background image

MAINTENANCE AND INSPECTION

 

 Disconnect the unit and release all pressure from the 

system before installing, moving or making any maintenance or 

service jobs. 

Regularly inspect the compressor. Look for visible damage and follow 

the maintenance procedure every time you use the unit.

1.  Pull the safety valve ring to make it go back to its initial position. 

 

 The safety valve shall be replaced in a TASC* if it 

cannot be moved or it leaks air after the ring has been released.

2.  Turn off the compressor and release pressure from the system.

3.  Clean all dust and mud from the motor and air-lines. Move 

vertically the cooling blades while the compressor is off. 

 

 Set the unit as far away as possible from the spraying 

area.  The hose will help preventing excessive spraying in the event the 

filter gets clogged.

LUBRICATION: 

No oil and no lubrication are required for this 

compressor.

THERMAL OVERLOAD PROTECTION

                        This compressor is built with an automatic thermal 

overload protector.

It will turn off the motor if there is overload.

If the overload protector turns off the motor too frequently check the 

following:

1.  Voltage drop.

2.  Clogged air filter.

3.  Not enough ventilation.

                       

The motor shuts off when the switch is activated. To re-establish the 

motor follow the following steps:

1.  Press the switch to ensure that the compressor is off.

2.  Let the compressor cool down for at least 5 minutes.

3.  Press the thermal switch located on the side of the crankcase.

4.  Lift the switch to start the compressor.

STORAGE

1.  Store the compressor in a dry place while not in use.

2.  Disconnect the hose and let both ends open and facing down to 

allow drying.

 

5

WARNING

WARNING

WARNING

WARNING

WARNING

PROBLEM

POSSIBLE CAUSE

SOLUTION

The compressor is not working

1. No electicity

2. Blown fuse in the installation.

3. Switch is open.

4. Thermal overload is activated.

5. Faulty pressure button.

1. Is it connected? Check fuse / switch or 

motor overload.

2. Replace blown fuse.

3. Restart and determine what caused the 

problem

.

4. The motor will be on when it cools down.

5. Replace in a Truper Authorized Service 

Center

.

The motor buzzes but is not running 

or runs slowly

1. Check valve is damaged or low.

2. Poor contact, voltage drop.

3. Damaged motor.

1. Replace or repair in a TASC*.

2. Check connections, remove electric 

extensions, check circuit using a voltmeter

.

3. Replace motor in a TASC*

The fuses blow

The circuit breaker is repeatedly 

activated.

CAUTION!

 NEVER USE AN 

EXTENSION CABLE WITH THIS UNIT!

1. Wrong fuse size. Overloaded circuit.

2. Faulty or low check valve.

1. Verify you are using the right fuse. Use a 

timedelay fuse. Disconnect other units

 

using the same circuit or operate the 

compressor in an independent circuit.

2. Replace or repair in a TASC*

The thermal overload protection 

repeatedly shuts down.

1. Voltage drop

2. Blocked air filter.

3. There is no adequate ventilation.

4. Verify if the valve is malfunctioning.

5. The compressor valves are not working.

1. Do not use extension. Check using a 

voltmeter

.

2. Clean the filter (see Maintenance section)

3. Move the compressor to a well-ventilated 

area.

4. Replace in a TASC*

5. Replace valve in a TASC*

Air outlet is lower than normal. Low 

pressure relief.

Pressure in the tank drops when the 

compressor stops.

1. Excessive use of air. The compressor is 

too small

.

2. Filter inlet is clogged.

3. Air comes out from the pipes (inside the 

machine out of the system

)

4. Broken inlet valves.

5. Worn piston ring.

1. Reduce the use of air or buy a larger unit 

with more air capacity (CFM)

2. Clean or replace in a TASC*

3. Replace parts in a TASC* or adjust if 

necessary.

4. Replace compressor valves in a TASC*

5. Replace piston and cylinder in a TASC*

Compressor stars in a continous 

mode and the safety valve opens 

when pressure is up.

1. Defective pressure button.

2. Defective safety valve.

1. Go to a TASC*

2. Go to a TASC*

Air leak in the relief valve.

Double-check the valve is not stuck in the 

open position.

Remove or replace check valve in a TASC*

TROUBLESHOOTING

TASC*: TRUPER AUTHORIZED SEVICE CENTER

Summary of Contents for 19361

Page 1: ...MP POR 2 5 C digo 19361 NOTA IMPORTANTE Este producto no debe quedar expuesto a goteo o salpicaduras por l quidos Compresor port til de aire Instructivo Lea este Instructivo por completo antes de usar...

Page 2: ...bre la m quina o se cruce cuando est en funcionamiento 12 No extienda su radio de acci n Evite toda postura que cause cansancio Cuide de que su posici n sea segura y de que conserve el equilibrio 13 M...

Page 3: ...lta presi n las siguientes precauciones deber n tomarse en cuenta siempre 1 Siga todos los c digos de seguridad y electricidad local 2 El compresor deber usarse s lo por personas que est n dispuestas...

Page 4: ...zar todos los c digos el ctricos para estas cantidades 2 Utilice un interruptor o fusible de acci n lenta Si no se hace una conexi n adecuada se podr a provocar un sobrecalentamiento choque el ctrico...

Page 5: ...umedad producida por el aire comprimido se podr observar por medio de gotas mientras ste sale de la bomba de aire comprimido Cuando la humedad sea alta o cuando el compresor se encuentre en uso contin...

Page 6: ...esi n da ado 1 Est conectado Revise el fusible interruptor o sobrecarga de motor 2 Reemplace fusible da ado 3 Vuelva a iniciarlo determinar causa del problema 4 El motor volver a prender cuando se enf...

Page 7: ...o 670655 FERREPRECIOS S A DE C V LIBERTAD ORIENTE No 304 LOCAL 30 INTERIOR DE PASAJE ROBLEDO COL CENTRO TEL 01 775 753 6615 16 Jalisco Guadalajara 670855 MAGNOCENTRO FERRETERO S A DE C V AV LA PAZ 118...

Page 8: ...e tener alg n problema para contactar un centro de servicio consulte nuestra p gina www truper com donde obtendr un listado actualizado o llame al Tel 01 800 690 6990 o 01 800 018 7873 donde le inform...

Page 9: ...Model COMP POR 2 5 Code 19361 Portable air compressor Manual IMPORTANT NOTICE This product should not be exposed to liquids dripping or splashing Read the user s manual thoroughly before operating th...

Page 10: ...ing one hand and enables to use both hands Keep proper footing and balance at all times Do not overreach over or walk across the tool when is running 12 Do not extend your range of action Avoid a stan...

Page 11: ...CIFIC SAFETY INSTRUCTIONS Since the air compressor and other components could produce high pressure pumping please use care and follow these caution measures 1 Follow all local safety and electricity...

Page 12: ...shock because it offers an escape cable to the electric current This product is built with and adequate grounded plug The plug shall be connected to a correctly installed and grounded power outlet th...

Page 13: ...UMIDITY IN THE COMPRESSED AIR Humidity produced by compressed air can be observed drops are present when air is coming out from the compressed air pump Humidity will increase when humidity is high or...

Page 14: ...switch or motor overload 2 Replace blown fuse 3 Restart and determine what caused the problem 4 The motor will be on when it cools down 5 Replace in a Truper Authorized Service Center The motor buzze...

Page 15: ...REPRECIOS S A DE C V LIBERTAD ORIENTE No 304 LOCAL 30 INTERIOR DE PASAJE ROBLEDO COL CENTRO TEL 01 775 753 6615 16 Jalisco Guadalajara 670855 MAGNOCENTRO FERRETERO S A DE C V AV LA PAZ 1180 COL CENTRO...

Page 16: ...ILLAHERMOSA TAB C P 86010 CONMUTADOR 01 993 353 7244 In the event of any problem contacting a Service Center please see our webpage www truper com to get an updated list or call our toll free numbers...

Reviews: