background image

 
 

 

TBEN-LH-16DIP 

EtherNet/IP

TM

 Configuration 

Guide 

 
 
0119A 

Summary of Contents for TBEN-LH-16DIP

Page 1: ...TBEN LH 16DIP EtherNet IPTM Configuration Guide 0119A...

Page 2: ...2 This page intentionally left blank...

Page 3: ...verview 17 3 1 Dimensions and connector assignment 17 3 2 Power connector pin assignment 17 3 3 IO connector pin assignment 17 3 4 LEDs 18 3 5 Grounding 18 3 6 IO data map 19 4 Configure TBEN LH 16DIP...

Page 4: ...0x06 Connection Manager Object 39 7 3 1 Common Services 39 7 3 2 Limitations 39 7 4 Class Code 71 0x47 Device Level Ring Object 40 7 4 1 Class Attributes 40 7 4 2 Instance Attributes 40 7 4 3 Common S...

Page 5: ...5 7 11 1 Instance 1 and 2 Attributes 47 7 11 2 Common Services 47...

Page 6: ...ign and a signal word that expresses the gravity of the danger The warnings have absolutely to be observed DANGER DANGER indicates an immediately dangerous situation with high risk the death or severe...

Page 7: ...EtherNet IP communication adapter v1 01 Network Configurator 3 21 1 4 Feedback about these instructions We make every effort to ensure that these instructions are as informative and as clear as possi...

Page 8: ...o 600 PGM DHCP It is factory default position of the rotary switches which is associated with the IP address IP Address 192 168 0 254 Subnet mask 255 255 252 0 Gateway 0 0 0 0 The device has limited f...

Page 9: ...requesting an IP address 400 DHCP DHCP client is active and requesting an IP address 500 PGM Device comes up with the last IP address saved in EEPROM IP address is programmable 600 PGM DHCP DHCP clien...

Page 10: ...is acquired the device disables its DHCP The device saves permanently assigned IP address and transitions to the PGM mode 2 3 5 Factory Reset mode 900 The factory reset mode resets the device back to...

Page 11: ...and IBTP TURCK Service Protocol With the IBTP protocol extended information such as FW version and operating mode improved scanning are read out of TURCK devices and displayed Setting an IP address F...

Page 12: ...P address transitions to 0 0 0 0 when DCHP server is started The device mode is provided position of the rotary switches composite firmware revision ARGEE loaded program is running and BEEP status of...

Page 13: ...ntil DHCP server locates the device IP transitions to 0 0 0 0 Figure 2 7 Device DHCP client active view Highlight device Click Change F2 Assign IP address Click Stop DHCP F6 button Figure 2 8 IP Confi...

Page 14: ...of the device into a browser If you don t know what is current IP address use TURCK Service Tool to discover device Enter password into Login field to get administrator s privilege Figure 2 9 Device W...

Page 15: ...e IP address is assigned the device DHCP client becomes disabled The procedure Start Rockwell DHCP server Select network interface Figure 2 11 BOOTP DHCP tool At Tools menu click at Network Settings F...

Page 16: ...16 Enter new IP address in the New Entry dialog Figure 2 14 IP address setup Wait for confirmation assigned IP address appears in the IP Address column Figure 2 15 IP address assignment complete...

Page 17: ...ssignment power distribution and grounding requirements are as follows 3 1 Dimensions and connector assignment Figure 3 1 Connector assignment 3 2 Power connector pin assignment Figure 3 2 X1 and X2 c...

Page 18: ...status 3 5 Grounding The device is entirely powered of the V1 Power v2 is feed through Remove the grounding clip between connectors P1 and P2 when shielded Ethernet cables are used Ground the network...

Page 19: ...input channel x x 0 1 15 CxP2 Connector x Pin2 x 0 1 7 CxP4 Connector x Pin4 x 0 1 7 Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Word 0 SCS7...

Page 20: ...The EDS file is the Electronic Data Sheet or the device configuration file described in the CIP Library Volume 1 Common Industrial Protocol CIP Edition 3 22 by ODVA The procedure Download TBEN LH 16D...

Page 21: ...on the Ethernet to access a drop down menu Click New Module to open the Select Module Type dialog page Figure 4 3 Add new module Enter the device name in the search area of the Select Module Type dia...

Page 22: ...drop down menu Click Apply and follow the dialog to complete the device configuration Figure 4 5 New Module setup dialog page The AB TBEN LH 16DIP connection selected during the device configuration p...

Page 23: ...ce Module Properties page Fill in the Name Description and Ethernet Address of the device Click Change to open the Module Definition page Use TBEN LH 16DIP_QC_ON connection from the drop down list and...

Page 24: ...n parameters The procedure Open the device Module Properties page Fill in the Name Description and Ethernet Address of the device Click Change to open the Module Definition page Use TBEN LH 16DIP_QC_O...

Page 25: ...le Type configuration page Enter Generic in the search area highlight the Generic Ethernet Module and click Create Figure 4 11 Generic module selection page Enter the Name Description and IP Address o...

Page 26: ...ghlight the Generic Ethernet Module and click Create Enter the Name Description and IP Address in the New Module page Select the Input Data INT data format in the Comm Format field Enter the Connectio...

Page 27: ...a highlight the Generic Ethernet Module and click Create Enter the Name Description and IP Address in the New Module page Select the Input Data INT data format in the Comm Format field Enter the Conne...

Page 28: ...ETH2 port set as MDIX cross over wiring Auto Negotiate and Auto MDX are disabled The TBEN LH 16DIP QuickConnect operational time Ready for connection time 100msec time measured from the device power...

Page 29: ...e Install TBEN LH 16DIP_R2 7_complex EDS file in the Omron Network Configurator using EDS File Install drop down menu Follow the dialog to complete registration Figure 5 1 Network configuration EDS fi...

Page 30: ...eate a Tag Set At the Edit Connection page Select Omron TBEN LH 16DIP in the Connection I O Type field Select Input Tag Set field and Connection Type in the Originator Device dialog box Register devic...

Page 31: ...31 5 1 3 Download configuration At the Network drop down menu select Connect Figure 5 5 Network Configurator on line Download configuration Figure 5 6 Network Configurator download...

Page 32: ...32 5 1 4 TBEN LH 16DIP parameters The device parameters provided by the EDS file allow for on line parameter setup download and upload Figure 5 7 Network Configurator edits...

Page 33: ...ge Select Omron TBEN LH 16DIP_QC_ON in the Connection I O Type field Select Input Tag Set and Connection Type field set as Point to point in the Originator Device Register device and verify setup with...

Page 34: ...Omron TBEN LH 16DIP_QC_OFF in the Connection I O Type field Select Input Tag Set field and Connection Type field of the Originator Device Register device and verify setup with web server Figure 5 10 T...

Page 35: ...controller confirms reception of the input data from the target device and maintains the connection open by production of the Heartbeat to the target device There is no output data Input Only connecti...

Page 36: ...Identity Object is required on all devices and provides general information about the device 7 1 1 Instance Attributes Attribute Access Name Type Value 1 Get Vendor UNIT 48 2 Get Product Type UNIT 12...

Page 37: ...do something different than the out of box default This shall not include configuration of the communications 3 Reserved shall be 0 4 7 Extended Device Status As defined by table below The EDS shall...

Page 38: ...ration assembly instance data size 14 short integers Instance 113 Output Heartbeat assembly size 0 enables QuickConnect Instance 114 Output Heartbeat assembly size 0 disables QuickConnect Instance 254...

Page 39: ...tance generated by the Connection Manager is referred to as a Connection Instance or a Connection Object 7 3 1 Common Services Service Code Class Instance Service Name Service Description 84 0x54 No Y...

Page 40: ...Loop Detected 3 indicates Partial Network Fault 4 indicates Rapid Fault Restore Cycle See section 5 6 3 4 Refer to Note 10 Get Active Supervisor Address Array of IP and or MAC address of the active r...

Page 41: ...sport class 0 1 Schedule priority messages 6 Set NV DSCP High USINT DSCP value for CIP transport class 0 1 High priority messages 7 Set NV DSCP Low USINT DSCP value for CIP transport class 0 1 Low pri...

Page 42: ...ue of 0 indicates no network mask address has been configured Gateway Address UDINT Default gateway address Value of 0 indicates no IP address has been configured Otherwise the IP address shall be set...

Page 43: ...onnect BOOL 0 Disable 1 Enable NOTE The symbol is an abbreviation for default setup 7 6 2 Common Services Service Code Class Instance Service Name 14 0x0E Yes Yes Get_Attribute_Single 16 0x10 No Yes S...

Page 44: ...3 Get Number of Instances 3 7 7 2 Instance Attributes Attribute Access Name Type Note 1 Get Interface Speed UDINT 1 Speed in megabits per second e g 10 100 1000 etc 2 Get Interface Flags DWORD 2 3 Get...

Page 45: ...cern the TBEN system and the gateway Attribute Access Name Type Description 109 6Dh Get STATUS REGISTER2 STRUCT Gateway Status Contains a general gateway station status Bit 15 10 reserved Bit 09 UB un...

Page 46: ...er of output channels supported by the module 113 71h Input data MODULE INPUT_1 DWORD Input data of the module according to channels 115 73h Get MODULE OUTPUT_1 DWORD Output data of the module accordi...

Page 47: ...class parameters but all in one object This object has 2 instances The following values are allowed per instance 0 Autonegotiate AutoMDIX 1 10BaseT Half Duplex Linear topology AutoMDIX diabled 2 10Bas...

Page 48: ...are located nationwide Including all major metropolitan marketing areas For Application Assistance or for the location of your nearest TURCK distributor call 1 800 544 7769 Specifications in this manu...

Reviews: