25
4.2 TBEN-LH-16DIP configuration using generic device profile
4.2.1 Generic device and default configuration connection
The procedure:
In the
Controller Organizer
, right-click on
Ethernet
to display a drop-down menu.
Click
New Module
to open the
“Select Module Type”
configuration page
Enter
“Generic”
in the search area, highlight the
Generic Ethernet Module
and click
Create
Figure 4.11
– Generic module selection page
Enter the
Name
,
Description
and
IP Address
of the device in the
New Module
page
Select the
Input Data
– INT
data format in the
Comm Format
field
Enter the
Connection Parameters
as seen in the following figure
Click OK and download configuration to the PLC
Figure 4.12 - TBEN generic module configuration