Acyclic data exchange via PROFIBUS-DP C2-master and TURCK IO-Link DTM
D301171 - IO-Link master 1108
5-2
Communication via DTM with C2-master
To be able to access the IO-Link master and the connected TURCK IO-Link sensors via
TURCK IO-Link DTM, the usage of a PROFIBUS-DP master Class 2 (C2-master) is necessary.
The example described in the following shows, besides configuration, parameterization and
diagnosis via DTM, also the measurement value representation for the IO-Link master or
respectively for the connected TURCK-sensors.
Used hardware
TURCK-PB-XEPI (Ethernet/ PROFIBUS - interface), EtherNet/IP-address 192.168.1.23
TURCK-IO-Link master SDPXIOL4-0001, DP-address 40
–
IO-Link port 1 (slot 2): TURCK pressure sensor, PS100R-501-LI2UPN8X-H1141
–
IO-Link port 2 (slot 3): not used
–
IO-Link port 3 (slot 4): Siemens ultra sonic sensor, PXS310C M18 IO-Link (6GR6333-
3KS00)
–
IO-Link port 4 (slot 5): not used
Used software
PACTware™, version 3.6
DTM for the PB-XEPI: CommDTM_PROFIBUS_DPV1 from Trebing & Himstedt,
version 3.0.0.8
TURCK-DTM for the IO-Link master SDPX-IOL4-0001
TURCK-DTM for the TURCK-sensor PS100R-501-LI2UPN8X-H1141
The software PACTware™, the DTMs as well as the documentation for the devices can be
downloaded free of charge from www.turck.com.
Hardware-configuration C2-master
The PB-XEPI is connected to the PC via EtherNet/IP.
Default IP-address: 169.254.0.1
Subnet: 255.255.0.0
The connection to PROFIBUS is done via a SUB-female connector.