8
2 Getting Started
2.1 About this document
The TBEN-LH EtherNet/IP
configuration guide provides information about configuration of the TBEN-LH-
16DIP including:
Address switches
IP address assignment
Configuration options with Rockwell and Omron PLCs
CIP Vendor specific objects
NOTE
The device data sheet and technical information is available for download at
www.turck.us.
2.2 Factory default IP address
The TBEN-LH-16DIP device is shipped with address switches set to 600 (PGM-DHCP). It is factory
default position of the rotary switches which is associated with the IP address:
IP Address: 192.168.0.254
Subnet mask: 255.255.252.0
Gateway: 0.0.0.0
The device has limited functionality in this state:
DHCP client is active and running; use any service to assign IP address
Web server is active
Some other services are active
Device cannot be configured with a PLC
The device responds to the PING command as follows:
Figure 2.1 - Ping
The first step in the device configuration is to assign an operational IP address.
The device DHCP client is running and waiting for an IP address assignment. When IP address is
acquired, the DHCP becomes disabled.