D301171 - IO-Link master 1108
3-9
Process image
3
Process image
The module SDPX-IOL4-0001 sends 2 byte process input data. It has no process output data.
Process input data
Byte
Bit
Name
Default
Description
0
0
DI channel 0 (port 1)
0
status PIN 4 of port 1, if in SIO-mode
1
DI channel 1 (port 1)
0
status PIN 2 of port 1
2
DI channel 2 (port 2)
0
status PIN 4 of port 2, if in SIO-mode
3
DI channel 3 (port 2)
0
status PIN 2 of port 2
4
DI channel 4 (port 3)
0
status PIN 4 of port 3, if in SIO-mode
5
DI channel 5 (port 3)
0
status PIN 2 of port 3
6
DI channel 6 (port 4)
0
status PIN 4 of port 4, if in SIO-mode
7
DI channel 7 (port 4)
0
status PIN 2 of port 4
1
0
PD valid channel 0 (port 1)
0
process data (PD) valid at "1"
1
PD valid channel 1 (port 1)
0
process data (PD) valid at "1"
2
PD valid channel 2 (port 2)
0
process data (PD) valid at "1"
3
PD valid channel 3 (port 2)
0
process data (PD) valid at "1"
4
PD valid channel 4 (port 3)
0
process data (PD) valid at "1"
5
PD valid channel 5 (port 3)
0
process data (PD) valid at "1"
6
PD valid channel 6 (port 4)
0
process data (PD) valid at "1"
7
PD valid channel 7 (port 4)
0
process data (PD) valid at "1"