True T-12FG Installation Manual Download Page 27

............ www.truemfg.com ............

True Food Service Equipment, Inc.

25

25

INSTALLATION / OPERATION INSTRUCTIONS

IF THE COMPRESSOR WILL NOT RUN

1. If there is no voltage at the compressor 

terminals, follow the wiring diagram 

and check back from compressor to the 

power supply to find where the circuit is 

interrupted.

2. If power is available at the compressor 

terminals, and the compressor does not 

run, check the voltage at the compressor 

terminals while attempting to start the 

compressor.

If voltage at the compressor terminals is 

below 90% of the nameplate voltage, it 

is possible the motor may not develop 

sufficient torque to start. Check to 

determine if wire sizes are adequate, 

electrical connections are loose, the 

circuit is overloaded, or if the power 

supply is inadequate.

3. On single phase compressors, 

a defective capacitor or relay may 

prevent the compressor starting. If the 

compressor attempts to start but is 

unable to do so, or if there is a humming 

sound, check the relay to see if the relay 

contacts are damaged or fused. The relay 

points should be closed during the initial 

starting cycle, but should open as the 

compressor comes up to speed.

Remove the wires from the starting 

relay and capacitors. Use a high voltage 

ohmmeter to check for continuity 

throughout the relay coil. Replace 

the relay if there is not continuity. 

Use an ohmmeter to check across the 

relay contacts. Potential relay contacts 

are normally closed when the relay is 

not energized, current relay contacts 

are normally open. If either gives an 

incorrect reading, replace the relay.

Any capacitor found to be bulging, 

leaking, or damaged should be replaced.

Make sure capacitors are discharged 

before checking. Check for continuity 

between each capacitor terminal and the 

case. Continuity indicates a short, and 

the capacitor should be replaced. 

Substitute a “known to be good” start 

capacitor if available. If compressor then 

starts and runs properly, replace the 

original start capacitor.

If a capacitor tester is not available, an 

ohmmeter may be used to check run 

and start capacitors for shorts or open 

circuits. Use an ohmmeter set to its 

highest resistance scale, and connect 

prods to capacitor terminals.

 

a) With a good capacitor, the  

indicator should first move zero, and 

then gradually increase to infinity.

 

b) If there is no movement of the 

ohmmeter indicator, an open circuit is 

indicated.

 

c) If the ohmmeter indicator moves 

to zero, and remains there or on a low 

resistance reading, a short circuit is 

indicated. Defective capacitors should be 

replaced.

4. If the correct voltage is available 

at the compressor terminals, and no 

current is drawn, remove all wires from 

the terminals and check for continuity 

through the motor windings. On single 

phase motor compressors, check for 

continuity from terminals C to R, and 

C to S. On compressors with line break 

inherent protectors, an open overload 

protector can cause a lack of continuity. 

If the compressor is warm, wait one hour 

for the compressor to cool and recheck. 

If continuity cannot be established 

through all motor windings, the 

compressor should be replaced.

Check the motor for ground by means of 

a continuity check between the common 

terminal and the compressor shell. If 

there is a ground, replace the compressor.

5. If the compressor has an external 

protector, check for continuity through 

the protector or protectors. All external 

inherent protectors on compressors can 

be replaced in the field.

IF THE MOTOR COMPRESSOR STARTS 

BUT TRIPS REPEATEDLY ON THE 

OVERLOAD PROTECTOR

1. Check the compressor suction and 

discharge pressures while the compressor 

is operating. Be sure the pressures are 

within the limitations of the compressor. 

If pressures are excessive it may be 

necessary to clean the condenser, purge 

air from the system, replace crankcase 

pressure regulating valve.

An excessively low suction pressure may 

indicate a loss of charge.

On units with no service gauge parts 

where pressures can be checked, check 

condenser to be sure it is clean and fan 

is running. Excessive temperatures on 

suction and discharge line may also 

indicate abnormal operating conditions.

2. Check the line voltage at the motor 

terminals while the compressor is 

operating. The voltage should be within 

10% of the nameplate voltage rating. If 

outside those limits, the voltage supply 

must be brought within the proper 

range, or a motor compressor with 

different electrical characteristics must be 

used. 

3. Check the amperage drawn while the 

compressor is operating. Under normal 

operating conditions, the amperage 

drawn will seldom exceed 110% of the 

nameplate amperage. High amperage 

can be caused by low voltage, defective 

running capacitors, or a defective starting 
relay.

Continued on next page

Summary of Contents for T-12FG

Page 1: ...eld Troubleshooting Freezer Units Only 25 26 Light Cover Install for T 12FG 27 Maintenance Care Cleaning Cleaning Condenser Coil 28 29 Stainless Steel Equipment Care Cleaning 30 31 Light Bulb Replacem...

Page 2: ...www truemfg com True Food Service Equipment Inc...

Page 3: ...ervice personnel Do not puncture refrigerant tubing Caution Risk of fire or explosion Flammable refrigerant used Consult repair manual owner s guide before attempting to service this product All safet...

Page 4: ...www truemfg com True Food Service Equipment Inc 2 2...

Page 5: ...helves in place so that children may not easily climb inside Refrigerant Disposal Your old refrigerator may have a cooling system that uses Ozone Depleting chemicals If you are throwing away your old...

Page 6: ...N At Receptacle Box 1 Turn breaker off 2 Disconnect all wires from receptacle 3 Insulate red wire tape or wire nut 4 Connect black white and green wires to 3 prong plug NEMA 5 20R per instructions on...

Page 7: ...is recommended for uncrating the unit A Remove the outer packaging cardboard and bubbles or styrofoam corners and clear plastic Inspect for concealed damage Again immediately file a claim with the fre...

Page 8: ...G REMOTE UNITS This section applies to remotes only Remote cabinets must be ordered as remote We do not recommend converting from a standard self contained to remote system All remote cabinets must be...

Page 9: ...inst the lower rail assembly see image 4 5 The bearing race on the castor or the top edge of the leg must make firm contact with the rail Unit leveling Four leveling shims have been provided for level...

Page 10: ...n with the hand brakes WARNING Unit may tip forward if procedure F is not strictly followed G Units final location should be adequately ventilated Conditions where heat exceeds 100 F require an exhaus...

Page 11: ...ons Doors can not be removed unless placed in specific locations stated in these instructions STEP 2 Two Door Units Slide the front door so it is centered on the cabinet The door can not be removed un...

Page 12: ...10 8 6 6 6 5 5 4 4 3 2 40 10 8 8 6 6 5 5 4 4 3 2 2 45 10 8 6 6 6 5 4 4 3 3 2 1 50 10 8 6 6 5 4 4 3 3 2 1 1 Wire Gauge for 2 Voltage Drop in Supply Circuits 230 Volts Distance In Feet To Center of Load...

Page 13: ...vel side to side and front to back Place a carpenter s level in the interior floor in four places A Position level in the inside floor of the unit near the doors Level should be parallel to cabinet fr...

Page 14: ...N Before loading product we recommend you run your TRUE unit empty for two to three days This allows you to be sure electrical wiring and installation are correct and no shipping damage has occurred R...

Page 15: ...www truemfg com True Food Service Equipment Inc 13 13 IF YOUR CABINET IS BUILT WITH THIS TEMPERATURE CONTROL PLEASE SEE THE FOLLOWING INSTRUCTIONS...

Page 16: ...temperature that will start the compressor Example If the Set Point is 9 F 23 C and the Differential is 10 F 5 C Set Point 9 F 10 Differential 1 F Or Set Point 23 C 5 Differential 18 C The compressor...

Page 17: ...lock settings If no appears the controller is unlocked If yes appears the controller is locked See images 3 and 4 C Once the lock setting has been set correctly release the info button Wait 5 seconds...

Page 18: ...interior sign lights by the interior door switch depress the rocker switch to the ON position Light Switch is located on inside top right of the ceiling ON Position Solid Door models lights are contr...

Page 19: ...ntrol Icons May need to unlock control WHY THE SET POINT IS THE TEMPERATURE AT WHICH THE COMPRESSOR WILL SHUT OFF Please note that the set point IS NOT the cabinet holding temperature HOW A To see the...

Page 20: ...the Manual Defrost button until dEF appears B REAL TIME CLOCK RTC If controller is preprogrammed for RTC press the and hold the Manual Defrost button for 5 seconds until dh1 appears Release the Manual...

Page 21: ...he set point press and hold the info button and the stand by button at the same time ScL will appear See image 1 B Push the up button until dFt appears See image 2 C Press and hold the info button to...

Page 22: ...www truemfg com True Food Service Equipment Inc 20 20 DISPLAY...

Page 23: ...228 DDY OS2 X 1 8 75 167 1 925 FID T3 80 176 1 669 FDD X 32 1 8 OS3 X 1 8 85 185 1 452 FTO TLD 90 194 1 268 FCM SIM 95 203 1 145 FDT X 1 8 ADR 100 212 0 974 FDH X 1 8 105 221 0 858 FT1 110 230 0 758...

Page 24: ...r housing along the interior ceiling Shelf Clip Shelf Shelf T Series GDM 5 Airflow Guard Pillaster WARNING Do not use pliers or any crimping tools when installing shelf clips Altering shelf clips in a...

Page 25: ...23F WARNING High usage high temperature and high humidity may require additional defrost settings per day Once clock is set grill is correctly reinstalled cabinet can be plugged in T 19F T 19FZ T 23F...

Page 26: ...ssary to warm up the set points To make the adjustment insert the appropriate tool in each adjustment screw and turn 1 4 of a revolution clockwise to the right This procedure will adjust both the cut...

Page 27: ...ually increase to infinity b If there is no movement of the ohmmeter indicator an open circuit is indicated c If the ohmmeter indicator moves to zero and remains there or on a low resistance reading a...

Page 28: ...the nameplate rating may indicate a broken suction reed or broken connecting rod in the compressor DIAGNOSIS AND REPLACEMENT OF FREEZER CABINET COMPONENTS 1 Defrost Time Clock A Check timer motor to b...

Page 29: ...rubber gasket and push rubber over the top lip of the lamp shield STEP 3 Be sure lamp cover is seated properly in rubber gasket IMPORTANT Before replacing light cover turn cabinet on and wait until i...

Page 30: ...anchoring compressor assembly to frame rails and carefully slide out tube connections are flexible Step 4 Clean off accumulated dirt from the condenser coil and the fan with a stiff bristle brush Step...

Page 31: ...abinet grill to expose the Condenser The Condenser looks like a group of vertical fins You need to be able to see through the condenser for the unit to function at maximum capacity Do not place filter...

Page 32: ...plastic scouring pad or soft cloth when you cannot see the grain 3 Use alkaline alkaline chlorinated or non chloride containing cleaners While many traditional cleaners are loaded with chlorides the...

Page 33: ...ituations environments of stainless steel A Soap ammonia and detergent medallion applied with a cloth or sponge can be used for routine cleaning B Arcal 20 Lac O Nu Ecoshine applied provides barrier f...

Page 34: ...must also be the same capacity as the drier being replaced 3 Micron level vacuums must be achieved to insure low moisture levels in the system 500 microns or lower must be obtained All claims for labo...

Reviews: