Safety Warnings
WARNING: INSTALLATION AND MAINTENANCE MUST BE CARRIED
OUT BY SUITABLY QUALIFIED AND COMPETENT PERSONEL ONLY.
HAZARDOUS VOLTAGES MAY BE PRESENT ON THE CONNECTION
TERMINALS.
INSTALLATION
•
Install this product in accordance with local regulations, codes and instructions.
•
All fuses must be 0.5A / 250V Type F with a breaking capacity of 35A or greater.
•
All conductors carrying hazardous voltage must have external switching or disconnect
mechanisms fitted that provide at least 3 mm of contact separation in all poles.
•
Signal cables connected to this device must not exceed 30 metres long.
•
If signal cables are routed outside the building, install extra surge-protection devices.
•
Power supply, current input, USB and all outputs: Observe maximum allowable voltages.
All circuits connected to these connectors must be limited-energy and insulated by
double/reinforced insulation from mains voltages according to IEC 61010-1:2010
Failure to install or operate the unit in accordance with the above
requirements may impair the electrical safety of the unit.
Voltage measurements: An external UL recognized or listed
overcurrent protection device (fuse or circuit breaker) must be fitted
in-line with the voltage lead. Recommended fuse: 0.5A Type F with a
breaking capacity of 35A or greater. Fuse voltage rating must be
greater than the maximum voltage that will be applied to the meter.
MAINTENANCE
•
Before cleaning, inspection or maintenance, isolate all power sources to the unit.
•
There are no user-serviceable parts inside this unit. Never open the case.
•
Inspect all external wiring connections at regular intervals. Replace any damaged wiring
and tighten any loose connections.
•
To clean the unit, use a dry cloth to wipe the casing.
•
Take great care connecting the supply. If you connect power to the wrong terminals, it may
destroy the unit.
Specification
Outputs When Powering APM from DC Supply
VALUE
4-20 mA analogue output using setpoint 1.
Using a diode-protected relay on setpoint 1.
Outputs when powering APM from AC supply
Reset
When powering from an AC supply only connect isolated devices or other
APMs to the COM terminal
(in this application SP1 was configured as an analogue output using the APM Configurator)
Use the Reset input with the peak hold function
D
Environment
Temperature - operating
–10 to +60 deg C
Temperature - storage
–40 to +70 deg C
Altitude
2000 metres
Relative Humidity (non-condensing)
– Continuous
0
– 85 %
Relative Humidity (non-condensing) - Intermittent
0
– 95%
Pollution Degree (IEC664)
2
IP rating (from the front)
IP65
NEMA Rating (from the front)
Type 4 & Type 12
Vibration
Shock
Power supply
Input
12-24V AC/DC +/-10%
Max Power
1.6W
Isolation
None
Supply Frequency
DC & 50-400 Hz
Display
Number of digits
4
Digit height
12 mm
Number of bar-graph segments
40
Number of starburst message characters
4
Backlight colours
Red, Green, White
LCD
Positive or negative
Digit update frequency
0.08
– 21 sec
Bar-graph update frequency
0.08
– 21 sec
Viewing angle
+/-70° Horizontal
+/-70° Vertical
Open Collector Outputs
Max voltage (open collector outputs)
34 V
Max current (open collector outputs)
500 mA
Analogue Output
Output
4-20 mA
Accuracy
0.50 %
Resolution
0.02 mA
Connections
Type
Screw Terminals
Wire type
Solid or Stranded
Min. cable temperature rating
65 deg C (149F)
Wire strip length
6.5mm to 7mm
(0.26” to 0.28”)
Wire gauge
0.8mm² - 3.3mm²
(18AWG to 12AWG)
Torque
0.5-0.6Nm
(4.42-5.31 lbf-in)
Certification
CE
IEC 61010-1
In the Box
APM
Getting started & safety guide
Gasket
Retaining clip
Panel Cut-out:
68 x 68 mm (2.68 in) +0.7 -0 mm (0.02
in).
Max. panel thickness:
10 mm.
Dimensions
: Depth behind panel inside front: 55mm
(2.17in) incl. external connections.
Weight
: 180 grams.