background image

Nominal size

Nom-

inal

width

B

[mm]

Nom-

inal

height

H

[mm]

B1

[mm]

H1

[mm]

EN-Ex

EN-Ex-D

B2

[mm]

H2

[mm]

m

[kg]

B2

[mm]

H2

[mm]

m

[kg]

400  × 200

400

200

434

234

476

276

9

480

280

15

400  × 250

400

250

434

284

476

326

10

480

330

17

400  × 300

400

300

434

334

476

376

12

480

380

18

400  × 400

400

400

434

434

476

476

18

480

480

26

500  × 200

500

200

534

234

576

276

11

580

280

17

500  × 250

500

250

534

284

576

326

12

580

330

18

500  × 300

500

300

534

334

576

376

13

580

380

19

500  × 400

500

400

534

434

576

476

18

580

480

26

500  × 500

500

500

534

534

576

576

19

580

580

28

600  × 200

600

200

634

234

676

276

13

680

280

20

600  × 250

600

250

634

284

676

326

14

680

330

22

600  × 300

600

300

634

334

676

376

15

680

380

22

600  × 400

600

400

634

434

676

476

18

680

480

26

600  × 500

600

500

634

534

676

576

19

680

580

29

600  × 600

600

600

634

634

676

676

20

680

680

30

Installation

Installation orientation

Any installation orientation. Airflow direction is crit-
ical.

Upstream conditions

The volume flow rate accuracy of CAV controllers
applies to a straight upstream section of the duct.
Bends, junctions or a narrowing or widening of the
duct cause turbulence that may affect measure-
ment. Duct connections, e.g. branches off the main
duct, must comply with EN 1505. Some installation
situations require straight duct sections upstream.

Duct, horizontal

Duct, vertical

Bend

1,5B

B

Bend

1,5H

H

Junction

B

1,5B

Junction

1,5H

H

Installation

 

CAV controllers EN-Ex

5

Summary of Contents for EN-Ex

Page 1: ...Ex are used for con stant volume flow control in ventilation and air con ditioning systems They can be used for supply air and extract air systems in the following areas with potentially explosive atm...

Page 2: ...pecially trained for work in areas with potentially explosive atmospheres They know the rules and regulations relevant to their work and to explosion protection Evidence of the relevant experience and...

Page 3: ...carrying out any work Wear protective gloves safety shoes and a hard hat Please note Be careful when unloading or moving the product and pay attention to the symbols and information on the packaging...

Page 4: ...0 EN EX 400 x 200 B H 400 M8 B H H B Fig 3 EN Ex D with acoustic cladding Nominal size Nom inal width B mm Nom inal height H mm B1 mm H1 mm EN Ex EN Ex D B2 mm H2 mm m kg B2 mm H2 mm m kg 200 100 200...

Page 5: ...284 676 326 14 680 330 22 600 300 600 300 634 334 676 376 15 680 380 22 600 400 600 400 634 434 676 476 18 680 480 26 600 500 600 500 634 534 676 576 19 680 580 29 600 600 600 600 634 634 676 676 20 6...

Page 6: ...controller check it for damage that could impair the movement of the damper blade if the controller has been dam aged replace it Before you install the product take suitable precau tions to protect a...

Page 7: ...sized fixing material fixing material is not included in the supply package The product must remain accessible for main tenance even after installation Important If there is a risk that the controller...

Page 8: ...nectors part of the supply package on both sides to the ducting It is also possible to connect the controller directly to the terminal point for equipoten tial bonding of the building This requires a...

Page 9: ...G Risk of explosion Ignition sources such as sparks open flames or hot surfaces can lead to explosions in an area with potentially explosive atmospheres Get written permission before you start working...

Page 10: ...explosive atmosphere To remove any potentially explosive atmos phere purge the system with fresh air before you work on it Use only tools that have been approved for use in areas with potentially exp...

Page 11: ...ause malfunction damage to property and total failure of equipment Use only original replacement parts from TROX Cleaning Please note The cleaning intervals given in the VDI 6022 standard apply Clean...

Page 12: ...Declaration of conformity Declaration of conformity CAV controllers EN Ex 12...