35
TURCK
RM-89
RSLogix 500 Sample
Figure 5 .2 shows the configuration screen when setting up a message instruction to communicate with a RM-89 on a
DeviceNet network . Note that the screen will change as you enter data .
1) Communications Channel: Data path out of the controller . First, set the channel to “Expansion Comms Port” and
press [Enter] . Next, set the slot number to the slot of the scanner module .
2) Communications Command: Always set to “CIP Generic” .
3) Target Type and Address: Always set the Target Type to “Network Device” and set the Local Node Address to the
MAC address of the RM-89 .
4) Service Type: Depends on what you are accomplishing with the instruction . Setting the Service Type to Custom
will allow you to set the Service Code field . Otherwise, the Service Code will automatically update when you
change the Service Type .
5) Class: Always 23
hex
if you have to set it yourself . Other classes are used, but they will be automatically set when
you select the appropriate Service Type .
6) Instance: Usually “1” . Set to “0” when issuing a Reset, Save to Flash, or Restore from Flash command .
7) Attribute: Depends on what you are accomplishing with the instruction .
8) Source Length: The length of the data you are writing down to the RM-89 . This length is always in bytes .
9) Send Address: The starting address in memory that will be the source of the data you are writing to the RM-89 .
Figure 5 .2 RSLogix 500 MSG Example
2
4
5
6
7
1
8
9
3