3.3. Battery connection
For safe operation and compliance, a separate DC over-current
protector or disconnect device is required between the battery and
the inverter. In some applications, switching devices may not be
required but over-current protectors are still required. Refer to the
typical amperage in the table below for the required fuse or circuit
breaker size.
Model
Cable
Cable (mm
2
)
Torque value(max)
5KW
3AWG
25
5.2Nm
Please follow the steps below to implement battery connection:
1.
Please choose a suitable battery cable with correct connector
which can well fit into the battery terminals.
2.
Use a suitable screwdriver to unscrew the bolts and fit the
battery connectors in, then fasten the bolt by the screwdriver.
Make sure the bolts are tightened with torque of 5.2 N.m in
clockwise direction.
3.
Make sure polarity at both the battery and inverter is correctly
connected.