Three Phase 120V/208V: Mainly for commercial systems in North America and
South America. The phase voltage may vary from 110V to 127V. The outputs of
microinverters are connected between two live lines, L1~L2, L2~L3 or L3~L1.
Make sure the CT/Meter range can cover the maximum loads power or PV system
generating power. There are 3 types of CHINT meter and different types of CT that you
can choose base on the actual installation requirement.
Step 3: Confirm the loads’ capacity for CT and Meter
Meter Model
DDSU666(60A)
DTSU666(80A)
DTSU666(5A)
SN
10C011XXXXXX
10C013XXXXXX
10C012XXXXXX
Description
Direct connect, NOT via any kind of CT
Direct connect, NOT via any kind of CT
Compatible with 100A/5A, 300A/5A, and 600A/5A CT
Type
Single Phase
Three Phase
Three Phase
Grid Type
Single Phase System (230V)
Three Phase System (230V/400V)
Split Phase System (120V/240V)
Three Phase System (120V/208V)
Meter Model
DDSU666(60A)
DTSU666 (100A/5A,300A/5A, 600A/5A),
DTSU666 (80A)
Talent-MG2-WP/GP
17