Truma CP classic Operating And Installtion Instructions Download Page 10

21

 Fault

 Cause

 Rectification

Yellow LED flashes 2 x

 

– Overvoltage > 16.4 V

 

– Check battery voltage and voltage sources such as the

charger

(Only with Combi E)

 

– No 230 V operating voltage

 

– 230 V fuse defective

 

– Overheating protection has been 

triggered

 

– Restore 230 V operating voltage

 

– Replace 230 V fuse

 

– Reset overheating protection, allow heating system to cool, 

remove connection cover and press reset button

Yellow LED flashes 3 x

 

– Open window above cowl 

(window switch)

 

– Close window

Yellow LED flashes 4 x

 

– Warm air temperature and / or 

water temperature exceeded:

 

– Not all warm air ducts are 

connected

 

– Warm air outlets blocked

 

– Circulated air intake blocked

 

– Check whether the 4 warm air ducts are connected

 

– Check individual outlet apertures

 

– Remove blockage from circulated air intake

 

– Summer mode with empty 

water container

 

– Fill boiler with water

Yellow LED flashes 5 x

 

– Room temperature sensor or 

cable defective

 

– Please contact Truma Service

Yellow LED flashes 6 x

 

– Water temperature exceeded in 

summer mode

 

– Fill boiler with water

Yellow LED flashes 7 x

 

– Control panel or control panel 

cable defective

 

– Please contact Truma Service

Yellow LED flashes 8 x

 

– FrostControl heating element 

has a short circuit

 

– Disconnect heating element plug from electronic control unit, 

replace heating element

If these actions do not remedy the problem, please contact Truma Service.

Summary of Contents for CP classic

Page 1: ...hren Operating instructions Page 13 Installation instructions Page 22 To be kept in the vehicle Mode d emploi Page 24 Instructions de montage Page 33 garder dans le v hicule Istruzioni per l uso Pagi...

Page 2: ...23 Assembly 24 Symbols used The unit must only be installed and repaired by an expert Note containing information and tips Please pay attention to the ESD regulations Electrostatic charge can destroy...

Page 3: ...ing or with drained water system Operating instructions e Heating and hot water mode heating with water temperature monitoring f Rotary switch Off g Yellow LED lit Boiler heat up phase yellow LED flas...

Page 4: ...he yellow LED o at the power selector switch indicates that the unit is operating with 230 V Heating with water temperature monitoring Move rotary switch on control panel to On position e Set the rota...

Page 5: ...elect the required operating level according to the tempera ture difference between the setting on the control panel and the current room temperature Once the room temperature selected on the control...

Page 6: ...ow LED o on the power selector switch illuminates and the red LED h or the yellow LED g on the control panel flashes Possible causes can be found in the troubleshooting guide If the flame goes out dur...

Page 7: ...the heating system does not operate The temperature setting on the control panel is lower than the room temperature Select higher room temperature at the control panel After switching on the heating...

Page 8: ...heck gas supply and open valves Gas cylinder empty Replacing a gas cylinder After operating for a longer pe riod of time the heating system switches to failure Gas pressure regulation system iced up U...

Page 9: ...th 5 Hz after the heating system has been switched off After running is active to reduce the temperature of the unit No fault after run switches itself off after max 5 minutes Red LED flashes 6 x Lack...

Page 10: ...s are connected Warm air outlets blocked Circulated air intake blocked Check whether the 4 warm air ducts are connected Check individual outlet apertures Remove blockage from circulated air intake Sum...

Page 11: ...istrative regulations of the respective country in which it is used National regulations and laws in Germany for example the End of life Vehicle Regulation must be observed Declaration of conformity T...

Page 12: ...tered see Truma Service Booklet or www truma com In order to avoid delays please have the unit model and factory number ready see type plate Veuillez vous adresser au centre de SAV Truma ou un de nos...

Reviews: