Nominal size
Nom-
inal
width
B
[mm]
Nom-
inal
height
H
[mm]
B1
[mm]
H1
[mm]
EN-Ex
EN-Ex-D
B2
[mm]
H2
[mm]
m
[kg]
B2
[mm]
H2
[mm]
m
[kg]
400 × 200
400
200
434
234
476
276
9
480
280
15
400 × 250
400
250
434
284
476
326
10
480
330
17
400 × 300
400
300
434
334
476
376
12
480
380
18
400 × 400
400
400
434
434
476
476
18
480
480
26
500 × 200
500
200
534
234
576
276
11
580
280
17
500 × 250
500
250
534
284
576
326
12
580
330
18
500 × 300
500
300
534
334
576
376
13
580
380
19
500 × 400
500
400
534
434
576
476
18
580
480
26
500 × 500
500
500
534
534
576
576
19
580
580
28
600 × 200
600
200
634
234
676
276
13
680
280
20
600 × 250
600
250
634
284
676
326
14
680
330
22
600 × 300
600
300
634
334
676
376
15
680
380
22
600 × 400
600
400
634
434
676
476
18
680
480
26
600 × 500
600
500
634
534
676
576
19
680
580
29
600 × 600
600
600
634
634
676
676
20
680
680
30
Installation
Installation orientation
Any installation orientation. Airflow direction is crit-
ical.
Upstream conditions
The volume flow rate accuracy of CAV controllers
applies to a straight upstream section of the duct.
Bends, junctions or a narrowing or widening of the
duct cause turbulence that may affect measure-
ment. Duct connections, e.g. branches off the main
duct, must comply with EN 1505. Some installation
situations require straight duct sections upstream.
Duct, horizontal
Duct, vertical
Bend
1,5B
B
Bend
1,5H
H
Junction
B
1,5B
Junction
1,5H
H
Installation
CAV controllers EN-Ex
5