The diagram below shows the pin-outs of the alarm interface port.

If you wish to use the alarm interface port for custom applications, take into
consideration the following limitations.
• Pins 3, 5 & 6 are open-collector outputs, limited to switching 40V and
sinking 20mA of current.
• Pins 2 and 7 are RS-232 compatible outputs.  They will switch from RS-
232 low (about -10V) to high (about +10V), and can drive a 25mA load.
• A positive (> 5V) pulse lasting longer than 1/4 second at pin 1 is required
to shut down the UPS during power failures.  This pin is inactive when the
AC mains is normal.
• For best performance, your alarm monitoring circuit should be isolated (via
transformers, relays or optocouplers) from the rest of your network.

Should you have any questions

related to the UPS hardware,

please call TSi Power at (715)

623-0636.  For software related

questions, please contact your

software vendor first.

¨

5

4

3

2

1

9

8

7

6

Pin #

1

6

2

7

3

4

9

5

Name

SHUTDOWN

ACFAIL (O-C)

ACFAIL

BATLOW

ACFAIL (O-C)

GND

GND

BATLOW (O-C)

Function

Input to UPS. A positive pulse              5V or higher and lasting longer than 1/4 sec will shut down 
the UPS when it is running on battery power.

Open-Collector Output from UPS.  Normally open, this transistor switch will close when AC fails.

Output from UPS.  Normally low, this signal will go high when AC fails.

Output from UPS.  Normally low, this signal will go high when about 2 minutes of battery reserve 
power (at full load) remains.

Open-Collector Output from UPS.  Normally closed, this transistor switch will open when AC fails.

Ground.

Ground.

Open-Collector Output from UPS.  Normally open, this transistor switch will close when about 2 
minutes of battery reserve power (at full load) remains.

RS-232

BAT NORMAL

BAT LOW

AC GOOD

AC FAIL

AC GOOD

AC FAIL

RS-232

BAT NORMAL

BAT LOW

NORMAL

SHUTDOWN

UPS INTERNAL ALARM CIRCUIT

Some older units may not be

equipped with all the functions

shown.  Please call TSi Power

for more information.

¨

Network Installation & Alarm Interface    

7

© Copyright—2000 TSi Power Corporation.  All rights reserved.

TSi Power’s ongoing product improvement process makes specifications subject to change.

Other company’s  product names herein are for identification purposes only and may be trademarks of their respective companies.

Summary of Contents for UPS-550B

Page 1: ...POWER CORPORATION 1103 West Pierce Avenue Antigo WI 30071 USA Phone 715 623 0636 FAX 715 623 2426 Internet www tsipower com e mail sales tsipower com Copyright 2000 TSi Power Corporation All rights re...

Page 2: ...battery supply inside the UPS is 24 volts Maximum Operating Ambient Temperature for the UPS and Battery Extension Unit is 40 degrees Celsius When you are using the rack cabinet or wall mounting kits p...

Page 3: ...UPS Access 8 Typical Holdup Times 10 Trouble shooting and Maintenance 11 UPS Technical Specifications 12 Installation Procedure for Mounting Kits 13 i Copyright 2000 TSi Power Corporation All rights...

Page 4: ...the large power on off switch in the front of the UPS and turn the UPS on All your equipment hooked up to the UPS should now be ready to power up Congratulations You ve already taken a large step tow...

Page 5: ...rging Light This red light is on when battery is being charged F Inverter On Light This yellow light blinks when AC power is abnormal and UPS is operating on battery G Remote Mode Light some models Th...

Page 6: ...odem connectors for remote access Connect the incoming phone line to LINE connector other phone equipment telephone fax modem etc to the MODEM connector U P S O U T P U T CAUTION TOREDUCETHE RISKOFFIR...

Page 7: ...uch more Its architecture is that of a standby UPS or off line UPS whose inverter is only activated when the line AC becomes irregular This has the advantage of lower cost and greater reliability sinc...

Page 8: ...e on indicating that the battery is being recharged This is normal 5 As a test you may simulate a power outage by unplugging the UPS power cord from the AC outlet All your equipment connected to the U...

Page 9: ...ours 11 When an overload occurs and the UPS shuts off you must remove the excess load and reset the UPS by turning it off and then on before the UPS will resume proper operation Your UPS will hold up...

Page 10: ...S A positive pulse 5V or higher and lasting longer than 1 4 sec will shut down the UPS when it is running on battery power Open Collector Output from UPS Normally open this transistor switch will clos...

Page 11: ...within this time The UPS will not interfere with the modem or telephone It may take about a minute after the UPS is turned on for the first time before the MODE switch becomes operational U P S O U T...

Page 12: ...ou need to access the remote PC you would dial the UPS turn on the remote PC and let your home modem and remote modem establish a connection When finished you can hang up and power to the PC will be t...

Page 13: ...y be trademarks of their respective companies Typical Holdup Times A typical desktop PC or Macintosh draws between 200 and 300 watts The table below shows some typical holdup times with a computer loa...

Page 14: ...attempt to repair the UPS High voltages are present and there are no user servicable parts inside Repairs can be performed only at the factory or at an authorized repair centers by qualified personnel...

Page 15: ...ransfer back to AC Transfer Time 1 millisecond phase locked to the AC Two long life leak proof sealed lead calcium batteries each rated at 12VDC 7A h provide 168VA h of capacity Typical recharging tim...

Page 16: ...ssembled properly with the equipment mounting rails securely installed at the intended location This should be either in the front or rear of the cabinet for MK 5000A or in the center of the cabinet f...

Page 17: ...he desired height Fasten the screws B provided with the kit through the mounting bracket into the rails using the clip nuts previously installed Wall Mounting for MK 5000C only 1 Make sure that the wa...

Page 18: ...IS NOT LIABLE FOR CONSEQUENTIAL DAMAGES THIS WAR RANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE Excluding batteries Battery manufacturer s war...

Reviews: