/
default value
Comment
0x1A
(26)
Location Tag
read/
write
32
Default "***"
The application-spe-
cific installation loca-
tion of the device can
be stored in this field.
IO-Link object directory – ISDU device parameters: Preferred Index (parameters and
diagnostics of the digital in- and outputs)
ISDU
Index
Hex.
(dec.)
Object name
Access
Length
[Byte]
Meaning
0x40
(64)
Parameter ID
read/
write
4
Customer-specific ID, for free use
0x41
(65)
Inverting
Input
read/
write
1
Invert digital input
0x42
(66)
Activate
Output
read/
write
1
Activate output
only for TBIL-S…-8DXP
0x43
(67)
Impulse
Stretching
Input
read/
write
8
Pulse stretching input
0x44
(68)
Short Circuit
Recovery
read/
write
1
Manual output reset after overcurrent
only for TBIL-S…-8DXP
0x45
(69)
Failsafe
read/
write
2
Output After Error
only for TBIL-S…-8DXP
0x46
(70)
Under
Voltage
Diagnostics
read/
write
2
Undervoltage Diagnosis (defining the
threshold value for the undervoltag dia-
gnostics)
Diagnostics
0x50
(80)
Supply Error
read
only
2
n
Over- and undervoltage supply
n
Overcurrent V
AUX
connector C0…C7 or
C0…C3
0x51
(81)
Output Short
Circuit
read
only
1
Overcurrent output 0…7
only for TBIL-S…-8DXP