True T-12FG Installation Manual Download Page 28

............ www.truemfg.com ............

True Food Service Equipment, Inc.

26

26

INSTALLATION / OPERATION INSTRUCTIONS

4.   If all operating conditions are 

normal, the voltage supply at the 

compressor terminals balanced and 

within limits, the compressor crankcase 

temperature within normal limits, and 

the amperage drawn within the specified 

range, the motor protector may be 

defective, and should be replaced.

If the operating conditions are normal 

and the compressor is running excessively 

hot for no observable reason, or if the 

amperage drawn is above the normal 

range and sufficient to repeatedly trip the 

protector, the compressor has internal 
damage and should be replaced.

IF THE COMPRESSOR RUNS BUT WILL 

NOT REFRIGERATE

1.   Check the refrigerant charge. Check 

the evaporator surface to determine 

if it is evenly cold throughout, or if 

partially starved. A lack of charge may 

be indicated by light, fluffy frost at 

the evaporator inlet. Add refrigerant if 

necessary.

2.  Check the compressor suction 

pressure. An abnormally low pressure 

may indicate a loss of refrigerant charge, 

a malfunctioning capillary tube, a lack of 

evaporator capacity possibly due to icing 

or low air flow, or a restriction in the 

system.

Often a restriction in a drier or strainer 

can be identified by frost or a decrease 

in temperature across the restriction due 

to the pressure drop in the line. This 

will be true only if liquid refrigerant is in 

the line at the restricted point, since any 

temperature change due to restriction 

would be caused by the flashing of liquid 

into vapor as the pressure changes.

Any abnormal restriction in the system 

must be corrected.

3.   Check the compressor discharge 

pressure. An abnormally high discharge 

pressure can cause a loss of capacity, and 

can be caused by a dirty condenser, a 

malfunctioning condenser fan, or air in 

the system.

4.   If the suction pressure is high, 

and the evaporator and condenser 

are functioning normally, check the 

compressor amperage draw. An amperage 

draw near or above the nameplate rating 

indicates normal compressor or unit may 

have damaged valves.

An amperage draw considerably below 

the nameplate rating may indicate a 

broken suction reed or broken 

connecting rod in the compressor.

DIAGNOSIS AND REPLACEMENT OF 

FREEZER CABINET COMPONENTS

1. Defrost Time Clock

 

A.   Check timer motor to be sure 

 

    it runs.

 

B.   Check contacts on the defrost  

 

    timer.

 

C.   Check solenoid windings for  

 

    continuity to ensure contact  

 

    switching.

 

D.  Check to be sure defrost 

 

    actuator pins are in proper 

 

    position.

 

E.   Check all wires in the timer for  

 

  tightness to terminals and 

 

    broken wires.

2. Defrost Control On The    

Evaporator Drain Pan

 

A.   If the defrost time is always 

35 minutes (or whatever duration the 

elapsed time adjustment is set at) and 

the fan motors do not delay after a 

defrost cycle and it has been determined 

that the solenoid in the defrost clock is 

functioning, change the defrost control 

in the evaporator compartment in 

the top of the freezer. This control is 

attached to the evaporator drain pan.

3. Coil Defrost Heater

 

A.   Lower the evaporator cover. 

Disconnect the coil heater by removing 

the wire nuts at the point where the 

heater joins the electrical circuit of the 

freezer in the evaporator compartment. 

Check heater for continuity with an 

ohmmeter. If the heater is defective, cut 

the bale wires holding the heater to the 

coil and remove the heater. Replace with 

a new heater using bale wires provided.

4.  Drain Tube Heater

 

A.   Lower the evaporator cover. 

Disconnect the drain tube heater by 

removing the wire nuts at the point 

where the heater joins the electrical 

circuit of the freezer in the evaporator 

compartment. Check the drain tube 

heater with an ohmmeter.

 

B.   If the drain tube heater is 

defective, disconnect the drain tube from 

the rigid plastic drain, bend the tabs that 

hold the evaporator drain pan to the 

evaporator cover and raise the drain pan 

so that the flexible heater is visible, pull 

heater out of the plastic drain tube and 

replace. Connect heater to the electrical 

circuit in the evaporator compartment.

5. Cabinet Temperature  

 

  Control

 

A.   Remove the two screws on the 

right side of the evaporator housing that 

holds the control mounting plate. Reach 

behind the evaporator housing on the 

control side of the cabinet and pull the 

control bulb out of the receptacle in 

the roof of the cabinet. Disconnect the 

wires from the control. Check control for 

continuity, replace if defective.

Summary of Contents for T-12FG

Page 1: ...eld Troubleshooting Freezer Units Only 25 26 Light Cover Install for T 12FG 27 Maintenance Care Cleaning Cleaning Condenser Coil 28 29 Stainless Steel Equipment Care Cleaning 30 31 Light Bulb Replacem...

Page 2: ...www truemfg com True Food Service Equipment Inc...

Page 3: ...ervice personnel Do not puncture refrigerant tubing Caution Risk of fire or explosion Flammable refrigerant used Consult repair manual owner s guide before attempting to service this product All safet...

Page 4: ...www truemfg com True Food Service Equipment Inc 2 2...

Page 5: ...helves in place so that children may not easily climb inside Refrigerant Disposal Your old refrigerator may have a cooling system that uses Ozone Depleting chemicals If you are throwing away your old...

Page 6: ...N At Receptacle Box 1 Turn breaker off 2 Disconnect all wires from receptacle 3 Insulate red wire tape or wire nut 4 Connect black white and green wires to 3 prong plug NEMA 5 20R per instructions on...

Page 7: ...is recommended for uncrating the unit A Remove the outer packaging cardboard and bubbles or styrofoam corners and clear plastic Inspect for concealed damage Again immediately file a claim with the fre...

Page 8: ...G REMOTE UNITS This section applies to remotes only Remote cabinets must be ordered as remote We do not recommend converting from a standard self contained to remote system All remote cabinets must be...

Page 9: ...inst the lower rail assembly see image 4 5 The bearing race on the castor or the top edge of the leg must make firm contact with the rail Unit leveling Four leveling shims have been provided for level...

Page 10: ...n with the hand brakes WARNING Unit may tip forward if procedure F is not strictly followed G Units final location should be adequately ventilated Conditions where heat exceeds 100 F require an exhaus...

Page 11: ...ons Doors can not be removed unless placed in specific locations stated in these instructions STEP 2 Two Door Units Slide the front door so it is centered on the cabinet The door can not be removed un...

Page 12: ...10 8 6 6 6 5 5 4 4 3 2 40 10 8 8 6 6 5 5 4 4 3 2 2 45 10 8 6 6 6 5 4 4 3 3 2 1 50 10 8 6 6 5 4 4 3 3 2 1 1 Wire Gauge for 2 Voltage Drop in Supply Circuits 230 Volts Distance In Feet To Center of Load...

Page 13: ...vel side to side and front to back Place a carpenter s level in the interior floor in four places A Position level in the inside floor of the unit near the doors Level should be parallel to cabinet fr...

Page 14: ...N Before loading product we recommend you run your TRUE unit empty for two to three days This allows you to be sure electrical wiring and installation are correct and no shipping damage has occurred R...

Page 15: ...www truemfg com True Food Service Equipment Inc 13 13 IF YOUR CABINET IS BUILT WITH THIS TEMPERATURE CONTROL PLEASE SEE THE FOLLOWING INSTRUCTIONS...

Page 16: ...temperature that will start the compressor Example If the Set Point is 9 F 23 C and the Differential is 10 F 5 C Set Point 9 F 10 Differential 1 F Or Set Point 23 C 5 Differential 18 C The compressor...

Page 17: ...lock settings If no appears the controller is unlocked If yes appears the controller is locked See images 3 and 4 C Once the lock setting has been set correctly release the info button Wait 5 seconds...

Page 18: ...interior sign lights by the interior door switch depress the rocker switch to the ON position Light Switch is located on inside top right of the ceiling ON Position Solid Door models lights are contr...

Page 19: ...ntrol Icons May need to unlock control WHY THE SET POINT IS THE TEMPERATURE AT WHICH THE COMPRESSOR WILL SHUT OFF Please note that the set point IS NOT the cabinet holding temperature HOW A To see the...

Page 20: ...the Manual Defrost button until dEF appears B REAL TIME CLOCK RTC If controller is preprogrammed for RTC press the and hold the Manual Defrost button for 5 seconds until dh1 appears Release the Manual...

Page 21: ...he set point press and hold the info button and the stand by button at the same time ScL will appear See image 1 B Push the up button until dFt appears See image 2 C Press and hold the info button to...

Page 22: ...www truemfg com True Food Service Equipment Inc 20 20 DISPLAY...

Page 23: ...228 DDY OS2 X 1 8 75 167 1 925 FID T3 80 176 1 669 FDD X 32 1 8 OS3 X 1 8 85 185 1 452 FTO TLD 90 194 1 268 FCM SIM 95 203 1 145 FDT X 1 8 ADR 100 212 0 974 FDH X 1 8 105 221 0 858 FT1 110 230 0 758...

Page 24: ...r housing along the interior ceiling Shelf Clip Shelf Shelf T Series GDM 5 Airflow Guard Pillaster WARNING Do not use pliers or any crimping tools when installing shelf clips Altering shelf clips in a...

Page 25: ...23F WARNING High usage high temperature and high humidity may require additional defrost settings per day Once clock is set grill is correctly reinstalled cabinet can be plugged in T 19F T 19FZ T 23F...

Page 26: ...ssary to warm up the set points To make the adjustment insert the appropriate tool in each adjustment screw and turn 1 4 of a revolution clockwise to the right This procedure will adjust both the cut...

Page 27: ...ually increase to infinity b If there is no movement of the ohmmeter indicator an open circuit is indicated c If the ohmmeter indicator moves to zero and remains there or on a low resistance reading a...

Page 28: ...the nameplate rating may indicate a broken suction reed or broken connecting rod in the compressor DIAGNOSIS AND REPLACEMENT OF FREEZER CABINET COMPONENTS 1 Defrost Time Clock A Check timer motor to b...

Page 29: ...rubber gasket and push rubber over the top lip of the lamp shield STEP 3 Be sure lamp cover is seated properly in rubber gasket IMPORTANT Before replacing light cover turn cabinet on and wait until i...

Page 30: ...anchoring compressor assembly to frame rails and carefully slide out tube connections are flexible Step 4 Clean off accumulated dirt from the condenser coil and the fan with a stiff bristle brush Step...

Page 31: ...abinet grill to expose the Condenser The Condenser looks like a group of vertical fins You need to be able to see through the condenser for the unit to function at maximum capacity Do not place filter...

Page 32: ...plastic scouring pad or soft cloth when you cannot see the grain 3 Use alkaline alkaline chlorinated or non chloride containing cleaners While many traditional cleaners are loaded with chlorides the...

Page 33: ...ituations environments of stainless steel A Soap ammonia and detergent medallion applied with a cloth or sponge can be used for routine cleaning B Arcal 20 Lac O Nu Ecoshine applied provides barrier f...

Page 34: ...must also be the same capacity as the drier being replaced 3 Micron level vacuums must be achieved to insure low moisture levels in the system 500 microns or lower must be obtained All claims for labo...

Reviews: