10.4 Timer 

Seconds   

    0.001 s ... 999 999 s 

Minutes 

 

    0.001 min ... 999 999 min 

Hours  

 

    0.001 h .. 999 999 h 

h.min.s 

 

    00h.00min.01s ...   

 

 

 

    99h.59min.59s 

Min. time measurable  500μs 

Measuring error      < 50 ppm 

Response time of the outputs: 

 

Relays 

     

< 7 ms 

 

Optocoupler     

< 1 ms 

 

10.5  Signal and Control inputs 

Polarity: 

 

  programmable NPN/PNP 

 

 

 

  for all inputs in common 

Input resistance    5 k

:

 

Pulse shape 

  any 

Switching level with AC supply: 

HTL level   

  Low: 

0 ... 4 VDC 

 

 

 

  High: 

12 ... 30 VDC 

5V level 

 

  Low: 

0 ... 2VDC 

 

 

 

  High: 

3,5 … 30 VDC 

Switching level with DC supply: 

HTL level   

  Low: 

0 ... 0,2 x UB 

 

 

 

  High: 

0,6 x UB ... 30 VDC 

5V level 

 

  Low: 

0 ... 2 VDC 

 

 

 

  High: 

3,5 ... 30 VDC 

Minimum pulse length of the Reset input:   1 ms 

Minimum pulse length of the Control inputs:10 ms 

10.6 Outputs 

Output 1 

Relay with make contact  

programmable as NC or NO 

Switching voltage   max. 250 VAC/ 110  VDC 

Switching current    max. 3 A AC/ V DC 

 

 

 

  min. 30 mA DC 

Switching capacity  max. 750 VA / 90 W 

Mechanical service life (switching cycles)    2x10

7

 

N° of switching cycles at 3 A/ 250 V AC    1x10

N° of switching cycles at 3 A/ 30 V DC 

  1x10

 

or NPN optocoupler 

Switching capacity     

30 VDC/10 mA 

U

CESAT

 for IC = 10 mA:    

max. 2.0 V 

U

CESAT

 for IC =   5 mA:    

max. 0.4 V 

 

Output 2 

Relay with changeover contact 

Switching voltage   max. 250 VAC/ 150 VDC 

Switching current    max. 3 A AC/ A DC 

 

 

 

  min. 30 mA DC 

Switching capacity  max. 750 VA/ 90 W 

Mechanical service life (switching cycles)     20x10

6

 

N° of switching cycles at 3 A/ 250 V AC       5x10

4

 

N° of switching cycles at 3 A/ 30 V DC      5x10

4

 

 

or NPN optocoupler 

Switching capacity     

30 V DC/10 mA 

U

CESAT

 for IC = 10 mA:    

max. 2.0 V 

U

CESAT

 for IC =   5 mA:    

max. 0.4 V 

 

10.7  Supply voltage 

AC supply:   

  90 ... 260 V AC / max. 8 VA 

 

 

 

  50/ 60 Hz 

 

 

  ext. fuse protection: T 0.1 A 

DC supply:   

  10 ... 30 V DC/ max. 1.5 W 

 

 

 

  reverse polarity protection 

 

 

  ext. fuse protection T 0.2 A 

10.8  Sensor supply voltage 

AC supply:   

24 V DC 

r

15%, 80 mA 

DC supply:   

 max. 80 mA, external voltage 

supply is connected through 

10.9  Climatic Conditions 

Operating temperature:  -20°C .. +65°C 

Storage temperature:   -25°C .. +75°C 

Relative humidity: RH.  93% at +40°C,  

 

 

 

    non-condensing 

Altitude: 

 

    to 2000 m 

10.10 EMC 

Noise immunity:    EN61000-6-2 

with shielded signal and 

control cables 

Noise emission:    EN55011 Class B 

10.11  Device safety 

Design to:   

  EN61010 Part 1 

Protection Class:    Class 2 

Application area:    Soiling Level 2 

10.12  Mechanical Data 

Housing:   

  Panel-mount housing 

 

 

 

  to DIN 43 700, RAL 7021 

Dimensions: 

  48 x 48 x 91 mm 

Panel cut-out: 

  45

+0,6

 x 45

+0,6 

mm 

 

Installation depth:   ca. 107 mm incl. terminals 

Weight: 

 

  ca. 125 g 

Protection:   

  IP 65 (front) 

Housing material:   Polycarbonate UL94 V-2 

Vibration resistance: 10 - 55 Hz / 1 mm / XYZ 

(EN60068-2-6):    30 min in each direction 

 

Shock resistance    100G / XYZ 

(EN60068-2-27):    3 times in each direction 

Cleaning:   

  The front of the unit should  

only be cleaned using a soft 

damp (water!) cloth. 

10.13 Connections 

Supply voltage and outputs: 

Plug-in screw terminal, 7-pin, RM5.08 

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Summary of Contents for 924K

Page 1: ...924K Electronic Preset Counter with two presets Installation and Operating Instructions www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com...

Page 2: ...12 7 9 Setting the presets 16 7 9 1 Setting via Decade Keys 16 7 9 2 Setting with Teach In Function 16 7 9 3 Setting the tracking presets 16 7 10 Set Function 16 8 Error message 16 9 Connections 17 9...

Page 3: ...damaging the machine or causing an accident to the operators then it is your responsibility to take the appropriate safety measures 2 2 Mounting in a control panel CAUTION Mount the device away from...

Page 4: ...or 10 30 VDC 4 Display Operating elements T1 6 Decade key T1 T6 P Prog Mode key R Reset key 8 Current count value main counter 9 Preset value Total count Batch counter 10 Run display for Timer 11 Sho...

Page 5: ...xt and T1 back 7 3 Entering a sub menu The sub menu is opened with the Prog Mode key and the first menu item is displayed 7 4 Selecting the menu items The Prog Mode key is used to select a menu item w...

Page 6: ...etting Parameter set 3 Freely programmable User settings Factory settings are highlighted in grey 7 8 2 Table Parameter Sets P SEt 1 P SEt 2 P SET 3 Func Count Count Count InP PoL PnP PnP PnP FiLtEr o...

Page 7: ...rement A B Inp A count input A Inp B count input B Percentage differential counting A B A in Inp A count input A Inp B count input B User input When the MPI input is activated the display is frozen an...

Page 8: ...ter preset 1 Manual reset sets main counter to preset value 2 batch counter to zero Electrical reset only sets the main counter to preset value 2 Count mode ADDING with automatic reset and Total count...

Page 9: ...lay colour upper line red lower line red Display colour upper line red lower line green 7 8 4 4 Submenu for reset mode Setting the reset mode Manual reset with red key and electrical reset reset input...

Page 10: ...Lock input is activated the setting of the preset values and the programming are both inhibited 7 8 5 2 Submenu for configuration Submenu for matching the input pulses and display Multiplication facto...

Page 11: ...top Edge to Inp B Start 1 Edge to Inp B Stop 2 Edge to Inp B Timing can only be controlled via the Gate input Inp A and Inp B no function The timer is reset by means of a RESET to zero when adding to...

Page 12: ...petitions of preset 2 Output 1 active when batch counter preset 1 manual reset sets both counters to zero electrical reset sets only main counter to zero Count mode SUBTRACTING with automatic reset an...

Page 13: ...imal place 0 0 1 decimal place 0 00 2 decimal places 0 000 3 decimal places Set value Set value can be programmed from 000000 to 999999 A previously programmed decimal point will be displayed Display...

Page 14: ...t Preset 1 Duration of timed signal of Output 1 programmable from 00 01 to 99 99 s Timed signal is post triggered 7 8 6 6 Submenu for Preset 2 Submenu for Preset 2 ADD mode output operations permanent...

Page 15: ...ue will be accepted and the counter will switch back to operating mode 7 9 2 Setting with Teach In Function Program the MPI input to tEAch In programming mode select the preset to be changed using the...

Page 16: ...0 VDC Supply voltage 15 AC 90 260 VAC L DC GND 0 VDC Supply voltage 10 Technical Data 10 1 General Data Display LCD positive or negative backlit 2 x 6 digit Digit height upper line 9 mm lower line 7 m...

Page 17: ...tching cycles 20x106 N of switching cycles at 3 A 250 V AC 5x104 N of switching cycles at 3 A 30 V DC 5x104 or NPN optocoupler Switching capacity 30 V DC 10 mA UCESAT for IC 10 mA max 2 0 V UCESAT for...

Page 18: ...es 6 924 X1XX XX0 Input trigger levels 0 Standard HTL A 5V Supply voltage 0 90 260 VAC 3 10 30 VDC LCD version 0 no backlighting 1 green backlighting 2 LED Look 3 Multicolour Outputs 0 Relay 1 Optocou...

Page 19: ...2 7 kHz 2 4 kHz Up Dn Up Up 9 kHz 2 7 kHz 2 4 kHz Quad Quad 2 9 kHz 1 2 kHz 1 2 kHz Quad 4 9 kHz 1 2 kHz 0 9 kHz A B A B A 9 kHz 13 2 Frequency meter HTL level AC supply typ Low 2 5 V typ High 22 V D...

Page 20: ...ount input add Inp B Count input sub Add Display 0 Preset Sub Display Preset 0 Up Up Inp A Count input 1 add Inp B Count input 2 add Add Display 0 Preset Quad A 90 B Inp A Count input Count on one edg...

Page 21: ...unt input Count on rising and on falling edges Inp B Count input Count on rising and on falling edges Reverse direction Add Display 0 Preset Sub Display Preset 0 A B Inp A Count input 1 Inp B Count in...

Page 22: ...ction Inp B Start Stop Add Display 0 Preset Sub Display Preset 0 FrRrun Inp A no function Inp B no function Control of the timing only via the GATE input Add Display 0 Preset Sub Display Preset 0 Auto...

Page 23: ...cy input 1 Inp B Frequency input 2 Formula A B AaddB Inp A Frequency input 1 Inp B Frequency input 2 Formula A B Quad A 90 B Inp A Frequency input 1 Inp B Reverse direction A B Inp A Frequency input 1...

Page 24: ...5 17 Output operations Mode Diagram Mode Diagram Only in the mode and Additionally in the mode and Add Sub AddAr SubAr AddBat SubBat AddTot SubTot www GlobalTestSupply com Find Quality Products Online...

Page 25: ...Page 26 www kuebler com Seite 26 Mode Diagram Trail TrailAr www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com...

Page 26: ...hl und Sensortechnik P O Box 3440 D 78023 Villingen Schwenningen Germany Tel 49 0 77 20 39 03 0 Fax 49 0 77 20 2 15 64 sales kuebler com www kuebler com R600318 91 4 25 max 10 5 7 45 48 48 15 5 Panel...

Reviews: