5.1
Calculating required cooling water
temperature
Dew point diagram
Fig. SG-02007
1. Measure ambient temperature (in the example: 36 °C).
2. Measure the relative humidity (80 % in the example).
3. Draw a vertical line in the diagram from the measured ambi-
ent temperature upwards until it intersects with the straight
line representing the measured humidity.
4. Draw a horizontal line from the point of intersection to the
dew point temperature.
5. Read dew point temperature (in the example: 32 °C).
The temperature of the cooling water flowing through the focus-
ing optics must be at least 2 °C above the dew point tempera-
ture: In the example, the cooling water temperature should be at
least 34 °C.
Note
Observe the laser device and welding optics requirements when
determining the required cooling water temperature. In tropical
countries, the cooling of the focusing optics must be ensured
using an external cooling unit.
12-29-01-A1-CRen
2022-03
Ambient conditions
2
‐
51
Summary of Contents for KF023
Page 1: ...Operator s manual Programmable focusing optics PFO 33 KF023...
Page 2: ......
Page 6: ...II Good to know 2022 03 12 29 01 A1 CRen...
Page 12: ...0 6 Table of contents 2022 03 12 29 01 A1 CRen...
Page 81: ...Protective glass monitoring active Fig 112272 12 29 01 A1 CRen 2022 03 Installation 2 43...
Page 90: ...2 52 Ambient conditions 2022 03 12 29 01 A1 CRen...
Page 112: ...3 22 Software 2022 03 12 29 01 A1 CRen...
Page 142: ...4 30 Adjusting the observation optics 2022 03 12 29 01 A1 CRen...
Page 170: ...5 28 Cooling water 2022 03 12 29 01 A1 CRen...
Page 176: ...6 6 Informing the service department 2022 03 12 29 01 A1 CRen...